IBM System Storage SAN Volume Controller Model 2145-CF8 Hardware Installation Guide V ersion 5. 1 .0 GC52-1356-01...
Page 3
IBM System Storage SAN Volume Controller Model 2145-CF8 Hardware Installation Guide V ersion 5. 1 .0 GC52-1356-01...
Page 4
Before using this information and the product it supports, read the information in the Safety and environmental notices and Notices, as well as the information in the IBM Environmental Notices and User Guide on the documentation CD. This edition applies to the IBM System Storage SAN Volume Controller Model 2145-CF8 running release 5.1.0 of IBM SAN Volume Controller software and to all subsequent releases and modifications until otherwise indicated in new editions.
Node status LED . 47 Chapter 2. Installing the SAN Volume Front-panel display . . 48 Controller 2145-CF8 hardware ..7 Navigation buttons . . 48 Preparing for the hardware installation SAN Volume Controller 2145-CF8 Optionally installing the redundant ac-power switch 11 operator-information panel .
Page 6
New Zealand compliance statement . . 62 European Union EMC Directive conformance Index ....67 statement . . 62 IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
. 14 Installing the SAN Volume Controller Positioned in rack . . 14 2145-CF8 node in the slide rails of the rack . . 31 Installing the support rails for a 2145 UPS-1U Raising the SAN Volume Controller 2145-CF8 into the rack .
Page 8
IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
. 43 Other IBM publications . . xviii Additional space requirements . . 43 IBM documentation and related Web sites Maximum heat output of each SAN Volume Cable-management arm and associated parts Controller 2145-CF8 node . . 43 descriptions and quantities .
Page 10
IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
A danger notice indicates the presence of a hazard that has the potential of causing death or serious personal injury. (D002) 2. Locate IBM Systems Safety Notices with the user publications that were provided with the SAN Volume Controller hardware.
7. Correct any problems that you find. Internal device checks Ensure that you perform an internal device check before you install or service the SAN Volume Controller. IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
To conduct the internal device check, perform the following steps: 1. Check for any non-IBM changes that might have been made to the device. If any are present, obtain the “Non-IBM Alteration Attachment Survey,” form number R009, from the IBM branch office. Complete the form and return it to the branch office.
Use caution when working in a potential safety hazard that is not covered in the safety checks. If unsafe conditions are present, determine how serious the hazards are and whether you can continue before you correct the problem. IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Product recycling and disposal Ensure that you are aware of the materials that must be recycled. Before using this information and the product that it supports, read the IBM Environmental Notices and User Guide on the SAN Volume Controller Documentation CD.
Page 16
IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Who should use this guide The intended audience for this guide is the IBM service representative. This guide should be read by the IBM service representative who is responsible for the initial installation of the SAN Volume Controller hardware, including the redundant ac-power switch and the uninterruptible power supply.
SAN Volume Controller. SAN Volume Controller Information Center The IBM System Storage SAN Volume Controller Information Center contains all of the information that is required to install, configure, and manage the SAN Volume Controller. The information center is updated between SAN Volume Controller product releases to provide the most current documentation.
Table 1. SAN Volume Controller library (continued) Title Description Order number IBM System Storage SAN This guide provides the GC27-2221 Volume Controller Models instructions that the IBM 2145-8F2 and 2145-8F4 service representative uses to Hardware Installation Guide install the hardware for SAN Volume Controller models 2145-8F2 and 2145-8F4.
IBM Systems Safety Notices document. Other IBM publications Table 2 lists IBM publications that contain information related to the SAN Volume Controller. Table 2. Other IBM publications Title Description Order number...
IBM documentation and related Web sites Table 3 lists Web sites that provide publications and other information about the SAN Volume Controller or related products or technologies. Table 3. IBM documentation and related Web sites Web site Address Support for SAN Volume Controller www.ibm.com/storage/support/2145...
Some publications are available for you to view or download at no charge. You can also order publications. The publications center displays prices in your local currency. You can access the IBM Publications Center through the following Web site: www.ibm.com/shop/publications/order/...
SAN Volume Controller installation and configuration overview The installation and configuration of a SAN Volume Controller cluster requires the completion of various tasks, some of which are normally completed by an IBM service representative. Additional publications are included with some of the hardware components;...
