Mechanical operation counter moc - e2.2-e4.2-e6.2 (4 pages)
Summary of Contents for ABB SACE Emax 2
Page 1
DOC. N° 1SDH001316R1002 - ECN000086501 - Rev. A SACE Emax 2 Emax low voltage air circuit-breakers E1.2-E2.2-E4.2-E6.2 Instructions for using Ekip Touch protection trip units and Accessories.
In the event of an alarm, it commands a TRIP Ekip Touch Trip unit for SACE Emax 2 CBs, equipped with touchscreen display and available in four different versions Trip coil CB opening actuator controlled directly by Trip unit...
ABB | SACE Emax 2 Introduction 1 - Contents Overview This manual describes the characteristics of the Ekip Touch Trip units installed on SACE Emax 2 CBs, among which: general overview: operating conditions consultation of menus for changing parameters and displaying measurements...
• anyone who is implementing procedures or using maintenance devices recommended by ABB or not must check carefully that neither their personal safety nor the safety devices are endangered by the installation, operation, maintenance method or by the tools used; contact your nearest ABB representative for further information, explanations or specific problems •...
ABB | SACE Emax 2 Overview of Ekip Touch 1 - General characteristics Families SACE Emax 2 can be configured to operate with two Trip unit families: • Ekip Dip with interface via dip-switches • Ekip Touch with touchscreen display Both families provide protection and measuring functions related to signals from the installation and are available in different models and versions.
Page 11
Ekip Touch in your installation: documents NOTE: some of the documents mentioned in the next table refer to SACE Emax 2, but can also be used with SACE Tmax XT7 Ekip Connect 3...
Disabling The PIN code can be disabled by entering its value as: 00000; In this case, the PIN is only required to change the PIN itself in the Settings menu. Recovery if the PIN code is lost, consult document 1SDH001501R0002, available in the ABB website, or contact ABB directly.
Page 31
I protection. The protection is always active; the trip threshold and time are reserved and defined by ABB. Harmonic distortion Harmonic distortion allows a monitoring alarm to be activated in the case of distorted waveforms; if enabled in the Measurements menu, the unit signals an alarm for peak factors exceeding 2.1.
Page 45
BLE - Connection security Activation of LV communication requires the Trip unit to be pre-engineered for a wireless connection: security of the data and LV connection between the Trip unit and its device is guaranteed thanks to the ABB EPiC application and the pairing configuration.
Page 53
IEEE1588 synch Synchronization problem of IEEE 1588 synchronization reference module MAC Address Ekip Com module detected with incorrect / not allowed MAC address, contact ABB. Ekip Installation Installation error between HMI and Mainboard, contact ABB Measuring Install Measurement module (Settings-Circuit breaker-Installation-Measuring-Install)
Page 54
1SDH000999R0002 and 1SDH001000R0002. NOTE: check error messages on display before consulting the table; if the suggestions given fail to resolve the problem, call the ABB assistance service and provide the report produced by the Ekip Connect software if possible Fault...