Input 1 Calibration Procedure - Honeywell UDC2800 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2800:
Table of Contents

Advertisement

Chapter 6 -  Input Calibration

Input 1 Calibration Procedure

104
Figure 6-5: Wiring Connections for 0 to 20 mA or 4 to 20 mA Inputs
Preliminary Steps
Apply power and allow the controller to warm up for 30 minutes
n
before you calibrate.
Before beginning the procedure, see
n
more information.
Make sure you have set Lockout to NONE in the Security set up
n
group. See Security Set Up Group for more information.
See the table
Voltage, Milliamp and Resistance Equivalents for
n
Input  Range Values
and 100 % range values.
CAUTION: For linear inputs, avoid step changes in inputs. Vary
smoothly from initial value to final 100 % value.
Input 1 Set up Wiring
for Voltage vs. Resistance equivalents or 0 %
for