1 General
The 5824 Serial/Parallel Printer Interface Module connects a compatible
fire alarm control panel (FACP) directly to a printer to print event his-
tory, system event logs, and detector statuses. This document is for quick
reference. For more information, refer to the FACP installation manual.
NOTE: Installation and wiring of this device must be
done in accordance with NFPA 72 and local ordinances.
2 Specifications
Operating Voltage
24 VDC
Current
50mA
(Alarm and Standby)
Max Per FACP
Addressable FACPs qty 4; 5208 FACP qty 1
Operating Temperature
32°F to 120°F (0°C to 49°C)
Max Wiring Distance
6000 ft. (1829 m)
from FACP
Mounting
Surface
Dimensions
6"W x 7-3/4"H x 1-7/16"D
(15.2 cm W x 19.7 cm H x 3.7 cm D)
Parallel Port
Ancillary
Serial Port
Primary Fire Signaling
3 Mounting
The 5824 ships in a plastic enclosure which must be mounted inside the
annunciator or accessory cabinet.
To mount the 5824 plastic enclosure into the appropriate cabinet:
1.
Remove the 5824 cover. Use a small screwdriver if necessary.
2.
Remove the 5824 circuit board from the base by pushing outward
on the base snap retaining tabs and lifting out the circuit board.
5824 Serial/Parallel Printer Interface Module
Product Installation Document
PN 151392:G5 2/2/2022 151062
.
Figure 1 5824 Circuit Board And Plastic Base
3.
Mount the plastic base into the appropriate accessory cabinet.
4.
Replace the circuit board in the plastic base.
NOTE: It may be necessary to connect the wiring to the
circuit board before the board is replaced into the base.
4 Wiring to a FACP
Terminate the wiring as shown in the diagram and table below.
–
+
A
-
+ A B
circuit board
snap retaining tabs
S-
S+
A
B
FACP
SBus
Connector
B
-
+
A
B
5824
Figure 2 Wiring the 5824 to the FACP
base