To connect a heating circuit controller channel, press the channel selection
button (CH) to select a suitable channel (channels Y1 and Y2 with the
RRV912, channels Y1 - 8 with the RRV918). The LED of the selected channel
blinks. If the selected channel is not yet connected, the binding LED flashes.
If no button is pressed for 10 minutes, the heating circuit controller re-
turns to normal operation.
Press the function button on the heating circuit controller. The LED lights up
green. Release the button when the LED starts blinking.
The first channel of a room connected assumes lead control. The
other channels of the same room connected are controlled in parallel.
The heating circuit controller restarts after successful connection. The heating
circuit controller returns to channel selection mode and is ready for connecting
another channel.
Heating circuit controller RRV912 : At the controller outputs (Y1, Y2)
max. 4 2-position actuators can be connected
(max. 2 per controller output) or one 3-position actuator..
Heating circuit controller RRV918 : Max. 10 2-position actuators can
be connected (max 2 per controller output) at controller outputs
(Y1...Y8).
The thermal actuators used must adhere to the following limit values:
• Max. switch-on current 250 mA
• Max. rated current
Connect window contacts
The window/door contact wave AP 260 is ready to operate as soon as the in-
serted batteries supply power.
For detailed information, see the documentation for GAMMA wave
products.
The door/window contact is connected by pressing the function button on the
door/window contact for at least one second. After the learning telegrams are
sent, the LED blinks for about 3 seconds.
To confirm successful connection, the central apartment unit beeps.
Connect smoke detector (QAX913 only)
Smoke detectors are always assigned to a room during connection. Inform the
central apartment unit to which room you want to assign a smoke detector:
Main menu > Commissioning > RF connections
> Smoke detector > Room X > Connect device:
64 / 134
Siemens
Building Technologies
30 mA
Synco™ living
Commissioning the system
CE1C2740en
13.12.2010