ACS880-01…+C135 drives with flange mounting kit Supplement Table of contents 3. Mechanical installation 2019 ABB Oy. All Rights Reserved. 3AXD50000349814 Rev A EFFECTIVE: 2019-04-16...
Introduction to the supplement 7 Introduction to the supplement Contents of this chapter This chapter describes the supplement. Applicability This supplement applies to ACS880-01 drive with flange mounting kits (option +C135). Target audience This supplement is intended for people who plan the installation and install the drive with the flange mounting kit.
Document library on the Internet on the inside of the back cover. For manuals not available in the Document library, contact your local ABB representative. The code below opens an online listing of the manuals applicable to the product. ACS880-01 manuals...
Hardware description 9 Hardware description Contents of this chapter This chapter describes the flange mounting kit. Product overview The flange mounting kit contains brackets for attaching the drive onto a mounting plate. The heat sink of the drive can be located in the cooling air channel and the front part on the other side of the mounting plate.
Hardware description 11 Upright position, R6 to R9 Hood (in the cooling air channel; required for UL Type 12) Top flange bracket Mounting plate Lifting hole Drive heat sink in the cooling air channel Side flange bracket Drive front side Bottom flange bracket Degree of protection This table shows the degree of protection of the flange-mounted drive.
12 Hardware description Special requirements Frame size Special requirement Insert sealing plug. Insert sealing plug and attach sealing tapes. Ordering codes The flange mounting kit is a plus code option (+C135) or can be ordered with these ordering codes also separately. Frame size Ordering code 3AXD50000024175...
Mechanical installation 13 Mechanical installation Contents of this chapter This chapter describes how to install the drive with the flange mounting kit mechanically. Safety Obey the general safety instructions in the hardware manual and the task-specific instructions in this supplement. Wear protective gloves and long sleeves.
14 Mechanical installation Examining the installation site Make sure that the installation site agrees with these requirements: • The installation site has sufficient ventilation to prevent overheating of the drive. See section Losses, cooling data and noise in the hardware manual for the required air flow in the cooling air channel and in the front part of the drive.
Mechanical installation 17 Flange mounting kit package contents The illustrations show the layout of the flange mounting kit packages. Examine that all items are present and there are no signs of damage. Frames R1 to R3 Quick guide Cable shelf Top bracket Grounding plate Bottom bracket...
20 Mechanical installation Installing the drive Free space requirements The flange-mounted drives can be installed side by side. Free space requirements above and below the drive are shown below. 200 mm (7.87 in) 300 mm (11.81 in)
Mechanical installation 21 Installing drives above one another Make sure that the outlet cooling air flows away from the drive above. 200 mm (7.87 in.) 120 mm (4.72 in.) 250 mm 120 mm (9.84 in.) (4.72 in.) 300 mm (11.81 in.)
22 Mechanical installation Installation procedure Frames R1 to R3 1. To remove the fan assembly, push the retaining clip with a flat screwdriver. Lift the assembly up.
Page 23
Mechanical installation 23 2. Insert the sealing plug to the hole shown in the figure. 3. Reinstall the fan assembly in reverse order.
Page 24
24 Mechanical installation 4. Attach the top and bottom U-brackets to the drive. 4 × M5 nut 6 N·m...
Page 25
Mechanical installation 25 5. First attach the side brackets (a) to the top and bottom U-brackets with four M6 nuts. Then, attach the tightening brackets (b) to the both ends with four M5×20 screws. Last attach the sealing plate (c) to the bottom of the drive with two M5×50 screws T20.
Page 26
26 Mechanical installation 6. Attach the top and bottom brackets to the side brackets. 8 × M6 nut 10 N·m...
Page 27
Mechanical installation 27 7. Push the grounding plate (d) onto the alignment pins of the bottom bracket and attach it to the drive with one M5×25 screw T20 and three M6 nuts. Then attach the cable shelf (e) to the bottom bracket with two M6 nuts. 5 ×...
Page 28
28 Mechanical installation 8. See chapter Dimension drawings for the dimensions of the flange and the required opening in the mounting plate. Attach the mounting template from the flange mounting kit package onto the mounting plate. Make the opening and drill the holes for the mounting screws. Consider the hole size for the Rivet or Kalei nuts (not included in the delivery).
