Honeywell QM100A1009 Instruction Sheet

Honeywell QM100A1009 Instruction Sheet

Modureg driver

Advertisement

Quick Links

APPLICATION
This analogic signal converter is intended to be used
to drive the Honeywell electric modulating regulators
Modureg series, which are used onboard of the VR400
valve series.
SPECIFICATION
GENERAL INSTRUCTIONS
Voltage supply : 110 Vac and 230 Vac,
50 / 60 Hz, -15%, +10%, 8 VA
Current consumption : 35 mA
Operating temperature : -10 / +60°C
EMC standard : EN 50081.1 / EN50082.2
Mounting : DIN rails TS 35 or TS 32
Connection technology : Screw terminals 0.5 / 2.5 mm
TECHNICAL DATA
Input
Voltage input : 0-10 Vdc, unipolar or bipolar
Maximum over voltage : 50 Vdc
Input impedance : 150 kOhm.
Current input versions : configurable 0 – 20 mA dc or 4 – 20
mA dc, unipolar or bipolar
Maximum overvoltage : 5 Vdc
Maximum overcurrent : 100 mA
QM100A1009
Input impedance : Typical 50 Ohm
Output
Current output : 16 – 165 mA, max load < 140 Ohm
Accurancy at 20°C : typical < +/- 0.1%, max +/- 0.2% of input
range
Stability : <0.025% from end value/°C
Response time : typical 200 ms
Status indication
LED INPUT : Green, power ON
STANDARDS AND APPROVALS
Noise emission and conduction
Noise immunity
Low Voltage Directve
Electro Magnetic Compatibility Directive
Voltage burst transient
INSTALLATION
See installation drawing on page 2.
IMPORTANT
1. Read these instructions carefully. Failure to follow the
instructions could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. The installation has to be carried out by qualified
personnel only.
4. Carry out through checkout when installation is
2
completed.
The modules must be installed, so that the ventilation holes
on both sides of the module lie in a vertical axis (standard
cabinet installation).
Furthermore, the ventilation holes must not be covered in
order to enable sufficient air flow through the module.
1
MODUREG DRIVER
INSTRUCTION SHEET
EN50 081.2
EN50 082.2
72/23/EEC
89/336/EWG
IEC 801-4,
EN 61000-4-4
EN1C-0006SZ20 R1203

Advertisement

loading

Summary of Contents for Honeywell QM100A1009

  • Page 1 IEC 801-4, EN 61000-4-4 APPLICATION INSTALLATION This analogic signal converter is intended to be used to drive the Honeywell electric modulating regulators See installation drawing on page 2. Modureg series, which are used onboard of the VR400 IMPORTANT valve series.
  • Page 2 DIMENSIONS ELECTRICAL CONNECTIONS Current Loop Converter Signal generator C(+) D(-) 4/20 Modureg EN1C-0006SZ20 R1203...
  • Page 3 MODUREG DRIVER SET UP INSTRUCTIO 1. 1. 1. 1. 1. Before wiring, adjust modureg zero and span using 3. 3. 3. 3. 3. Adjust the minimum outlet pressure through the mechanical mechanical adjustment screws. adjustment screw (9 mm brass nut). 1.1 Work on the 7 mm plastic nut for the span and on the 4 4 4 4 4 .
  • Page 4 Automation & Control Solutions Automation & Control Solutions Automation & Control Solutions Automation & Control Solutions Automation & Control Solutions Control Product Satronic AG Honeywell-Platz 1 CH-8157 Dielsdorf Phone: +41 1 855 22 11 Fax: +41 1 855 22 22 EN1C-0006SZ20 R1203...