6.2

Relay output connection

The relay is shown in a de-energized/unpowered state.
K2 contact ratings:
Note
Switch and potentiometer settings are for illustration purposes only.
6.3

Solid-state switch

Solid-state switch to customer's control or instrumentation device.
The switch is shown in de-energized/unpowered state.
K3 contact ratings:
Connect protective earth wire to terminal provided in housing. Use crimp type cable socket
for 4 mm screw diameter, ring form or U-form (e.g. DIN 46234)
Pointek CLS200/CLS300 standard
Operating Instructions, 05/2021, A5E47827796-AA
• max. switching voltage/current (DC): 30 V DC / 5 A
• max. switching voltage/current (AC): 250 V AC / 8 A
• max. switching capacity: 150 W / 2000 VA
• Maximum Voltage: 30 V DC or peak AC
• Maximum Current: 82 mA
• Non-polarized
Wiring
6.2 Relay output connection
31