Page 24
Controller cluster, host systems, and storage controllers plan. This task helps to assure a seamless configuration. For more information, see Chapters 3 and 4 of the IBM System Storage SAN Volume Controller Planning Guide. 3. Complete all physical planning charts.
Page 25
Configuration tasks To configure a SAN Volume Controller cluster, you must complete the following tasks or have them completed by an IBM service representative or IBM Business Partner: 1. Register your product. To receive product support notifications from IBM, you must register your product.
Page 26
IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Minimum of one pair of SAN Volume Controller nodes v Minimum of two uninterruptible power supply units v One IBM System Storage Productivity Center or one master console per SAN installation for configuration SAN Volume Controller 2145-CF8 node features...
Figure 2 on page 3 shows an example of the main wiring for a SAN Volume Controller cluster with the redundant ac-power switch feature. The four-node cluster consists of two I/O groups: IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
v I/O group 0 contains nodes A and B v I/O group 1 contains nodes C and D Figure 2. A four-node SAN Volume Controller cluster with the redundant ac-power switch feature 1 I/O group 0 2 SAN Volume Controller node A 3 2145 UPS-1U A 4 SAN Volume Controller node B 5 2145 UPS-1U B...
2145 UPS-1U, as shown by node A and node B. The SAN Volume Controller 2145-CF8 is an example of a node that has two power supplies. The SAN Volume Controller 2145-8A4 is an example of a node that has a single power supply.
Page 31
in the I/O group stops and the SAN Volume Controller cluster can continue to operate, although with reduced performance. Each uninterruptible power supply must be in the same rack as the node that it powers. Each 2145 UPS-1U includes one power cord that connects the uninterruptible power supply to a redundant ac-power switch, if one exists, or to a rack power distribution unit (PDU), if one exists.
Page 32
IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Chapter 2. Installing the SAN Volume Controller 2145-CF8 hardware There are several steps that you must perform to prepare, and then install the SAN Volume Controller hardware. To install the SAN Volume Controller hardware, perform the following tasks in order.
Figure 3. Parts provided for SAN Volume Controller 2145-CF8 hardware installation in a rack 1 SAN Volume Controller node 2 SAN Volume Controller support rails (2) 3 2145 UPS-1U 4 2145 UPS-1U support rails (2) 5 Power and signal cable assembly...
Page 35
Feature code 0010: initial SAN Volume Controller 2145-CF8 software preinstalled on feature code 3001 and 3002 v One of the following: – Feature code 3001: initial SAN Volume Controller 2145-CF8 node, quantity – Feature code 3002: additional SAN Volume Controller 2145-CF8 node, quantity 1...
Page 36
Feature codes 3001 and 3002 ship the same parts. Verify that you have the following parts: – SAN Volume Controller 2145-CF8 node – Part number 49Y4827: SAN Volume Controller 2145-CF8 Support rail kit, quantity 1 – Part number 49Y4831: SAN Volume Controller 2145-CF8 Cable-management arm assembly, quantity 1 –...
Use the redundant ac-power switch to make the SAN Volume Controller cluster more resilient to power failure. DANGER Multiple power cords: The product is equipped with multiple power cords. To remove all hazardous voltages, disconnect all power cords. (L003) Chapter 2. Installing the SAN Volume Controller 2145-CF8 hardware...
Figure 4. Attaching the mounting plates Labeling the cables You must label each end of the two redundant ac-power switch input-power cables before you connect the input-power cables to the redundant ac-power switch. IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
2. Position the four “C” clips in the rack’s mounting bar, as shown in Figure 6 on page 14. Chapter 2. Installing the SAN Volume Controller 2145-CF8 hardware...
4. Verify that the redundant ac-power switch power cables are tidy. Ensure that they do not obstruct other equipment and that they are tied in place where necessary. IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Complete the following steps to install the 2145 UPS-1U: 1. Install the support rails for the 2145 UPS-1U. 2. Install the 2145 UPS-1U in the rack. 3. Install the 2145 UPS-1U cable-retention bracket. Chapter 2. Installing the SAN Volume Controller 2145-CF8 hardware...
Front Rear Figure 9. Adjusting the rail depth on the 2145 UPS-1U 1 Assembly wing nuts IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
9. Tighten the assembly wing nuts on both rail assemblies. Installing the 2145 UPS-1U in the rack After you have completed the preparation procedures, you are ready to install the 2145 UPS-1U in the rack. Chapter 2. Installing the SAN Volume Controller 2145-CF8 hardware...
