LATCHING 3.1.2. EXTERNAL LED 3.2. CONNECTION BOX 3.3. ZONE LINE INPUT MOUNTING INSTALLATION AND WIRING 5.1. COMMON INSTALLATION (6295-6298) 5.2. INTRINSICALLY SAFE INSTALLATION (6295-6296) 5.2.1. RATING LABEL 5.2.2. CABLE GLAND TEST MODE TECHNICAL DATA 6295 TECHNICAL DATA 6296 TECHNICAL DATA 6297...
6295-6298 ENCLOSED HEAT DETECTOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 1. INTRODUCTION This document describes the enclosed heat detectors, type number 6295-6298. The document contains information about the product and instructions on how to mount and connect it.
6295-6298 ENCLOSED HEAT DETECTOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 3. GENERAL DESCRIPTION The heat detectors are conventional fixed temperature heat detectors. The detectors will give an alarm at a certain fixed tempera- ture (57 °C / 72 °C / 87 °C / 117 °C).
E- Ext. LED, for example Ext. indicator 2218; J2:3 (-) Do not connect an external indicator (LED) to terminals (E+, E-) when the detector is used as intrinsically safe detector in hazardous (Ex) areas, see 5.2. INTRINSICALLY SAFE INSTALLATION (6295-6296) on page 9.
6295-6298 ENCLOSED HEAT DETECTOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 4. MOUNTING The connection box must be mounted in the ceiling. Screws are not supplied. (Measure in mm) a) Cut out the required number of knockouts and apply the compression glands. Tighten the compression glands firmly.
6295-6298 ENCLOSED HEAT DETECTOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 5.2. INTRINSICALLY SAFE INSTALLATION (6295-6296) Screen wire termination is not provided. Interconnecting cable Alternative A Exp. Board 4580 Hazardous (Ex) area EX zone line input End-of-line device Galvanic Isolator / Barrier unit **...
Uo<=Ui (=30V) Io<=Ii (=40mA) Co > = Ci x 5 (15nF) Lo >= Li (0 H) 5.2.1. RATING LABEL Serial Number of type 6295/6296 is indicated on the rating label. SILVER GROUND PRINTED BLACK Running number (1-99999) Production month Production year 5.2.2.
6295-6298 ENCLOSED HEAT DETECTOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 6. TEST MODE For information about how to set a zone in test mode, see Planning Instructions or Operating Instructions. It is possible to use test equipment for testing, for example “SOLO” or “Testfire”.
7. TECHNICAL DATA 6295 All current consumptions are valid by nominal voltage and by 25 °C. Voltage: Allowed 12 – 30 V DC Normal 24V DC (Zone line voltage) Current: Quiescent 0 mA Active 35 mA Current limitation required when active...
6295-6298 ENCLOSED HEAT DETECTOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 8. TECHNICAL DATA 6296 All current consumptions are valid by nominal voltage and by 25 °C. Voltage: Allowed 12 – 30 V DC Normal 24V DC (Zone line voltage) Current:...
9. TECHNICAL DATA 6297 All current consumptions are valid by nominal voltage and by 25 °C. Voltage: Allowed 12 – 30 V DC Normal 24V DC (Zone line voltage) Current: Quiescent 0 mA Active 35 mA Current limitation required when active Must be minimum 6 and maximum 40 mA Alarm resistance 400 Ω...
6295-6298 ENCLOSED HEAT DETECTOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 10. TECHNICAL DATA 6298 All current consumptions are valid by nominal voltage and by 25 °C. Voltage: Allowed 12 – 30 V DC Normal 24V DC (Zone line voltage) Current:...
11. APPROVALS ENCLOSED HEAT DETECTOR 6295 Applicable directive/ Approval Applicable standards Notified body EN54-5 No. 2531-CPR-232.1192 EN61000-6-3 (Emission) Self declaration EN50130-4 (Immunity) RoHS EN IEC 63000 Self declaration EN IEC 60079-0 ATEX Self declaration EN 60079-11 ENCLOSED HEAT DETECTOR 6296...
Page 17
DOCUMENT NAME: TECHNICAL DESCRIPTION 6295-6298 DOCUMENT NUMBER: MEW01946 EN DATE OF ISSUE: 2016-01-11 REV: 4 DATE OF REVISION: 2022-09-13 Panasonic Fire & Security Europe AB Jungmansgatan 12 SE-211 11 Malmö Tel: +46 (0)40 697 70 00 www.panasonic-fire-security.com...