hit counter script
Mitsubishi Electric Lossnay LGH-100RX3-CAN Technical Manual

Mitsubishi Electric Lossnay LGH-100RX3-CAN Technical Manual

Hide thumbs Also See for Lossnay LGH-100RX3-CAN:
Table of Contents

Advertisement

TECHNICAL MANUAL FOR CANADA
Models
Lossnay Unit
LGH-50RX
-CAN
3
LGH-100RX
LGH-200RX
Lossnay Remote Controller
PZ-41SLB-E
PZ-52SF-E
-CAN
3
-CAN
3

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric Lossnay LGH-100RX3-CAN

  • Page 1 TECHNICAL MANUAL FOR CANADA Models Lossnay Unit LGH-50RX -CAN LGH-100RX -CAN LGH-200RX -CAN Lossnay Remote Controller PZ-41SLB-E PZ-52SF-E...
  • Page 2: Table Of Contents

    CONTENTS Lossnay Unit CHAPTER 1 Ventilation for Healthy Living Necessity of Ventilation ............................Ventilation Standards ............................Ventilation Method .............................. Ventilation Performance ............................Outdoor Air (ventilation) Load ..........................10 CHAPTER 2 Lossnay Construction and Principle Construction and Features of Lossnay ......................16 Construction and Principle of Core ........................
  • Page 3 CHAPTER 6 Examples of Lossnay Applications Large Office Building ............................66 Medium Size Office Building ..........................69 Urban Small-Scale Building ..........................73 Hospitals ................................74 Schools ................................76 Public Halls (combination facilities such as day-care centres) ................78 CHAPTER 7 Installation Considerations ....................
  • Page 4: Lossnay Unit

    Lossnay Unit CHAPTER 1 Ventilation for Healthy Living...
  • Page 5: Necessity Of Ventilation

    CHAPTER 1 Ventilation for Healthy Living Fresh outdoor air must be introduced constantly at a set ratio in an air conditioning system. This fresh air is introduced to be mixed with the return air from the room, to adjust the temperature and humidity, supply oxygen, reduce body and other odors, remove tobacco smoke and to increase the cleanness of the air.
  • Page 6 CHAPTER 1 Ventilation for Healthy Living In the case of Japan, an Instruction Guideline based on these regulations has been issued, and unified guidance is carried out. Part of the Instruction Guideline regarding ventilation is shown below. The fresh outdoor air intake must be 10 m or higher from ground level, and be distanced appropriately from the exhaust air outlet.
  • Page 7: Ventilation Standards

    CHAPTER 1 Ventilation for Healthy Living Effect of carbon dioxide (CO Concentration (%) Effect of concentration changes 0.03 (0.04) Standard atmosphere. 0.04 - 0.06 City air. 0.07 Tolerable concentration when many people stay for long time. There is no toxic level in alone.
  • Page 8: Ventilation Method

    CHAPTER 1 Ventilation for Healthy Living 3. Ventilation Method 3.1 Ventilation class and selection points An appropriate ventilation method must be selected according to the purpose. Ventilation is composed of “Supply air” and “Exhaust air” functions. These functions are classified according to natural flow or mechanical ventilation using a fan (forced ventilation).
  • Page 9 CHAPTER 1 Ventilation for Healthy Living 3.2 Comparison of ventilation methods There are two main types of ventilation methods. Centralized ventilation method This is mainly used in large buildings, with the fresh outdoor air intake being installed in one machine room. For this method, primary treatment of the fresh outdoor air, such as heat recovery to the intake air and dust removal is performed being distribution to the building by ducts.
  • Page 10 CHAPTER 1 Ventilation for Healthy Living Comparison of centralised ventilation method and independent zoned ventilation method Centralized ventilation method Independent zoned ventilation method The air transfer distance is long thus requiring As the air transfer distance is short, the fan power Fan power much fan power.
  • Page 11: Ventilation Performance

    CHAPTER 1 Ventilation for Healthy Living 4. Ventilation Performance The ventilation performance is largely affected by the installation conditions. Ample performance may not be achieved unless the model and usage methods are selected according to the conditions. Generally, the ventilation performance is expressed by “Air volume” and “wind pressure (static pressure)”, and these are necessary when considering ventilation.
  • Page 12 CHAPTER 1 Ventilation for Healthy Living 4.3 Measurement of the air volume and wind pressure Mitsubishi measures the machine’s air volume and wind pressure with a device as shown below according to the Japan Industrial Standards (JIS B 8628). Measuring device using orifice (JIS B 8628 standards) Chamber Damper Rectifying...
  • Page 13: Outdoor Air (Ventilation) Load

    CHAPTER 1 Ventilation for Healthy Living 5. Outdoor Air (ventilation) Load 5.1 How to calculate each approximate load The outdoor air load can be calculated with the following formula if the required outside air intake volume Q m /h to be introduced is known: (Outdoor air load) = γ...
  • Page 14 CHAPTER 1 Ventilation for Healthy Living Example calculations of determining ventilation load during both cooling and heating are given as follows: 5.2 Ventilation load during cooling (in general office building) Classification of cooling load Class Heat from walls (q from direct sunlight (q Indoor infiltration heat Heat from glass from conduction &...
  • Page 15 CHAPTER 1 Ventilation for Healthy Living Determining internal heat gain When classifying loads, the internal heat gain (indoor generated heat + indoor infiltration heat) will be the value of the outdoor air load subtracted from the approximate cooling load when it is assumed that there is no reheating load. (Internal heat gain) = 157.0 W/m –...
  • Page 16 CHAPTER 1 Ventilation for Healthy Living 5.3 Ventilation load during heating Classification of heating load Class Heat lost from walls (q Heat lost from glass (q Indoor heat loss Heat loss from conduction & convection (q Accumulated heat load in walls (q Sensible heat (q Outdoor air load...
  • Page 18: Chapter 2 Lossnay Construction And Principle

    CHAPTER 2 Lossnay Construction and Principle...
  • Page 19: Construction And Features Of Lossnay

    CHAPTER 2 Lossnay Construction and Principle 1. Construction and Features of Lossnay Lossnay construction The Lossnay is constructed so that the exhaust air passage from Lossnay Core the indoor side to the outdoor side (RA → EA) and the fresh air (Supply air diffuser) passage from the outdoor side to the indoor side (OA →...
  • Page 20 CHAPTER 2 Lossnay Construction and Principle A comparison of the ordinary paper and the Lossnay Core plates is as shown in the table. Ordinary paper Water vapor is transferred, but gas elements that are easily dissolved in water such as CO , NO are also transferred.
  • Page 21: Calculation Of The Total Heat Recovery Efficiency

    CHAPTER 2 Lossnay Construction and Principle 3. Calculation of the Total Heat Recovery Efficiency The Lossnay Core’s heat recovery efficiency can be considered Indoors Outdoors using the following three transfer rates: Exhaust air Supply air (Stale air) (Fresh cold or warm air) (1) Temperature (sensible heat) recovery efficiency (2) Humidity (latent heat) recovery efficiency (3) Enthalpy (total heat) recovery efficiency...
  • Page 22: What Is A Psychrometric Chart

    CHAPTER 2 Lossnay Construction and Principle 4. What is a Psychrometric Chart? The chart which shows the properties of humid air is called a psychrometric chart. The psychrometric chart can be used to find the (1) Dry bulb temperature, (2) Wet bulb temperature, (3) Absolute humidity, (4) Relative humidity, (5) Dew point and (6) Enthalpy (total heat) of a certain air condition.
  • Page 23: Calculation Of Lossnay Heat Recovery

    CHAPTER 2 Lossnay Construction and Principle 5. Calculation of Lossnay Heat Recovery The following figure shows the conditions of various air states when fresh air is introduced through the Lossnay Core. If a conventional sensible heat recovery unit is used alone and is assumed to have the same heat recovery efficiency as Lossnay, the condition of the air supplied to the room is expressed by point A in the figure.
  • Page 24: Chapter 3 General Technical Considerations

