hit counter script
ABB EP010 User's And Operator's Manual

ABB EP010 User's And Operator's Manual

Modbus / fbp interface
Table of Contents

Advertisement

Quick Links

EP010
Modbus / FBP Interface
User and Operator Manual
ABB SACE
L2388
EP010
1SDH000510R0001

Advertisement

Table of Contents
loading

Summary of Contents for ABB EP010

  • Page 1 EP010 Modbus / FBP Interface User and Operator Manual ABB SACE L2388 EP010 1SDH000510R0001...
  • Page 2: Table Of Contents

    General data ........8 2.6.2 Power supply for EP010 ......8 2.6.3 Connection of the FieldBusPlug .
  • Page 3 EP010 - PR222DS/PD wiring diagram ....14 Figure 9. EP010 - PR122/3 wiring diagram ....18 INDEX OF TABLES PAGE Table 1.
  • Page 4: Introduction

    INTRODUCTION This is the User and operator Manual for the EP010, the generic ABB SACE Modbus / Field Bus Plug Interface. It contains two sections: 1 information independent from the device connected to the Modbus port (in the following “device”) 2 information dependent from the device.
  • Page 5: Device Independent Section

    The Modbus / Fieldbus Interface EP010 establishes together with the FieldBusPlug a connection between a fieldbus and the device connected to the EP010 Modbus port. Power supply for EP010 comes directly from the Field Bud Plug. The connected device, however, must have its own power supply.
  • Page 6: Fieldbusplug Connector

    Table 1. FBP port pins Wrong power supply polarity or swap between bus lines and power supply lines can cause a destruction of the EP010! The field bus plug is plugged into this connector and fixed using the supplied fixing screw.
  • Page 7: Leds

    The Modbus Port is the lowest terminal box of the EP010, with the following meaning: TERMINAL NAME MODBUS CABLE L (left) l (right) Table 2. Modbus port terminal Total lenght of the Modbus cable from EP010 to connect device has to be less equal to 1 m.
  • Page 8: Earthing

    Power supply (24V DC) for EP010 comes from the FBP. Connected Modbus device, however, must be indipendently powered. 2.3.1 Earthing Terminal PE has to be connected to earth. Addressing An address must be set on every field bus plug. The possibilities for setting the address very depending on the type of the field bus.
  • Page 9: Technical Data

    EP010 supports only the “long serial protocol” to communicate with the FBP. Therefore, the AS-i P and AS-i Fieldbus Plugs cannot be used with the EP010. When a Profibus FBP is used, the EP010 GSD file associated to the connected device is required.
  • Page 10: Led Displays

    36 x 90 x 62 mm Wiring method screw terminals Mounting position preferred orientation of connecting terminals up-and downwards Weight 0.102 kg Dimensions for mounting refer to the following figure: Figure 7. Dimensions for mounting Page N. ABB SACE EP010 1SDH000510R0001 L2388 9/28...
  • Page 11: Identification

    Important: at the end of start-up, the WD LED flashes at 0.5 Hz a number of times that’s device dependent. This way, the type of device that can be connected to an EP010 unit can be immediately identified in field.
  • Page 12: Communication With The Fbp

    After a failure has been detected and signalled, the FAULT LED continues flashing until: 1 the FBP is communicating with the EP010 (and then the EP010 is communicating with the device using the Modbus port) and the fault is removed OR 2 the EP010 id powered off (i.e.
  • Page 13: Permanent (Non Volatile) Information Saving

    (Most Significant Word) Command parameter Table 6. Command format At the moment, the “Command parameter” is not used and it’s not evaluated by the EP010. Its value doesn’t care. 2.8.4 Permanent (non volatile) information saving No information is permanently saved by EP010.
  • Page 14: Troubleshooting

    The exact failure cause can be read from FBP (see also next paragraph). Please note that NO communication between FBP and EP010 is active if there a failure on the relevant serial channel (UART)............
  • Page 15: Device Dependent Section

    3. DEVICE DEPENDENT SECTION PR222DS/PD This user manual applies to the following EP010 SW versions: 1. PR222DS/PD FBP Interface v01.00 or higher Order Code Description S/N Product Type field (G) WD LED number of flash 1SDA059469R1 PR222DS/PD FBP Interface 3.1.1 Wiring Figure 8.
  • Page 16 1 L2 run time current A | In 2 L3 run time current A | In 3 N run time current A | In 4 Ground run time current A | In Page N. ABB SACE EP010 1SDH000510R0001 L2388 15/28...
  • Page 17 {0.2 ...1}, step 0.01 17 Protection G electronic trip delay {0.1 ... 0.8}, step 0.01 18 First bit field: 0: Prot. L electronic pre-alarm disable Enabled | Disabled 0 | 1 Enabled Page N. ABB SACE EP010 1SDH000510R0001 L2388 16/28...
  • Page 18: Performance Data And Conditions

