Ann-Rly Annunciator Module - Honeywell FIre-LITe ALArms MS-9600LS Manual

Addressable fire alarm control panel
Hide thumbs Also See for FIre-LITe ALArms MS-9600LS:
Table of Contents

Advertisement

Product Description
ANN-LED Board Layout and Connection to FACP
Figure 1.13 illustrates the ANN-LED board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
Address DIP switch

ANN-RLY Annunciator Module

The ANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.
Specifications
Operating Voltage: 24 VDC
Max. Current:
Alarm: 75 mA
Standby: 15 mA
Relay Contact Ratings
2 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Operating Temperature: 32
For indoor use in a dry location only
36
1 2 3 4 5 6 7 8
ANN-BUS
TB1
ANN-LED
+24 VDC
-24 VDC
+ - + - + -
TB3
FACP
Figure 1.13 ANN-LED Connection to FACP
o
o
F to 120
F (0
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS/
ACS BUS
TB1
TB5
TB4
TB6
JP8
JP5
o
o
C to 49
C)
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010