    CHAPTER 3 General Technical Considerations...
  • Page 25: Lossnay Heat Recovery Effect

    CHAPTER 3 General Technical Considerations 1. Lossnay Heat Recovery Effect 1.1 Comparison of outdoor air load of various ventilators Examples of formulas to compare the heat recovered and outdoor air load when ventilating with the Lossnay (total heat recovery unit), sensible heat recovery ventilation (sensible HRV) and conventional ventilators are shown below. (1) Cooling during summer Conditions Model LGH-50R type...
  • Page 26 CHAPTER 3 General Technical Considerations (2) Heating during winter Conditions: Model LGH-50R type Heat recovery efficiency table (%) (at 50Hz, high speed) (For winter) Ventilation rate: 500 m Conventional Lossnay Sensible HRV (Specific gravity of air ρ = 1.2 kg/m ventilator Temperature –...
  • Page 27: Example Heat Recovery Calculation

    CHAPTER 3 General Technical Considerations 2. Example Heat Recovery Calculation (1) Setting of conditions (Note: Tokyo Power, industrial power 6 kV supply) Units When Heating When Cooling Operation time (Hr/year) 10h/day × 26 days/mo. × 5 mo./year = 1,300 Hr/year 10h/day × 26 days/mo. × 4 mo./yaer = 1,040 Hr/year Electricity fee (¥/kWh) 16.22...
  • Page 28 CHAPTER 3 General Technical Considerations Psychrometric chart for calculating Lossnay economical effect 0.037 0.036 0.035 0.034 0.033 0.032 0.031 0.030 0.029 Humid air psychrometric chart 0.028 0.027 (-10 to +50°C, atmospheric pressure 101.325 kPa) 0.026 0.025 0.024 0.023 ± ∞  0.022 0.021 0.0203...
  • Page 29: Calculation Of Lossnay Economical Effects

    CHAPTER 3 General Technical Considerations 3. Calculation of Lossnay Economical Effects The following is a sample questionnaire from which it is possible to assess the economical benefits of using the Lossnay in particular applications. (1) Setting of conditions Return air volume (RA) Outdoor air volume (OA) = Air volume ratio (RA/OA) = Air conditions...
  • Page 30 CHAPTER 3 General Technical Considerations (4) Outdoor air load and heat recovery Heating Cooling = Air specific gravity × outdoor air volume = Air specific gravity × outdoor air volume Fresh air load without × (indoor enthalpy – outdoor air enthalpy) ×...
  • Page 31: Psychrometric Chart

    CHAPTER 3 General Technical Considerations 4. Psychrometric Chart...
  • Page 32: The Result Of No Bacterial Cross Contamination For The Lossnay Core And Determining Resistance Of The Lossnay Core To Molds

    The object of this test is to verify that there is no bacterial cross contamination from the outlet air to the inlet air of the Lossnay Core in the heat recovery process. (2) Client MITSUBISHI ELECTRIC CO. NAKATSUGAWA WORKS. (3) Test period April 26, 1999 - May 28, 1999 (4) Test method The configuration of the test equipment is shown below.
  • Page 33 CHAPTER 3 General Technical Considerations Table 1 Test result with bacillus subtilis (CFU/30L air) 5.4 × 10 5.6 × 10 < 10 < 10 8.5 × 10 7.5 × 10 < 10 < 10 7.5 × 10 < 10 < 10 <...
  • Page 34: Flame-Proofing Properties Of Lossnay Core

    CHAPTER 3 General Technical Considerations 6. Flame-proofing Properties of Lossnay Core The Lossnay Core satisfied all requirements of Paragraph 4-3 of the Fire Prevention Law Enforcement Rules. Details of the tests carried out are as seen below. Notation format 2 - (3) Notification of flame-proofing property test (For flame-proof materials and related items) Flame-proofing committee test No., B-80028...
  • Page 35 Messrs. Mitsubishi Electric Corp., Japan Construction General Laboratories Nakatsugawa Works 5-8-1 Fujishirodai, Suita City 565 Tel: 06-872-0391 Hiorshi Wakabayashi Dr. of Engineering, Director Company name Mitsubishi Electric Corp., Nakatsugawa Works Applicant Address 1-3 Komanba-cho, Nakatsugawa, Gifu Single-face laminated Product Lossnay Core...
  • Page 36: Lossnay Core's Soundproofing Properties Test

    Hz. This means that a sound source of 96.9 dB can be shielded to 63 dB. No. 122-1 Soundproofing effect test results Test number IVA-78-122 For Mitsubishi Electric Corporation Acceptance data : February 22, 1979 Report May 24, 1979 Nakatsugawa Works General Building Reseach Corporation The results of the tests are as noted below.
  • Page 37: Change In Lossnay Core Over Time

    CHAPTER 3 General Technical Considerations 8. Change in Lossnay Core Over Time The following details show an example of a building that has installed the Lossnay units, from which it is possible to assess the change in the units over time. 8.1 Outline of building where Lossnay is installed Building name : Meiji Seimei, Nagoya Office/shop building...
  • Page 38 CHAPTER 3 General Technical Considerations 8.3 Outline of Lossnay operation : September 1972 Start of operation Start of daily operation : 7:00 Average daily operation 11 hours End of daily operation : 18:00 : November 1983 Inspection after usage Bypass operation month : Three months of April, May, June Total operation time : (134 –...
  • Page 39: Comparison Of Heat Recovery Techniques

    CHAPTER 3 General Technical Considerations 9. Comparison of Heat Recovery Techniques The methods by which heat recovery devices can be categorised may be considered as follows: Basic methods of total heat exchangersa Country of Type Method Air flow development Static Conductive Cross-flow Japan...
  • Page 40 CHAPTER 3 General Technical Considerations 9.2 Comparison of static-type and rotary-type heat recovery units Item Static-type Rotary-type <Conductive transmission-type: cross-flow> <Heat accumulation/humidity accumulation- Static-type transmission total heat recovery unit type: counterflow> with orthogonally layered honeycomb shaped The rotor core is composed of honeycomb-shaped treated paper formed into multiple layers.
  • Page 42: Chapter 4 Characteristics

    CHAPTER 4 Characteristics...
  • Page 43: How To Read The Characteristic Curves

    CHAPTER 4 Characteristics 1. How to Read the Characteristic Curves 1.1 Obtaining characteristics from static pressure loss (1) Static pressure loss from straight pipe duct length (at required air volume) (2) Static pressure loss at curved section (at required air volume) (3) Static pressure loss of related parts (at required air volume) Total static pressure loss Estimated static pressure loss curve...
  • Page 44 CHAPTER 4 Characteristics Reference The pressure loss caused by the outdoor air is as follows: Pressure loss caused by outdoor air (Pa) × V × (velocity) r : Air weight 1.2 kg/m v : Velocity (m/s) 2 4 6 8 10 12 14 16 18 Outdoor air (m/s) 2.2 Calculation of duct pressure loss When selecting a model that is to be used with a duct, calculate the volumes according to Tables 3, 4, 5 and 6, and then select...
  • Page 45 CHAPTER 4 Characteristics The figure obtained from Table 4 must then be corrected for duct type at various velocities. This can be done using Table 5 below. Table 5 Friction coefficient compensation table Average velocity (m/sec) Duct inner surface Example Very rough surface Concrete finish 1.85...
  • Page 46 CHAPTER 4 Characteristics (3) How to calculate curved sections Table 6 List of pressure losses in each duct section Length of Length of Duct Duct equivalent equivalent Outline diagram Conditions Outline diagram Conditions circular circular value value section section pipe pipe R/D = 0.5 0.73...
  • Page 47: How To Obtain Efficiency From Characteristic Curves

