B.4: Configuring Annunciators For The Afp-200 - Honeywell NOTIFIER ACS Series Manual

Annunciator control system
Table of Contents

Advertisement

AFP-200 Systems (UL 8th)
B.4 Configuring Annunciators for the AFP-200
The switch numbers given below are for SW28 on the ACM-24AT and ACM-48A, and for the 8-pin DIP switch on the ACM-16AT and
ACM-32A. Address and DIP switches must be set before the annunciator will operate properly. See Section 5.2 for switch locations.
Switch
#
1
Not used: This switch must be set "OFF"
2, 3
Expanders installed: Set these switches according to how many expanders are installed at the address. See Section 5.12.3,
"Configuring Number of Expander Modules" for ACM-24AT/ACM-48A; see Section 5.13.3, "Configuring Number of Expander
Modules" for ACM-16AT/ACM-32A.
4
Not used; set to OFF
5
Receive Only: Set this switch "ON" for each annunciator that will provide the same information as another annunciator in a
different location. (When two or more annunciators hold the same address, all but one must be configured as "Receive Only"
annunciators.)
6
Piezo Disable: Set this switch "ON" to disable the piezo from sounding for any event. (The piezo will also be disabled if Flash
Inhibit is "ON".)
7
Switch Inhibit: Set this switch "ON" to disable the point control switches on the annunciator and prevent them from executing
system control functions. When inhibited, the switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by the system.
NOTE: Only the first four switches control the AFP-200. Their functions are: 1=Acknowledge 2=Signal Silence, 3=System Reset,
4=Drill.
8
Flash Inhibit: Set this switch "ON" to disable the flashing of LEDs associated with unacknowledged events. Flash Inhibit also
disables the piezo from sounding.
1
For ACM-24AT and ACM-48A with AFP-200, set all pins on SW32 to "OFF".
34
1
ACM-24AT and ACM-48A
ACM-16AT and ACM-32A Function
Eight-Point Shift: Set switch "ON" to shift the control panel functions from the
first eight annunciator positions to expander positions 57-64. This shift can
only be set on an annunciator set for address "1".
Configuring Annunciators for the AFP-200
ACS Manual — P/N 15842:N3 5/4/2022