hit counter script

Safety Check Function; Loss-Of-Flame Test; Slt Test; Menu And Parameter Lists - Siemens LMV51 Series Basic Documentation

Burner control with integrated fuel / air ratio control and load control for forced-draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Loss-of-flame test

SLT test

AZL51... menu structure
with parameter definitions
Siemens Building Technologies
HVAC Products

6.4 Safety check function

The safety check function may only be performed by authorized staff.
It is possible to activate
· the floss-of-flame test, and
· the SLT test
The loss-of-flame test is triggered manually with the AZL51... and produces an
interruption of the flame signal.
Using safety shutdown «Loss of flame», the LMV51... must shut the burner down.
Activation of the SLT test negates the internal controller and temperature limiter
function.
The setpoint and the temperature limiter switch-off threshold will be ignored.
The burner will be switched on and the output automatically increased to 100 %.
After safety shutdown by STL lockout or manual selection, the SLT test can be
deactivated again.

6.5 Menu and parameter lists

For each line, a parameter for the AZL51... menu is defined.
Name of column
Menu level
Description
Value range
Access rights
Basic parameter setting
Basic Documentation LMV51...
6 Display and operating unit AZL51...
Description
This parameter name or this submenu level corresponds to
the name on the menu
Brief explanation of the parameter or of the submenu level
Definition of setting limits within which the parameter can be
changed
Definition of access rights. Parameters can be set by:
User :
Plant operator
Service : Heating engineer
OEM :
Boiler / burner manufacturer
Factory-set parameter
107/157
CC1P7550en
29.05.2002

Advertisement

Table of Contents
loading

Table of Contents