    CHAPTER 4 Characteristics 3. How to Obtain Efficiency from Characteristic Curves How to read characteristic curve Recovery Static pressure efficiency outside unit Recovery efficiency Enthalpy recovery efficiency (heating) Enthalpy recovery efficiency (cooling) Total static pressure loss (or total straight pipe equivalent length) Static pressure loss related parts (straight pipe equivalent length total) Static pressure outside unit...
  • Page 48: Sound

    CHAPTER 4 Characteristics 4. Sound Sound is emitted when any object is excited causing it to vibrate. The object that vibrates is called the sound source, and the energy that is generated at the source is transmitted through the air to the human ear. Humans can hear the sound only when the ear drum vibrates.
  • Page 49 CHAPTER 4 Characteristics 4.3 Frequency analysis of sound It is said that the human ear senses differently according to the frequency. However, the sound generated from a vibration is not limited to one frequency, but instead, various frequencies are generated at differing levels. This is expressed by the NC curve, which is determined according to the difficulty of hearing a conversation.
  • Page 50 CHAPTER 4 Characteristics * Approximate values of noise levels using practical examples The following diagram shows noises found near us. Approximate degree of noise levels can be seen with these examples. * Noise levels and perception (dB) (Perception at site) Boiler making Painful to ear Forginb, rivetting,...
  • Page 51 CHAPTER 4 Characteristics 4.4 Indoor noise (1) Principle of indoor noise 1) Power levels The Power level (PWL) of the sound source must be Fig. 1 understood when considering noise effects. Main unit The following formula is used to obtain PWL from the measured sound pressure data (values noted in catalog) in an anechoic chamber.
  • Page 52 CHAPTER 4 Characteristics Transmission loss in ceiling material (dB) Example For the supply air diffuser (and return grille) in Fig. 2, PWL must be corrected for the noise alternation provided by the Material ( ) duct work (TL) such that: Plaster Plaster Lauan...
  • Page 53 CHAPTER 4 Characteristics 2) When supply air diffuser (and return grille) is sound source ..part 1 (A) If the main unit is separated from the supply air diffuser Fig. 6 (and return grille) as shown in Fig. 6, the use of a silencer box a), silence duct b) or silence grille c) is recommended.
  • Page 54: Nc Curves

    CHAPTER 4 Characteristics 5. NC Curves LGH-50RX type Background noise : 25 dB or less (A range) Background noise : 25 dB or less (A range) Measurement site : Anechoic chamber Measurement site : Anechoic chamber Operation conditions : Lossnay ventilation Operation conditions : Lossnay ventilation Power supply : 208 V 60 Hz...
  • Page 55: List Of Models

    CHAPTER 4 Characteristics 6. List of Models 6.1 Model specifications and list of material colours for Industrial Lossnay...
  • Page 56 CHAPTER 4 Characteristics...
  • Page 57 CHAPTER 4 Characteristics...
  • Page 58 CHAPTER 4 Characteristics 6.2 List of industrial/business Lossnay accessories Model Accessories Duct packaging site Duct connection flanges ..× 4 * Top view. There is a space Mounting screws ... . . × 34 between the EA side and the OA Washers .
  • Page 60: Chapter 5 System Design Recommendations

    CHAPTER 5 System Design Recommendations...
  • Page 61: Lossnay Usage Conditions

    CHAPTER 5 System Design Recommendations 1. Lossnay Usage Conditions Main unit installation conditions Outdoor air and exhaust air conditions Commercial-use Lossnay -10°C to +40°C, RH80% or less. -15°C to + 40°C, RH80% or less. In some cases special attention needs to be paid to extreme operating conditions. These are described as below: 1.1 Use in cold climates (outdoor temperature: –5°C or less) Plot the Lossnay intake air conditions A and B on a psychrometric...
  • Page 62: Noise Value Of Lossnay With Built-In Fans

    CHAPTER 5 System Design Recommendations 2. Noise Value of Lossnay with Built-in Fans The noise level specified for Lossnay units is as that measured in an anechoic chamber. The sound level may increase by 8 to 11 dB according to the installation construction material, and room contents. When using the Lossnay in a quiet room, it is recommended that measures such as installing a muffling duct, silencer intake/exhaust grill or silencer box be carried out.
  • Page 63: Transmission Rate Of Various Gases And Related Maximum Workplace Concentration

    CHAPTER 5 System Design Recommendations 6. Transmission Rate of Various Gases and Related Maximum Workplace Concentration Air volume Exhaust air Supply air Transmission Max. workplace Measurement ratio concentration concentration rate concentrations conditions (ppm) (ppm) (ppm) Measurement method Hydrogen fluoride <0.5 Hydrogen chloride <0.5 •...
  • Page 64: Solubility Of Odors And Toxic Gases, Etc., In Water And Effect On Lossnay Core

    CHAPTER 5 System Design Recommendations 7. Solubility of Odors and Toxic Gases, etc., in Water and Effect on Lossnay Core Main Molecular Sulubility Max. Non-toxic/ Useability generation Gas name formula vapour in water workplace toxic/ of Lossnay site mist odor concentration m /m g/100g...
  • Page 65: Automatic Ventilation Switching

    CHAPTER 5 System Design Recommendations 8. Automatic Ventilation Switching Effect of Automatic Ventilation Mode The automatic damper mode automatically provides the correct ventilation for the conditions in the room. It eliminates the need for troublesome switch operations when setting the Lossnay ventilator to “By-pass” ventilation. The following shows the effect “By-pass”...
  • Page 66: Vertical Installation

    CHAPTER 5 System Design Recommendations 9. Vertical Installation Installation of ceiling embedded-type industrial Lossnay 9.1 Top/bottom reverse installation Bottom All LGH-RX models can be installed in reverse. Bottom 9.2 Vertical installation Vertical installation is possible, but the installation pattern is limited for some models. Refer to the following table for the installation patterns.
  • Page 67: Installation Of Supplementary Fan Devices After Lossnay Unit

    CHAPTER 5 System Design Recommendations 10. Installation of Supplementary Fan Devices After Lossnay Unit On occasions it may be necessary to install additional fans in the ductwork following the LGH type Lossnay. This is because of the inclusion of extra components such as control dampers, high-efficiency filters, sound attenuators, etc. which create a significant extra static pressure to the airflow.
  • Page 68: Chapter 6 Examples Of Lossnay Applications

    CHAPTER 6 Examples of Lossnay Applications...
  • Page 69: Large Office Building

    CHAPTER 6 Examples of Lossnay Applications Lossnay ventilation systems are proposed for eight types of applications in this chapter. These systems are planned for Japanese use, and actual systems will differ according to each country. These should be used only as reference. 1.
  • Page 70 CHAPTER 6 Examples of Lossnay Applications (2) Ventilation For general offices, a ceiling embedded-type Lossnay will be installed in the ceiling. The inside of the ceiling will be used as a return chamber for exhaust, and the air from the Lossnay will be supplied to the air-conditioning return duct and mixed with the air in the air conditioning passage.
  • Page 71 CHAPTER 6 Examples of Lossnay Applications A gallery will be constructed on the outer wall for the outer wall exhaust air outlets to allow for blending in with the exterior. Reference floor air conditioner system layout A Air-cooling heat pump air conditioner = Lossnay B Air-cooling heat pump air conditioner Additional room...
  • Page 72: Medium Size Office Building