Page 44
2. At the front of the 2145 UPS-1U, install the two mounting screws (M6x10) 1 as shown in Figure 12 on page 19. IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
2145 UPS-1U front panel, shown in Figure 13, by pushing the panel to the left and then pulling it forward. Figure 13. Removing the 2145 UPS-1U front panel 4. Remove the protective label from the internal battery connector (shown in Figure 14 on page 20). Chapter 2. Installing the SAN Volume Controller 2145-CF8 hardware...
The power socket is shown by 1 in Figure 16 on page 21. The 2145 UPS-1U is in standby mode; so all indicators are off. Connect each 2145 UPS-1U for an I/O group to a different power source. IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
SAN Volume Controller has been connected to this 2145 UPS-1U and turned on. 9. Repeat all of these steps to install additional 2145 UPS-1U units. Chapter 2. Installing the SAN Volume Controller 2145-CF8 hardware...
4. Position the bracket with the power cable protruding through the rightmost slot in the bracket. 5. Secure the bracket in place with one screw on each side, as shown in Figure 19. Figure 19. 2145 UPS-1U power cable-retention bracket IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
4. Connecting the SAN Volume Controller 2145-CF8 node to the uninterruptible power supply. Installation guidelines Before you install the support rails for the SAN Volume Controller 2145-CF8 node, review the following guidelines: v Do not install a unit in a rack where the internal-rack ambient temperature exceeds the lowest manufacturer-recommended ambient temperature for all of your rack-mounted devices.
Figure 20. SAN Volume Controller 2145-CF8 cable-management arm, support rails, and associated parts Table 4. Cable-management arm and associated parts descriptions and quantities Reference Description Quantity Slide rail (left) Slide rail (right) Large cable tie Cable ties M6 screws 10-32 screws...
If a thumbscrew is installed in the slide rail 3 , remove it. Figure 21. Installing the SAN Volume Controller 2145-CF8 slide rails on the rack 3. Install the rear of the rail into the rear of the rack.
Figure 22. Installing the rear of a SAN Volume Controller 2145-CF8 slide rail in the rear of the rack 4. Install the front of the rail into the front of the rack. a. Pull the slide rail forward. b. Insert the two pins on the front of the rail, as shown by 1 in Figure 23, into the two lower holes in the U on the front of the rack.
2 toward the rack. Figure 24. Rack rear: Attaching the SAN Volume Controller 2145-CF8 cable-management support arm 3. Install the L-shaped cable-management stop bracket, as shown by 1 in Figure 25 on the unattached end of the support arm.
Figure 26. Attaching the free end of the SAN Volume Controller 2145-CF8 support arm 5. To install the cable-management arm assembly, you must place the cable-management arm mounting bracket into the same slide rail onto which you installed the cable-management support arm.
Figure 28. SAN Volume Controller 2145-CF8 cable-management arm on the support arm 7. Slide the SAN Volume Controller 2145-CF8 into the rack until it latches into place. 8. Attach the power-and-serial-cable bundle, the fibre-channel cables, and the one or two Ethernet cables to the rear of the node.
To install the SAN Volume Controller 2145-CF8 node in the rack, perform the following steps: 1. Place the SAN Volume Controller 2145-CF8 in the rails on the rack.
Figure 30. Installing the SAN Volume Controller 2145-CF8 node in the slide rails of the rack 2. Lift the locking levers on the slide rails and push the node 2 all the way into the rack until it clicks into place.
Perform the following steps to connect the SAN Volume Controller to the 2145 UPS-1U: 1. At the back of the SAN Volume Controller 2145-CF8 node, plug the power cables of the combined power and serial cable assembly into the power connector 2 , as shown in Figure 32.
2 in Figure 33. 3. Push both the bracket and the cable toward the SAN Volume Controller 2145-CF8 power supply ( 2 ), carefully aligning the power cord with the power connector on the power supply and the bracket with the power-supply handle.
If only one cable is connected, the cable must be connected to Ethernet port 1. To connect the SAN Volume Controller 2145-CF8 to the SAN and to the Ethernet network, perform the following steps: 1. Connect the Ethernet cables to Ethernet port 1, as shown by 8 in Figure 34 and Ethernet port 2 ( 7 ).
Verify that the green power LED is lit. If the LED is not illuminated, see MAP 5000: Start in the IBM System Storage SAN Volume Controller Troubleshooting Guide to repair the problem.
