Cable types
Cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire
insulation at 40 °C (104 °F) ambient temperature. Not more than three current-
carrying conductors in raceway or cable or earth (directly buried). For other
conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
Copper cables with concentric copper shield
Max. load
Cable Entries
Input, DC link and motor cable (per phase) terminal sizes, accepted cable diameters
and tightening torques are given below
Frame size
Wire size
R5
10...2/0
R6
3/0 ... 350 MCM *
*
with cable lugs 6...2/0 AWG, tightening torque 14.8...29.5 lbf·ft
Dimensions, weights and noise
Frame size
Height
Drive
R5
32.03
R6
38.19
Package
R5
R6
Cable type
current
A
AWG/kcmil
31
44
57
75
88
101
114
132
154
176
202
224
250 MCM or 2 x 1
251
300 MCM or 2 x 1/0
273
350 MCM or 2 x 2/0
U1, V1, W1, U2, V2, W2, UDC+, UDC-
Wire Ø
(UL type 1)
AWG
in.
1.39
2.09
Width
in.
in.
10.43
11.81
42.72
15.75
45.08
15.75
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
00096931
.
Tightening
torque
lbf·ft
11.1
14.8...29.5
UL type 1
Depth
in.
15.35
17.28
21.61
23.03
Technical data 127
Grounding PE
Wire size
Tightening
torque
AWG
lbf·ft
10...2/0
11.1
5...4/0
5.9
Noise
Weight
lb
dB
143
70
220
73
11
9