    CHAPTER 6 Examples of Lossnay Applications (3) Humidification If the load fluctuation of the required humidification amount is proportional to the ventilation volume, it is ideal to combine the humidifier installation with the ventilation system. For this application, the humidifier is installed on with the air supply side of the Lossnay.
  • Page 73 CHAPTER 6 Examples of Lossnay Applications 2.2 Current topics For general office buildings of the past, centralised air conditioning methods allowing the total centralised control and systematization of the entire building (or divided into floor systems) were favoured due mainly to facility control, uniformity of operation hours, maintenance efficiency and building usage.
  • Page 74 CHAPTER 6 Examples of Lossnay Applications 2.3 Proposed details A) General floors An independent dispersed-type control system incorporating an air cooling heat pump chiller and cassette-type fan coil unit for cooling and heating is used. This can cater for load fluctuations resulting from increases in office automation systems or changes in partitions hence requiting independent control of each module zone (approx.
  • Page 75 CHAPTER 6 Examples of Lossnay Applications 2.5 System trends Creation of an environment including independence, management and control of each zone can be realised as work trends become more diversified. Simultaneous cooling/heating system due to necessity from increased fixed sash windows and increase in office automation systems.
  • Page 76: Urban Small-Scale Building

    CHAPTER 6 Examples of Lossnay Applications 3. Urban Small-Scale Building 3.1 System plan points This system is based on effectively using available space within a limited area by installing the air conditioner and ventilator in available excess space. For this application, the air flow must be considered for the entire floor with the ventilator installed in the ceiling space. Setting outline Application : Office...
  • Page 77: Hospitals

    CHAPTER 6 Examples of Lossnay Applications 3.4 Effect (1) Accurate ventilation is possible with Class 1 ventilation (forced simultaneous air intake/exhaust) using the Lossnay. (2) Outdoor air supply to the toilet and kitchenette is possible with the Lossnay, and accurate ventilation is possible even in highly sealed buildings.
  • Page 78 CHAPTER 6 Examples of Lossnay Applications 4.3 Plan proposals GF layout (1) Air conditioning Centralised heat source control using a fan coil for the Medicine supply general system allows efficient operating time control and storage energy conservation. Machine Gastro 24-hour system using a package air conditioner for special room X-ray camera...
  • Page 79: Schools

    CHAPTER 6 Examples of Lossnay Applications 4.4 Effect (1) The following is possible by independently ventilating the air-conditioned rooms with the Lossnay: Transmission of diseases can be prevented by shielding the air between rooms. Infiltration of outside noise can be prevented with the Lossnay Core’s soundproof properties. As outdoor air does not need to be taken in from the hallway, the door can be sealed, shutting out hallway noise.
  • Page 80 CHAPTER 6 Examples of Lossnay Applications 5.4 Plan details (1) To pursue comfort, save energy and space, an air Classroom layout conditioning and ventilation system using a ceiling embedded-type fan coil unit and ceiling embedded-type Lossnay was applied. (2) Automatic operation using a weekly program timer was (Hallway) applied, energising when the general classrooms and special classrooms are to be used.
  • Page 81: Public Halls (Combination Facilities Such As Day-Care Centres)

    CHAPTER 6 Examples of Lossnay Applications 6. Public Halls (combination facilities such as day-care centres) 6.1 System plan points Air conditioning and ventilation facilities for buildings located near airports and military bases, etc., that require soundproofing, have conventionally been of the centralised method. However, independent dispersed air conditioning and ventilation has been demanded due to the need for operation in zones, as well as for energy conservation purposes.
  • Page 82 CHAPTER 6 Examples of Lossnay Applications 6.4 Effect (1) Operation is possible without special knowledge, so management is easy. (2) Operation is possible according to each room’s needs, and is thus energy-saving. (3) Soundproof ventilation is possible with the separately installed ventilators. (4) Energy saving ventilation is possible with the heat recovery ventilation.
  • Page 84 CHAPTER 7 Installation Considerations...
  • Page 85: Chapter 7 Installation Considerations

    CHAPTER 7 Installation Considerations LGH- 50 · 100RX models Installation diagram Always leave inspection holes ( 450 or 600) on the air filter and Lossnay Core removal side. Always insulate the two ducts outside the room (intake air and exhaust air ducts) to prevent frosting. Exhaust air grill Suspension bolt position It is possible to change the direction of the outside air...
  • Page 86 CHAPTER 7 Installation Considerations (1) The ceiling embedded-type: 500 · 1000 and 2000 m /h types are available. Select an adequate model according to the room size, air volume for the application and noise levels. (2) All types have an extra-high notch. This setting is for when a long duct is used or when a large air volume is required. The positive and negative pressures of the room can also be adjusted with this.
  • Page 87 CHAPTER 7 Installation Considerations 1.1 Selecting Duct Attachment Direction You can choose between two directions for the outside duct (OA, EA) piping direction, to improve construction. Standard Construction Construction with the Direction Changed It is possible You can avoid *A space is to set the unit obstructions of the necessary to...
  • Page 88: Chapter 8 Filtering For Freshness

    CHAPTER 8 Filtering for Freshness...
  • Page 89: Necessity Of Filters

    CHAPTER 8 Filtering for Freshness 1. Necessity of Filters Clean air is necessary for humans to live a comfortable and healthy life. Besides atmospheric pollution that has been generated with the development of modern industries and the growth in the use of automobiles, air pollution in air-tight room has progressed to the point where it adversely affects the human body, and is now a major problem.
  • Page 90: Calculation Table For Dust Collection Efficiency Of Each Lossnay Filter

    CHAPTER 8 Filtering for Freshness 3. Calculation Table for Dust Collection Efficiency of Each Lossnay Filter Measurement method ASHRAE Countingh method Gravitational Colorimetric Applicable (DOP method) method method Application model Tested dust Compound Atomspheric JIS 14 types DOP 0.3 µm Filter type dust dust...
  • Page 91 CHAPTER 8 Filtering for Freshness The ability of the filters used within the Lossnay units are shown below, expressed in terms of collection ratio (%). Colourimetric method High efficiency 90% filter filter NP/400 0.8 1.0 8.0 10.0 Particle diameter (µm)
  • Page 92: Comparison Of Dust Collection Efficiency Measurement Methods

    CHAPTER 8 Filtering for Freshness 4. Comparison of Dust Collection Efficiency Measurement Methods The gravitational, colorimetric and counting methods used for measuring dust collection efficiency each have differing features and must be used according to the application of the filter. Inward flow dust Outward flow dust Efficiency...
  • Page 93 CHAPTER 8 Filtering for Freshness Gravitational method This method is used for air filters which remove coarse dust (10 µm or more). The measurement method is determined by the gravitational ratio of the dust amount on the in-flow side and out-flow sides. In-flow side dust amount –...
  • Page 94: Calculation Of Dust Concentration

    CHAPTER 8 Filtering for Freshness 5. Calculation of Dust Concentration An air conditioning system using the Lossnay is shown below. Using this diagram the level of dust concentration can be easily determined. Dust concentration study diagram High-efficiency filter ηo Indoor unit Lossnay unit Indoor unit filter ηi η...
  • Page 95 CHAPTER 8 Filtering for Freshness [Calculation example] The indoor dust concentration for the following types of design conditions with the above system shall be used in the following example. Outline of air conditioning Air conditioning area No. of persons in room Outdoor air intake volume Cooling capacity Heating capacity...
  • Page 96: Chapter 9 Service Life And Maintenance

    CHAPTER 9 Service Life and Maintenance...
  • Page 97: Service Life

    CHAPTER 9 Service Life and Maintenance 1. Service Life The Lossnay Core has no moving parts. This stationary design eliminates vibration troubles and also permits greater installation flexibility. In addition, chemicals are not used in the heat recovery system. Performance characteristics remain constant throughout the period of service.
  • Page 98: Chapter 10 Ventilation Standards In Each Country

    CHAPTER 10 Ventilation Standards in Each Country...
  • Page 99: Ventilation Standards In Each Country