Figure 37 shows how the node number is displayed on the front panel. If the node number is not the same, contact the IBM Support Center.
Page 63
10. Check whether the second line of the front-panel display shows the message Active. If Active is not shown on the second line, go to MAP 5600: Fibre channel in the IBM System Storage SAN Volume Controller Troubleshooting Guide to repair the fault.
Page 64
IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
To print the current page or active frame, press Ctrl+P. v To select, press Enter. Accessing the publications You can find the HTML version of the IBM System Storage SAN Volume Controller information at the following Web site: http://publib.boulder.ibm.com/infocenter/svcic/v3r1m0/index.jsp You can access this information using screen-reader software and a digital speech synthesizer to hear what is displayed on the screen.
Page 66
IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Appendix B. SAN Volume Controller physical installation planning Before the IBM service representative can set up your SAN Volume Controller environment, you must verify that the prerequisite conditions for the SAN Volume Controller, the uninterruptible power supply, and optional redundant ac-power switch installation are met.
(-4°F to 140°F) (0 ft to 34991 ft) condensing, but no precipitation Preparing your environment The following tables list the physical characteristics of the SAN Volume Controller 2145-CF8 node. IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Cable exit Maximum heat output of each SAN Volume Controller 2145-CF8 node The node dissipates the following maximum heat output. Table 10. Maximum heat output of each SAN Volume Controller 2145-CF8 node Model Heat output per node SAN Volume Controller 2145-CF8...
The following tables describe the physical characteristics of the 2145 UPS-1U. 2145 UPS-1U dimensions and weight Ensure that space is available in a rack that is capable of supporting the 2145 UPS-1U. IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Height Width Depth Maximum weight 44 mm 439 mm 579 mm 16 kg (1.73 in.) (17.3 in.) (22.8 in.) (35.3 lb) Note: The 2145 UPS-1U package, which includes support rails, weighs 18.8 kg (41.4 lb). Heat output The 2145 UPS-1U unit produces the following approximate heat output. Heat output during normal Heat output during battery Model...
Page 72
2.8 m (9 ft) SI 32 39M5172 Liechtenstein, Switzerland 2.8 m (9 ft) IEC 60884 Stnd. 39M5158 Sheet 416534?2 (CH Type 12) Thailand 2.8 m (9 ft) NEMA 6-15P 39M5095 IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Figure 39 shows the controls and indicators on the front panel of the SAN Volume Controller 2145-CF8. Figure 39. SAN Volume Controller 2145-CF8 front panel 1 Node-status LED 2 Front-panel display 3 Navigation buttons...
LEDs that indicate information such as system-board errors, hard-drive activity, and power status. Figure 40 on page 49 shows the operator-information panel for the SAN Volume Controller 2145-CF8. IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Note: See MAP 5800: Light path to help you isolate the faulty FRU. Release latch The release latch on the SAN Volume Controller 2145-CF8 gives you access to the light-path diagnostics panel, which provides a method for determining the location of a problem.
To turn off the power, press and release the power button. For more information about how to turn off the SAN Volume Controller node, see “MAP 5350: Powering off a SAN Volume Controller node” in the IBM System Storage SAN Volume Controller Troubleshooting Guide.
The rear-panel indicators consist of LEDs that indicate the status of the fibre-channel ports, Ethernet connection and activity, power, electrical current, and system-board errors. Figure 41 shows the rear-panel indicators on the SAN Volume Controller 2145-CF8 back-panel assembly. Figure 41. SAN Volume Controller 2145-CF8 rear-panel indicators...
The ac, dc, and power-supply error LEDs indicate whether the node is receiving electrical current. Figure 42 shows the location of the SAN Volume Controller 2145-CF8 ac, dc, and power-supply error LEDs. Figure 42. SAN Volume Controller 2145-CF8 ac, dc, and power-error LEDs Each of the two power supplies has its own set of LEDs.
An Ethernet-link LED is located beside each Ethernet port. Ethernet-activity LED An Ethernet-activity LED beside each Ethernet port indicates that the SAN Volume Controller 2145-CF8 is communicating on the Ethernet network that is connected to the Ethernet port. SAN Volume Controller 2145-CF8 connectors External connectors that the SAN Volume Controller 2145-CF8 uses include four fibre-channel ports, a serial port, two Ethernet ports, and two power connectors.