Page 29
Mechanical installation 29 9. Attach chains to the drive lifting holes and lift the drive with a lifting device onto the opening in the mounting plate. 10. Attach the bottom bracket with one screw. 1 × M6×25 screw 10 N·m...
Page 30
30 Mechanical installation 11. Attach the top bracket with one screw. 1 × M6×25 screw 10 N·m 12. Attach the rest of the mounting screws. Remove the chains. 8 × M6×2 screw 10 N·m...
Mechanical installation 31 Frames R4 to R5 1. To remove the fan assembly, lift the fan mounting plate up from the front edge. Unplug the fan power supply wires. Lift the assembly off. 2. Insert the sealing plug to the hole shown in the figure.
Page 32
32 Mechanical installation 3. Reinstall the fan assembly in reverse order. 4. Attach the sealing tapes on both sides of the drive.
Page 33
Mechanical installation 33 5. Attach the side brackets to the drive. Note that R4 has 6 screws for attaching the side brackets while R5 has 8 screws. R4: 6 × M6×10 screw T30 R5: 8 × M6×10 screw T30 8 N·m 6.
Page 34
34 Mechanical installation 7. Attach the top bracket to the side brackets. 4 × M6 nut 10 N·m 8. Attach the cable shelf to the bottom bracket. 3 × M6 nut 10 N·m...
Page 35
Mechanical installation 35 9. See chapter Dimension drawings for the dimensions of the flange and the required opening in the mounting plate. Attach the mounting template from the flange mounting kit package onto the mounting plate. Make the opening and drill the holes for the mounting screws. Consider the hole size for the Rivet or Kalei nuts (not included in the delivery).
Page 36
36 Mechanical installation 10. UL Type 12 installation only: Attach the hood to the cooling channel. 3 × M6 nut 10 N·m Back Front Back Front Back: View from top Back: View from bottom...
Page 37
Mechanical installation 37 11. Attach chains to the lifting holes of the flange and lift the drive with a lifting device onto the opening in the mounting plate. 12. Attach the top bracket with one screw. 1 × M6×25 10 N·m...
Page 38
38 Mechanical installation 13. Attach the bottom bracket with one screw. 1 × M6×25 10 N·m 14. Attach the rest of the mounting screws. Remove the chains. 12 × M6×25 10 N·m...
Page 39
Mechanical installation 39 For instructions on installing an auxiliary cooling fan to drives with front cover on, see chapter Maintenance in the hardware manual.
40 Mechanical installation Frames R6 to R9 1. Attach the side brackets of the flange to the drive. 12 × M6×10 T30 6 N·m 2. Attach the top and bottom brackets. 8 × M6 nut 6 N·m...
Page 41
Mechanical installation 41 3. See chapter Dimension drawings for the dimensions of the flange and the required opening in the mounting plate. Attach the mounting template from the flange mounting kit package onto the mounting plate. Make the opening and drill the holes for the mounting screws. Consider the hole size for the Rivet or Kalei nuts (not included in the delivery).
Page 42
42 Mechanical installation 4. UL Type 12 installation only: Attach the hood to the cooling channel. 3 × M6 nut 6 N·m Back Front Back: View from top Back: View from bottom 5. Attach chains to the lifting holes of the flange and lift the drive with a lifting device onto the opening in the mounting plate.
Page 43
Mechanical installation 43 6. Attach the bottom bracket with one screw. 1 × M6×25 6 N·m 7. Attach the top bracket with one screw. 1 × M6×25 6 N·m...
Page 44
44 Mechanical installation 8. Attach the rest of the mounting screws. Remove the chains. R6…R8: 14 × M6×25 6 N·m 16 × M6×25 6 N·m...
Dimension drawings 45 Dimension drawings Contents of this chapter This chapter contains the dimension drawings of the flange mounting kits and required openings in the mounting plate. For the dimensions of the drive, see the hardware manual.
Page 99
Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to abb.com/searchchannels. Product training For information on ABB product training, navigate to new.abb.com/service/training.