    CHAPTER 10 Ventilation Standards in Each Country 1. Ventilation Standards in Each Country 1. Japan Table Summary of Laws Related to Ventilation Item Acceptable Range Room Environment Standard Values Related Laws If a central air quality management system or mechanical ventilation equipment is installed, comply with the standard target values shown in the table below.
  • Page 100 CHAPTER 10 Ventilation Standards in Each Country 2. U.S. ASHRAE standard 62 - 1999 Application Outdoor air recommendation Occupancy Dry Cleaner 30 cfm/person 30 people/100 m Dining room 20 cfm/person 70 people/100 m Bars 30 cfm/person 100 people/100 m Kitchens 15 cfm/person 20 people/100 m Hotel bedroom...
  • Page 102: Chapter 11 Lossnay Q And A

    CHAPTER 11 Lossnay Q and A...
  • Page 103 CHAPTER 11 Lossnay Q and A Question Answer Remarks There is no problem with the life of the paper unless it is intentionally Depending on how it damaged, directly placed in water or in direct sunlight (ultra-violet rays). is stored, paper can Paper is used for the The life is longer than metal as it does not rust.
  • Page 104 CHAPTER 11 Lossnay Q and A Question Answer Remarks Between 55 to 60% of the heat energy that escapes with ventilation is There are also recovered by the Lossnay, so the cooling/heating cost can be reduced by "savings in approximately 43,000 yen per year. The initial costs can be suppressed maintenance cost", down to a 59,000 yen increase when comparing the air conditioner, "ventilation functions",...
  • Page 105 CHAPTER 11 Lossnay Q and A Question Answer Remarks According to the results obtained from the test performed by the Tokyo University Hospital (Inspection Centre, Prof. Kihachiro Shimizu), as the supply air and exhaust air pass through different passages, transmission Can the Lossnay be used of bacteria from exhaust side to supply side is low.
  • Page 106 CHAPTER 11 Lossnay Q and A Question Answer Remarks Tobacco smoke tends to stick to dust in the air, and when it passes Ample filtering will not through the Lossnay Core, most of the nicotine and tar will be filtered by be possible with a the air filter.
  • Page 107 CHAPTER 11 Lossnay Q and A Question Answer Remarks What is the difference Refer to “Chapter 3 Section 9 Performance comparisons with various 17 between the rotary-type and heat recovery units and ventilators”. static-type? For the ceiling embedded-type, the unit is installed in the false ceiling, so Is an inspection hole an inspection hole is required at the Core and filter removal section and necessary?
  • Page 108: Lossnay Remote Controller

    Lossnay Remote Controller...
  • Page 110: Summary

    Lossnay M-NET Remote Controller ( PZ-52SF-E ) It can be used in combination with Mitsubishi Electric Air conditioner Network system ( MELANS ) . Refer to page 176. Since this remote controller is supplied the power from the M-NET transmission line, it cannot be linked with Mr. Slim and other such systems that do not use M-NET.
  • Page 111: Terminology

    3. Terminology Interlocked Lossnay This is a Lossnay linked to City Multi, or Mr. Slim indoor units. This is a Lossnay that has been set to interlocked group set- ting to receive signals and operate via indoor unit’s remote controller → indoor unit → Lossnay. Non-interlocked Lossnay This is a Lossnay that is not set to interlocked group setting with City Multi nor Mr.
  • Page 112: System Features And Examples

    4. System Features and Examples Features Classification Item Notes/Cautions Control • Multiple unit operation Maximum 15 units with PZ-41SLB-E; 16 units with PZ- 52SF-E or other M-NET controller. • Remote controller operation Last touch priority • External device operation Signal form: 12VDC, 24VDC, uncharged a-contact •...
  • Page 113 System Example 1 Lossnay with 1 remote controller Multiple Lossnay units with 1 remote controller 2 remote controller system with 1 Lossnay Non-polar Lossnay Non-polar 2 wires Lossnay Non-polar 2 wires (Main) Lossnay 2 wires Power supply Lossnay Power supply Power supply Remote (Sub)
  • Page 114 2 remote controller system with multiple Lossnay units Use Lossnay remote controller PZ-41SLB-E . (Do not use PZ-52SF-E). Lossnay transmission connection terminal Power supply Power supply LGH-50 and 100RX types LGH-200RX type Remote controller PZ-41SLB-E It is also possible to operate 2 remote controller units when using multi- Remote Controller Input Terminal ple Lossnay units.
  • Page 115 System Selection Interlocked with City Multi ( Refer to page 122 ) M-NET transmission cable Lossnay operation when indoor unit is stopped Lossnay stopping when indoor unit is operating Switching Lossnay fan speed When interlocked with indoor unit for compatibility with both R22, R407C and R410A High/Low When interlocked with indoor unit for other than the above Fixed to high...
  • Page 116 Central Controller System Outdoor unit Centralised Controller Indoor unit Indoor unit Lossnay Power supply unit PAC-SC34KUA Remote controller Remote controller A-control Mr.Slim outdoor unit Lossnay A-control Mr.Slim indoor unit Mr.Slim A-control remote controller Central Con- troller Sys- Lossnay Lossnay Lossnay M-NET Lossnay M-NET remote controller remote controller...
  • Page 117 Reference: Remote controller for the Lossnay and indoor unit. Refer to the technical documentation related to the Remote controller for the indoor unit. Remote controllers for Lossnay unit Lossnay remote controller (PZ-41SLB-E) Lossnay M-NET remote controller (PZ-52SF-E) With Lossnay interlock switches and indicators. Without Lossnay interlock switches and indicators.
  • Page 118 Basic System 4.4.1 System Summary Design Example 1 Basic system Design Example 2 Lossnay control of multiple units Up to 15 Lossnay units can be controlled at one time with 1 Lossnay Non-polar Lossnay Non-polar remote controller switch. 2 wires 2 wires (Main) (up to 7 units when using LGH-...
  • Page 119 Combined Line Method Connect the transmission cable from the first Lossnay to the second, the second to the third, and so on up to a maximum of 15 units. (1) Up to four wires can be connected to one signal terminal when a transmission cable is ø0.65 or strand wire 0.3 mm , or up to 2 wires in other cases.
  • Page 120 4.4.3 Operation with 2 Remote controllers Characteristics Remote controller Note • Lossnay can be operated from two remote locations. • Use only up to 2 remote controller • Lossnay conditions can be checked from two remote Lossnay remote controller (Operation will not go normally if 3 locations.
  • Page 121 Interlocking with Mr. Slim 4.5.1 Interlocked Mr. Slim and Lossnay System Features Interlocked operation with Mitsubishi air-conditioners is possible. System Example A-control Mr.Slim outdoor unit A-control or K-control Mr.Slim indoor unit Lossnay unit LGH-RX type Slim-Lossnay connection cable ( Enclosed accessory ) A-control remote controller Lossnay Function Table ( Interlocked settings )
  • Page 122 Controller Function Table especially regarded to the Lossnay unit Local Remote A-control remote Lossnay remote Model controller controller PAR-20MAA PZ-41SLB-E, PZ-52SF-E Start/Stop « Fan speed switching « Ventilation mode switching × (Automatic) Priority instructions. Local × permitted/prohibited Status ( Operation/Stop ) «...
  • Page 123 4.6.1 Independent Lossnay System with Lossnay M-NET Remote Controller and MELANS Features The Mitsubishi Electric air-conditioner network system ( MELANS ) can operate and monitor each group of Lossnay units and air-conditioners. Can also perform operations using Lossnay M-NET remote controller.
  • Page 124 Lossnay Function Table ( Group Setting ) Item Details Number of Lossnay remote controllers and/or MELANS 5 units ( Number of Lossnay remote controller is 2 units max. ) units that can be connected to 1 Lossnay unit Operation of 2 remote controllers in 1 group Possible Fan speed switching High/Low...
  • Page 125 4.6.2 City Multi and Lossnay Interlocked System Characteristics Interlocked operation with Mitsubishi air-conditioners is possible. Can also perform independent Lossnay operations using MA remote controller or ME remote controller. System Examples The following groups can be configured. Single Refrigerant System Outdoor unit (051) Lossnay remote controller PZ-41SLB-E can not be used with any group.
  • Page 126 Lossnay Function Table (Interlocked Settings) Item Details Number of indoor units that can be set to interlocked opera- 16 units per group tion with 1 Lossnay unit in each group Number of Lossnay units that can be set to interlocked oper- 1 unit ation with 1 indoor unit Independent start/stop of ventilation (Lossnay)
  • Page 127 4.6.3 MA Remote Controller/ME Remote Controller in Combination with Lossnay M-NET Remote Controller System The MA remote controller, ME remote controller, and Lossnay M-NET remote controller can be used in combination. Combination of Air Conditioner Remote Control and Lossnay Remote Control Indoor Unit Lossnay LGH-RX type «...
  • Page 128 System Examples: 2 A mixed system including the City Multi can also be configured. Centralised controller ( 000 ) ( ) address Lossnay Lossnay Lossnay Lossnay Lossnay Lossnay Lossnay Lossnay(008) Power (001) (002) (003) (004) (005) (006) (007) supply ( 101 ) ( 103 ) ( 106 ) ( 156 )
  • Page 129 ® 4.6.4 When Using the LONWORKS Compatible Adaptor (LMAP02-E) ® to Connect to LONWORKS ® By using the LON adaptor (model name: LMAP02-E), it is possible to control and observe Lossnays on a building management ® system using the LONWORKS ®...
  • Page 130: Examples Of Applications Using External Control Input Terminals, Operation Monitor Output Terminals And Malfunction Monitor Output Terminals