Figure 44. Power connector SAN Volume Controller 2145-CF8 ports used during service procedures The SAN Volume Controller 2145-CF8 contains a number of ports that are only used during service procedures. Figure 45 shows ports that are used only during service procedures.
The physical port numbers are 1 - 4, counting from the left side to the right side when you view the rear panel of the SAN Volume Controller 2145-CF8. Figure 47 provides a view of the rear of the SAN Volume Controller 2145-CF8. Figure 47. Physical fibre-channel port numbers for the SAN Volume Controller 2145-CF8...
Page 82
Green Either on Green Beeps for Overload while on line or off one second and then stops Amber Beeps for Overload while on one second battery and then stops IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Table 12. 2145 UPS-1U error indicators (continued) [1] Load2 [2] Load1 [3] Alarm [4] Battery Overload Power-on Buzzer Error condition Either on Either on Flashing Green Solid on Fan failure or off or off Either on Either on Flashing Amber Solid on Battery test fail or off...
Use the test and alarm reset button to start the self-test. To start the self-test, press and hold the test and alarm reset button for three seconds. This button also resets the alarm. IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Web sites. The materials at those Web sites are not part of the materials for this IBM product and use of those Web sites is at your own risk.
Page 86
IBM may use or distribute any of the information you supply in any way it believes appropriate without incurring any obligation to you. Licensees of this program who wish to have information about it for the purpose of enabling: (i) the exchange of information between independently created...
IBM, therefore, cannot guarantee or imply reliability, serviceability, or function of these programs. The sample programs are provided ″AS IS″, without warranty of any kind. IBM shall not be liable for any damages arising out of your use of the sample programs.
Such cables and connectors are available from IBM authorized dealers. IBM cannot accept responsibility for any interference caused by using other than recommended cables and connectors. IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Klasse A ein. Um dieses sicherzustellen, sind die Geräte wie in den Handbüchern beschrieben zu installieren und zu betreiben. Des Weiteren dürfen auch nur von der IBM empfohlene Kabel angeschlossen werden. IBM übernimmt keine Verantwortung für die Einhaltung der Schutzanforderungen, wenn das Produkt ohne Zustimmung der IBM verändert bzw.
U.K. under approval number NS/G/1234/J/100003 for indirect connection to public telecommunications systems in the United Kingdom. Korean Class A Electronic Emission Statement Taiwan Class A compliance statement IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Fax: 0049 (0)711 785 1283 e-mail: mailto:tjahn@de.ibm.com Taiwan Contact Information This topic contains the product service contact information for Taiwan. IBM Taiwan Product Service Contact Information: IBM Taiwan Corporation 3F, No 7, Song Ren Rd., Taipei Taiwan Tel: 0800-016-888 Notices...
Page 92
IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
2145 UPS-1U 31 cable retention bracket 22 cable retention brackets redundant ac power switch 11 configuration 4 SAN Volume Controller 2145-CF8 33 Deutschsprachiger EU Hinweis 63 connecting 31 cable-management arm display on front panel controls and indicators on the front...
Page 94
SAN Volume Controller 2145-CF8 51 charts and tables 7 planning for SAN Volume system information 49 tables and charts 7 Controller 41 system-error 49, 52 preparing for 7 legal notices 59 IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Page 95
54 SAN (storage area network) Ethernet 53 specifications 41 connecting to 34 SAN Volume Controller 2145-CF8 53 support rails 23 SAN Volume Controller power temperature with redundant ac checking grounding xi button 50 power 42...
Page 96
SAN Volume Controller 2145-CF8 54 verifying installation SAN Volume Controller 2145-CF8 35 Web sites xix who should read this guide xv IBM System Storage SAN Volume Controller: Model 2145-CF8 Hardware Installation Guide...
Page 97
IBM business partner, or your authorized remarketer. When you send comments to IBM, you grant IBM a nonexclusive right to use or distribute your comments in any way it believes appropriate without incurring any obligation to you. IBM or any other organizations will only use the personal information that you supply to contact you about the issues that you state on this form.
Page 98
Readers’ Comments — We’d Like to Hear from You Cut or Fold Along Line GC52-1356-01 Fold and Tape Please do not staple Fold and Tape _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ NO POSTAGE NECESSARY IF MAILED IN THE...
Page 100
Part Number: 31P1135 Printed in USA GC52-1356-01...