    19200 9 - 10: parity Even | Odd | None 00 | 01 | 10 Even 11: Addressing type ABB | Standard 0 | 1 Standard 12 - 15: not used 23 System disconnection timeout {0 ... 6000}, step 1...
  • Page 19: Pr122/3 With Pr120/D

    PR122/3 with PR120/D This user manual applies to the following EP010 SW versions: 1. PR122/3 FBP Interface v01.00 or higher Order Code Description S/N Product Type field (G) WD LED number of flash 1SDA060198R1 PR122/3 FBP Interface 3.2.1 Wiring Figure 9. EP010 - PR122/3 wiring diagram 3.2.2...
  • Page 20 111 RP tripped 112 UF tripped 113 OF tripped 114 Electronic Trip Test 115 Simulated Trip from Test Unit 116 External Input Trip 117 Hardware error Trip 118 NOT USED 119 NOT USED Page N. ABB SACE EP010 1SDH000510R0001 L2388 19/28...
  • Page 21 8 | 9 | 10 Reset history measurements | Reset energy counters | Reset Events log|Restart trigger Datalogger | Stop Datalogger byte 2-3: Don’t care Slave ID SW version MM.mm MSB = MM LSB = mm Page N. ABB SACE EP010 1SDH000510R0001 L2388 20/28...
  • Page 22 0 | 1 29 Plant Configuration 3P | 3P+N 0 | 1 30 Slave Address {1 ... 247} 31 Addressing Type Standard | ABB 0 | 1 Standard 32 Baud rate 9600 | 19200 0 | 1 19200 33 Protocol Type E.8.1 | O.8.1 | N.8.2 | N.8.1...
  • Page 23 0 | 1 1: not used 2: Start Up Th OFF | ON 0 | 1 3: Zone sel OFF | ON 0 | 1 4: Thermal mem OFF | ON 0 | 1 Page N. ABB SACE EP010 1SDH000510R0001 L2388 22/28...
  • Page 24 135 Prot RV configuration 0: Prot enable/disable Enable | Disable 0 | 1 1: Trip enable/disable Enable | Disable 0 | 1 2-15: not used 136 Prot RV threshold {0.10 ... 0.40}, step 0.05 Page N. ABB SACE EP010 1SDH000510R0001 L2388 23/28...
  • Page 25 {0.13 ... 0.50}, step 0.01 0.13 183 Prot I configuration 0: Prot enable/disable Enable | Disable 0 | 1 1: not used 2: Start Up Th OFF | ON 0 | 1 3-15: not used Page N. ABB SACE EP010 1SDH000510R0001 L2388 24/28...
  • Page 26 0.06 | 0.10 | 0.20 | 0.30 | 0.40 | 0 | 1 | 2 | 3 | 4 | 5 0.06 0.50 | 0.80 | 1.00 | 3.00 | 4.80 6 | 7 | 8 | 9 Page N. ABB SACE EP010 1SDH000510R0001 L2388 25/28...
  • Page 27: Performance Data And Conditions

    E3L2000/3P E3L2000/4P E6H-A4000/3P E6H-A4000/4P E3L2500/3P E3L2500/4P E6H-A5000/3P E6H-A5000/4P E4S4000/3P E4S4000/4P E6V-A4000/3P E6V-A4000/4P —- E4S/f4000/4P E6V-A5000/3P E6V-A5000/4P Coding Coding Un 1000 1150 3.2.3 Performance data and conditions Parameters refresh rate max. 20 [s] Page N. ABB SACE EP010 1SDH000510R0001 L2388 26/28...
  • Page 28: Revision History

    Revision e - 10/02/2005 4.5.1 Added Par. 1.1: reference to ABB SACE documentation “GSD file, doc. n. ITSCE-RE1024001” Par. 1.2: reference to ABB SACE documentation “GSD file, doc. n. ITSCE-RE1024001” Table 14: rows 118 and 119 to complete a byte.
  • Page 29: Revision F - 04/03/2005

    Par. 2.8.5: changed “Modbus scan rate” with “Modbus polling rate”. Changed “ 3000 [ms]” with 3 [s]”. Par. 3.1: inserted the right EDS file name. Par. 3.2: inserted the right EDS file name. 4.6.3 Deleted Tables 9 - 16. Page N. ABB SACE EP010 1SDH000510R0001 L2388 28/28...

Table of Contents