    5. Examples of Applications Using Exter- nal Control Input Terminals, Operation Monitor Output Terminals and Malfunc- tion Monitor Output Terminals Various applications are possible by using the input/output termi- nals as shown below. Input/Output Specifications Terminal Specification Page External control input ter- This is the input terminal block for start/stop the Lossnay unit using external 128/130 equipment, such as a Mr.
  • Page 131 External Control Operating Mode Selection There are four modes when operating using signals from external equipment. 1. ON/OFF interlock ( the last trigger from either external signal or remote control switch has priority ) 2. ON interlock 3. OFF interlock 4.
  • Page 132 Delayed Interlocked Operation (PZ-41SLB-E, M-NET) (1) It is possible to delay operation of the Lossnay with respect to the operation of the external device. (Energy saving effect.) (2) The times that can be set for delayed operation are 10, 20, 30, 40, 50, and 60 minutes. (3) Delayed operation does not occur if the Lossnay operation was cancelled within the last 2 hours.
  • Page 133 Multiple Lossnay Units in Interlocked Opera- tion with One Indoor Unit. (M-NET only) [ Example: System 1 ] Set the Main/Sub switch of the Lossnay connected to the M-NET transmission cable to “Main,” set the second and following Lossnay units to “Sub,” and connect 5 and 6 of the Lossnay remote controller’s (PZ-41SLB-E) transmission cable terminal (TM2) to the corresponding point on the next unit.
  • Page 134 To Pick Up an Error Signal Externally (PZ-41SLB-E, M-NET) [ Example System ] M-NET transmission cable Lossnay Indoor unit Lamp on monitoring unit Operation moniter output MA remote controller Connection Method (PZ-41SLB-E, M-NET) 1. Using a Mr. Slim (A- Example: Slim-Lossnay connection cable ( Lossnay’s enclosed accessory ) control) indoor unit Lossnay External...
  • Page 135 5. Connecting to equipment such as an electrically operated damper and picking up the operating signals. Connect the power supply cable from the electrically operat- Lossnay ed damper to 9 and 0 of the operation monitor output ter- minal ( TM3 ) . Note : Electrically operated damper Operation...
  • Page 136 1 When using PZ-41SLB-E to connect multiple units Connect the sensor to the Lossnay with the “Main” setting. It is not necessary to connect to any Lossnay with the “Sub” setting. Connect any sensor, etc., connected to external change input to the Lossnay with the “Main” setting. Any Lossnay with the “Sub”...
  • Page 137: Precautions When Designing Systems Of M-Net

    6. Precautions When Designing Sys- tems of M-NET Power Supply of the M-NET Transmission Cable On an M-NET system, the remote controller or central controller operate on power received from the transmission cable. Accordingly, there is need to provide power to the transmission cable. There are two systems for supplying power.
  • Page 138 Wiring Example Example <Centalised controller and Lossnay units> Centralised controller Ground Lossnay unit Lossnay unit Lossnay unit Lossnay unit Lossnay unit Lossnay unit Power supply unit Lossnay Lossnay Lossnay Lossnay Lossnay Lossnay remote remote remote remote remote remote controller controller controller controller controller...
  • Page 139 Power Supply to the Indoor Unit Transmission Cable. In principle, the number of indoor units ME remote controllers and Lossnay M-NET remote controllers that can be connected to one outdoor unit will depend on the type of outdoor unit. The following are the general guidelines when connecting multiple indoor units and Lossnay units to an outdoor unit.
  • Page 140: Cable Installation Of The M-Net

    7. Cable Installation of the M-NET Precautions When Installing Wiring. 1. When routing transmission cable outside of the unit, position it 5 cm or more away cable for the power supply so that it will not pick up electrical noise. ( Never use multi- core cable or place the transmission cable in the same conduit as the power supply cable.
  • Page 141 Electrical Wiring Types of control cables 1. Wiring the M-NET transmission cables • Types of transmission cables Design cable in accordance with the following < Table 1 > . • Cross-sectional area 1.25 mm to 2.00 mm < Table 1 > System configuration Single-refrigerant system Multi-refrigerant system...
  • Page 142 Length of Control Cable Maximum power supply cable length. ( L1 + L2, L1 + L3, L1 + L4 ) : The longest length of the cable from the power supply unit or the indoor unit to the farthest terminal shall be less than 200 m. Maximum distance between ends ( L2 + L3, L2 + L4, L3 + L4 ) : The length of cable between ends shall be less than 500 m.
  • Page 143: System Designs Of M-Net

    8. System Designs of M-NET Address Definitions An address is a unique number used to identify each air conditioner and controller. Device Description Address definition range Indoor unit Set to specify in order each refrigerant system. 001 to 050 001 to 050 ( Note ) Lossnay Set to specify in order each refrigerant system.
  • Page 144 Precautions When Performing Group Settings ( when not interlocked with City Multi indoor unit ) Precautions The maximum number of Lossnay units in one group is 16. ( Refer to page 121. ) When two remote controllers are used within the same group, set one remote controller as the master ( address 101 to 150 ) and the other as the slave ( address 151 to 200 ) .
  • Page 145: Automatic Ventilation Switching

    9. Automatic Ventilation Switching Effect of Automatic Ventilation Mode The automatic damper mode automatically provides the correct ventilation for the conditions in the room. It eliminates the need for troublesome switch operations when setting the Lossnay ventilator to “By-pass” ventilation. The following shows the effect “By-pass”...
  • Page 146: Cold Weather Area Operation Specifications

    ( °C ) ( °C ) 4deg 4deg 10°C 4deg 8°C ( °C ) ( °C ) 24°C ( a ) When there is no target temperature ( b ) When there is no target temperature and the outside temperature has been 28°C or higher in the last 24 hours. ( °C ) ( °C ) 4deg...
  • Page 147 City Multi + LOSSNAY ( LGH ) + PRE-HEAT UNIT INSTALLATION EA damper Indoor LOSSNAY Outdoor LGH-RX type Pre-heat unit OA damper Power source For damper Relay damper damper Power source Operation monitor For LOSSNAY Output Pre-heat unit LOSSNAY LGH-RX type OFF delay TIMER 1.
  • Page 148: Troubleshooting

