hit counter script

Cable; Selecting The Correct Instrumentation Cable - Siemens SITRANS LC500 Operating Instructions Manual

Capacitance transmitters
Table of Contents

Advertisement

Voltage drop versus mA for current transmitter operation
Examples:
With a 250 Ohm sensing resistor, no barrier and negligible cable resistance, the
overall supply voltage should be at least 15.0 V.
With a 250 Ohm sensing resistor, a barrier of 280 Ohm, and 20 Ohm cable
resistance (500 m), the total resistance is 550 Ohm, so the overall supply voltage
should be at least 20.5 Volts.
For a multi-drop application, where the measuring supply is fixed to 4 mA, the
voltage on the terminals of the SITRANS LC500 should be at least 12 Volts.
The loop circuit is completely isolated from the measurement circuit. It is designed so that
the internal capacitance and inductance on the terminals are isolated and do not factor
in safety calculations.

Cable

Notes:
To maintain reliable transfer of the HART modem signals, the RC
the connections should be less than 65 μSec. .
For output signals (from the SITRANS LC500), only the cable and barrier
resistance are relevant. For input signals the measurement resistance is also
relevant.
Use twisted pair cable, screened as a pair.
1.
RC = Resistance x Capacitance
2.
Or, if you use a common screen over a cable containing multiple twisted pairs,
do not use other pairs for signals that could interfere with HART signals.

Selecting the correct instrumentation cable

you need to know the cable length and the measurement resistance
select a cable that will give you a capacitance time constant of less than 65 μSec
7ML19985GE04
SITRANS LC500 – OPERATING INSTRUCTIONS
voltage drop over 250 ohm
measuring resistance
voltage drop over 280 ohm in
barrier
voltage drop over blocking
diode in barrier
margin or voltage drop over
instrument cable
operation voltage,
transmitter
mA
1
2
time constant of
Page 25

Advertisement

Table of Contents
loading

Table of Contents