Installation Guide Sensepoint Plus, Sensepoint Pro, Series 3000 XPIS and Sensepoint XCD Duct Mounting Kit...
Page 2
Sensepoint Plus, Sensepoint Pro, Series 3000 XPIS and Sensepoint XCD Duct Mounting Kit Issue 3 07/2009 MAN0639 Warning A gas detector calibrated at 0.3l/m in static air will read high at elevated flow rates. This is a ‘fail safe’ effect that naturally occurs in duct applications. Elevated flow rates effectively make the detector more sensitive.
Page 3
Sensepoint Plus, Sensepoint Pro, Series 3000 XPIS and Sensepoint XCD Duct Mounting Kit Issue 3 07/2009 MAN0639 Assembling Duct Components Drill a 100 mm diameter hole in the target duct wall. Drill 4 x 10 mm equidistant holes around it. (use the part-duct as a template). Align the Gasket over the holes.
Page 4
Sensepoint Plus, Sensepoint Pro, Series 3000 XPIS and Sensepoint XCD Duct Mounting Kit Issue 3 07/2009 MAN0639 Assembling Detector Components Fit the Detector to the Mounting Plate. Screw the detector firmly into the plate mounting hole in a clockwise direction. Fit the Sensor Retainer to the Detector. NOTE THAT THE DETECTOR SHOWN IS SENSEPOINT PRO SENSEPOINT PLUS, SERIES 3000 XPIS AND SENSEPOINT XCD FIT IN...
Sensepoint Plus, Sensepoint Pro, Series 3000 XPIS and Sensepoint XCD Duct Mounting Kit Issue 3 07/2009 MAN0639 Mounting the Detector Assembly to the Duct Assembly Place the Detector Assembly onto the Duct Assembly Retaining Plate fitted to the duct. NOTE THAT THE DETECTOR SHOWN IS SENSEPOINT PRO SENSEPOINT PLUS, SERIES 3000 XPIS AND SENSEPOINT XCD FIT...