    11. Troubleshooting 11.1 Service Flow Confirmation items Trouble Mode 1 The system will not start properly. 1 Condition of trouble – remote controller dis- play, etc. • Check the initialization checklist from 2 Frequency of trouble – date of start of opera- installation to operation (table 1-1).
  • Page 149 11.1.1 Error List Cancellation measures Remote LED 1 LED 2 controller (green) (red) Error Measures taken Reset Stop Error item display Display Display monitor Change Error power by Lossnay ↓ error (No. of (No. of output address delete supply Start code blinks) blinks)
  • Page 150 11.2 Items to Check Trouble Mode 1: The system will not start properly. Initialization checklist from installation to operation (Table 1-1) After checking the system, check the points below up to operation. Checkpoint Do the capacity of the main power supply on/off unit and wiring span meet specification? Is the specified power supplied to the Lossnay power terminal (TM1)? (refer to page 161) Is the wiring length of the transmission cable within specifications? When using PZ-41SLB-E:...
  • Page 151 System checklist (1) Use this checklist when using a PZ-41SLB-E or an external device (Table 1-2-1) Symptom Cause Corrective action « Power is not supplied to the Lossnay, or power « Check the power supply to the Remote controller display does not outside specifications is connected.
  • Page 152 (2) System checklist when using the M-NET (Table 1-2-2) Symptom Cause Corrective action « The Lossnay is not set for interlocked opera- « Check the Lossnay address, and Does not interlock with City Multi. (The Lossnay tion, or is set for interlocked operation at the set for an address correspond- cannot be operated by wrong address.
  • Page 153 Symptom Cause Corrective action 1 When using City Multi and Lossnay interlocked The power display “ ” system (connected to the indoor unit system) does not display when power is supplied to the « The transmission cable is not correctly con- «...
  • Page 154 (1) Checklist of error codes displayed on the PZ-41SLB and LED displays (Table 2-1) LED1 LED 2 Error code Symptom Cause Corrective action (green) (red) « When using multiple Lossnay units, the « Turn off the main power supply and set the LC 6608 —...
  • Page 155 (2) Checklist of error codes displayed on the PZ-52SF-E, M-NET controllers, and LED displays (Table 2-2) LED1 LED 2 Error code Symptom Cause Corrective action (green) (red) « There is another unit with the same « Check the addresses of devices in 6600 —...
  • Page 156 Trouble Mode 3: The remote controller does not operate or operates irregularly. (1) Checklist for when using the PZ-41SLB-E (Table 3-1) Symptom Cause Corrective action « Transmission cable is connected to the wrong « Check the transmission cable Nothing displays on the connection (connected to 5,6 LCD.
  • Page 157 Symptom Cause Corrective action « It is less than 10 minutes since the power was « After supplying power to the sys- Displays “HO” and does not start. supplied to the system. tem, HO blinks for a maximum of about 10 minutes. (This is not an error.) «...
  • Page 158 Trouble Mode 4: The Lossnay does not operate or operates irregularly. Lossnay checklist (Table 4). Symptom Cause Corrective action « Connectors for the fan connection or connec- « Check the lead wire connectors The fan does not operate. The fan does not operate tors for the control circuit section connection and the control circuit section normally.
  • Page 159 Symptom Cause Corrective action « When the outdoor air temperature is -10°C or « This is no error. Supply air fan periodical- ly stops operating. less, operation stops after a fixed period of about 10 minutes to keep the Lossnay Core from freezing.
  • Page 160 Temperaturers vs. thermistor resistance table Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance (°C) value (kΩ) (°C) value (kΩ) (°C) value (kΩ) (°C) value (kΩ) (°C) value (kΩ) 88.85 - ∞ 17.92 9.57 5.38 3.17 17.16 9.20 5.19 3.06 32.43 16.43...
  • Page 161 11.3 Circuit Test Point LED1 (green) • When blinking, there is an error with the Lossnay unit (number of blinks indicates the type of error). • Blinks at 1 second intervals when starting. • Lit during delayed start, normally off at other times. Exhaust fan operation unit (combined) Exhaust fan operation unit Fuse (6.3 A/250 V)
  • Page 162: Installation Method

    12. Installation method 12.1 Electrical installation With this product, the wiring installation method will vary according to the design of the system. Perform electrical installation for each of the required sections. 12.1.1 Names of components in control box LGH-50 and LGH-100RX types LGH-200RX type Earth pole LED4...
  • Page 163 12.1.3 Wire connection diagram ----- Model LGH-200RX * Connect the wires shown as dotted lines. * Be sure to connect the grounding wire. * Breaker should be provided by the customer. TH1 (OA) TH2 (RA) BROWN (CN16) BLUE FUSE (TB5) 250V6.3A (CN32) (Subordination)
  • Page 164 12.2 Connecting the power supply cable LGH-50 and 100RX types 1. Remove the screws and open the control Control box cover Screw box cover LGH-200RX type Control box cover Screw 2. Connecting the power supply cable and LGH-50 and 100RX types PG connection transmission cable Power supply...
  • Page 165 LGH-50 and 100RX types LGH- 200RX type 3. When installing upside down Protective cover Protective cover CAUTION: If installing and using this product upside down, the power supply cable outlet will be at the top. Be sure to attach the protective cover so that no drops of water can get inside the Control box Control...
  • Page 166 4. When operating multiple Lossnay units. 5. When connecting to CO sensor when switching the High/Low switch externally. 6. When connecting to City Multi, Lossnay remote controller (PZ-52SF-E) or Mitsubishi Electric Air-Conditioner Network System (MELANS). 1. When connecting to remote controller...
  • Page 167 Lossnay External control input (TM2) When the external device has a charged operating signal of 12V DC or 24 V DC 0.5 mm to 1 mm sheathed PVC cable • Connect the operating signal (wire) from the external device via the remote output retrieval component (sold separately) to 1 and 2 on the external control input terminal block (TM2).
  • Page 168 Round terminal M-NET transmission cable input terminal block 6. When connecting to the City Multi, Lossnay M-NET remote controller (PZ- LGH-50 and 100RX 52SF-E) or Mitsubishi Electric Air- types LGH-200RX type Conditioner Network System (MELANS) A B S * If centralised control is performed according the wire con- nection shown in this section, the remote controller (PZ- 41SLB-E) cannot be used.
  • Page 169 When interlocking with the City Multi • Keep the overall length of the transmission cable within 500 Lossnay meters. Note that the wiring length between the Lossnay and City City power supply unit (sold separately) or outdoor unit should be Multi Multi 200 meters or less.
  • Page 170 12.3.2 Switching function selection switches (SW-2 and 5) Perform the necessary function settings using the function selection switches (SW-2 and 5). The setting can be changed at any time. On the LGH-200RX type, set both the upper and lower circuit boards similarly. 1.
  • Page 171 7. Settings for automatic recovery following power supply interruption (cannot be set when PZ-41SLB-E is used) Sets for automatic recovery following power supply interruption. Mode Operation No automatic recovery Stop after recovery (factory setting) Automatic recovery Recover to operate in mode used before power outage 8.
  • Page 172 12.4.2 Lossnay independent trial operation (1) Remove the control box cover. (2) Turn the trial operation switch (SW2-1and SW2-3) “ON.” • Operation will start with the “High” setting and with Bypass ventilation operating. (This will take approximately 45 seconds after the power is turned on.) •...
  • Page 173: Lossnay Remote Controller (Pz-41Slb-E)

    13. Lossnay Remote Controller (PZ-41SLB-E) 13.1 Operation [2-CONTROLLERS] Display [INTERLOCKED] Display Displayed when two Lossnay remote Displayed when the Lossnay starts off by controllers operate the Lossnay unit(s). interlocked indoor unit or external signal. Note that the most recent button operations of either one will be given priority in such a case.
  • Page 174 13.2 Mode of Use Independent Operation of the Lossnay Unit: Operation Relevant button Relevant display items Sequence Press the ON/OFF button and confirm that the 1. Starting the Operation lamp turns on. Lossnay unit AUTO The 2CONTROLLERS display item will be turned on if BY-PASS HEAT EX.
  • Page 175 Mode of Use (cont.) Interlocked Operation mode types and actions Display Interlocked Action Action (of the external unit) number Operation mode (of the building-management system) ON/OFF Interlocking: When the external device begins to operate, the The Lossnay unit toggles between ON and Subsequent opera-tion Lossnay unit will also begin to operate;...
  • Page 176 13.5 Component Names and External Dimensions Typical System Setup Mounting holes (x 2) <Independent operation of the Lossnay unit:> Lossnay Display section Remote controller(s) Power supply Function Selector • When two individual remote controllers have button been installed, the most recent control signals will be given priority.
  • Page 177 Interlock terminals 3. Connection of wiring and remote-controller mount- ing: Insert the signal wire. (1) Fully insert the (non-polar) signal wiring into the connection terminals. (2) Gently tug on the wiring to confirm that it is being securely gripped. Press this button (3) Mount the remote controller on the switch box using the two screws to release.
  • Page 178 13.7 Trial Operation After installation has been completed, it is of the utmost impor- tance that trial operation of the Lossnay unit and any external device such as an air conditioner is carried out. When power supply is supplied to the remote controller the [HO] display will flash (for approximately 40 seconds); following this, the system will switch to operation-start mode.
  • Page 179: Lossnay M-Net Remote Controller (Pz-52Sf-E)

    14. Lossnay M-NET Remote Controller (PZ-52SF-E) 14.1 Operation [CENTRAL] Display [INTERLOCKED] Display Displayed when remote operation is Displayed when the Lossnay unit starts due prohibited by a centralised control unit, etc. to interlocked indoor unit or external signal. Ventilation Modes [Fan speed] Display Indicates the ventilation mode.
  • Page 180 14.2 Installing the Lossnay M-NET Remote Controller 14.2.1 Mount the switch box. 1. Install the switch box ( purchased separately ) as explained below. Projecting Switch box object such as Note: a stud Be sure to install the switch box with the clearance shown in the illustration at Outline of Lossnay the left.
  • Page 181 5. Set the Lossnay M-NET remote controller address. Set the Lossnay M-NET remote controller address using the rotary switches SW1 and SW2 on the front of the Lossnay M-NET remote controller. Setting range: 101 to 200 Rotary switch SW1 indicates the tens column and SW2 indicates the ones Rotary switches column.
  • Page 182 14.3 Registering the Lossnay Unit with the Lossnay M-NET Remote Controller Initial registration mode operation A Lossnay unit must be registered with the Lossnay M-NET remote controller in a group arrangement. Register a Lossnay unit using the initial registration mode as shown below. In addition, the initial registration mode can be used to search for a Lossnay unit registered to the group or to delete a registration.
  • Page 183 Confirmation of registered address 6 To display the addresses of the Lossnay units that are registered with this Lossnay M-NET remote controller. in step 2 or 4 displays the address of a registered Lossnay unit and its type, “LC”. Each press of FILTER If no Lossnay unit is registered, “...
  • Page 184: Appendix

    15. Appendix 15.1 Centralised Controller (MJ-103MTRA) 15.1.1 Operation setting There are two methods for the operation, performing the operation classified by groups or collective operation. Group operation setting ON/OFF OPERATION SETTING TEST RUN 1F1ROOM ON/OFF MODE FAN SPEED GROUP SELECT (HEAT RECOVERY) DIRECTION BACK...
  • Page 185 Name of switches Function Display Operation status display → [ON] → [OFF] The ON/OFF condition of the displayed ON/OFF button group is switched. * When there is an interlocked Lossnay unit, turning this switch ON starts opera- tion in a [High] fan speed state. On the group composed of independent Lossnay units, operation mode is selected in a sequence that goes from HEAT...
  • Page 186 15.1.2 Initial setting DIP switch and rotary switch setting Remove the cover from the controller and perform the DIP switch and rotary switch setting. 1 Remove the cover screw. Rotary switches DIP switch Note: When this controller is shipped from the factory, the screw is contained in the same package.
  • Page 187 15.1.3 Group configuration setting Registration can be made for the indoor units, local remote controllers and slave system controllers in the same group. Registration can also be performed for the group that is composed of only Lossnay. Example of a group configuration Supply the power from the power supply unit (PAC-SC34KUA) through the M-NET transmission cable.
  • Page 188 This is the procedure for registering all units and controllers in the displayed GROUP SETTING group number. 6 Repeat operation 3 to 5 to set all the groups controlled by this controller. ADDRESS BACK 7 When all settings have been completed, press the button.
  • Page 189 15.1.4 Interlocked operation setting This is the procedure for registering the interlocked operation of an Lossnay unit with a single or multiple indoor units. All indoor units to be interlocked with an Lossnay unit for operation should be registered as group before- hand. Example of an interlocked group configuration Duct Outdoor unit...
  • Page 190 6 Use the numeric keypad to set the address of the indoor unit to operate with INTERLOCKED SETTING the displayed Lossnay unit. INTERLOCKED UNIT ADDRESS Operation example UNIT ADDRESS For an indoor unit with an address of 012. 1) Input “0”. 2) Input “1”.
  • Page 191: Remote Controllers For Mr. Slim Indoor Unit

    15.2 Remote Controllers for Mr. Slim indoor unit A-control remote controller (PAR-20MAA) Without Lossnay interlock switches and indicators. [Ventilation] Display Displayed during ventilation (Lossnay) operation. 1Hr. CENTRALLY CONTROLLED ON OFF ˚C CLOCK CHECK FILTER CHECK MODE ˚C TEST RUN STAND BY ERROR CODE FUNCTION NOT AVAILABLE...
  • Page 192 15.2.2 Function Selection Perform only when change is necessary with Mr. SLIM air conditioner. (Cannot be perf med with CITY MULTI control system.) Set the functions of each indoor unit from the remote controller, as required. The functions of each indoor unit can be selected only from the remote controller.
  • Page 193 [Procedure] (Set only when change is necessary.) Check the set contents of each mode. When the set contents of a mode were changed by function selection, the functions of that mode also change. Check the set contents as described in steps and change the setting based on the entries in the Table 1 check field.
  • Page 194: Network Remote Controller (Par-F27Mea)

    15.3 Network Remote Controller (PAR-F27MEA) CENTRALLY CONTROLLED 1Hr. DAILY ON OFF AUTO OFF CLOCK REMAINDER FILTER CHECK MODE TEST RUN STAND BY LIMIT TEMP. ERROR CODE NOT AVAILABLE DEFROST TEMP. ON/OFF CLOCK→ON→OFF FILTER CHECK TEST TIMER SET PAR-F27MEA 15.3.1 Method for Operating Lossnay with Network remote Controller (When Interlocked with City Multi Indoor Unit) Operation method is same as A-control remote controller.
  • Page 195 4 To register the interlocked operation of the Lossnay unit and the indoor unit. Use the [TEST RUN] buttons (shown as D) to register the relationship of the interlock between the Lossnay indicated in • “OA UNIT ADDRESS NO.” and the indoor unit indicated in “INDOOR UNIT ADDRESS NO.” •...
  • Page 196 9 Press the “Timer/continuous” button (shown as E) once again. The display will now alternate between the registered unit and the address of the next registered unit. (The way of display is the same as in step 8.) Address of another INDOOR UNIT ADDRESS NO.
  • Page 197 MEMO...
  • Page 198 Y04-002 Jul.2004 <MEE>...

Table of Contents