Small VRF system for light commercial and home use DESIGN & TECHNICAL MANUAL...
Page 2
CONTENTS 1. GENERAL INFORMATION 2. MODEL SELECTION 3. OUTDOOR UNITS 4. INDOOR UNITS 4. CONTROL SYSTEM 6. SYSTEM DESIGN 5. FUNCTION SETTING 8. EXTERNAL INPUT & OUTPUT 9. NOTES 10. OPTIONAL PARTS...
CONTENTS 2. MODEL SELECTION 1. MODEL SELECTION PROCEDURE..........02 - 01 2. MODEL LINE UP ................02 - 02 2-1. OUTDOOR UNIT ................02 - 02 2-2. INDOOR UNIT ................... 02 - 03 2-3. OPTIONAL PARTS ................02 - 05 3.
Page 5
CONTENTS 2. MODEL SELECTION 8. CAPACITY TABLE HEATING (INDOOR UNIT) ......02 - 51 8-1. COMPACT CASSETTE TYPE ............02 - 51 8-2. CIRCULAR FLOW CASSETTE TYPE ..........02 - 53 8-3. CASSETTE TYPE ................02 - 55 8-4. MINI DUCT TYPE ................02 - 57 8-5.
Page 6
CONTENTS 3. OUTDOOR UNITS SPECIFICATIONS ..............03 - 01 DIMENSIONS ................03 - 03 INSTALLATION SPACE ............03 - 04 3-1. SINGLE OUTDOOR UNIT INSTALLATION ..........03 - 04 3-2. MULTIPLE OUTDOOR UNIT INSTALLATION ..........03 - 05 3-3. OUTDOOR UNITS INSTALLATION IN MULTI ROW ........03 - 05 REFRIGERANT CIRCUIT ............
Page 7
CONTENTS 4. INDOOR UNITS SPECIFICATIONS ..............04-01 1-1. COMPACT CASSETTE TYPE ................ 04-01 1-2. CIRCULAR FLOW CASSETTE TYPE ............04-03 1-3. CASSETTE TYPE................... 04-04 1-4. MINI DUCT TYPE ................... 04-06 1-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE ......... 04-07 1-6.
Page 8
CONTENTS 4. INDOOR UNITS WIRING DIAGRAMS ..............04-70 4-1. COMPACT CASSETTE TYPE ................ 04-70 4-2. CIRCULAR FLOW CASSETTE TYPE ............04-72 4-3. CASSETTE TYPE................... 04-73 4-4. MINI DUCT TYPE ................... 04-74 4-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE ......... 04-75 4-6.
Page 9
CONTENTS 4. INDOOR UNITS AIR FLOW ................04-200 NOISE LEVEL CURVE ............. 04-202 8-1. COMPACT CASSETTE TYPE ..............04-202 8-2. CIRCULAR FLOW CASSETTE TYPE ............04-204 8-3. CASSETTE TYPE..................04-206 8-4. MINI DUCT TYPE ..................04-207 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE ........04-208 8-6.
Page 10
CONTENTS 3. OUTDOOR UNITS SPECIFICATIONS ..............03 - 01 DIMENSIONS ................03 - 03 INSTALLATION SPACE ............03 - 04 3-1. SINGLE OUTDOOR UNIT INSTALLATION ..........03 - 04 3-2. MULTIPLE OUTDOOR UNIT INSTALLATION ..........03 - 05 3-3. OUTDOOR UNITS INSTALLATION IN MULTI ROW ........03 - 05 REFRIGERANT CIRCUIT ............
Page 11
CONTENTS 4. INDOOR UNITS SPECIFICATIONS ..............04-01 1-1. COMPACT CASSETTE TYPE ................ 04-01 1-2. CIRCULAR FLOW CASSETTE TYPE ............04-03 1-3. CASSETTE TYPE................... 04-04 1-4. MINI DUCT TYPE ................... 04-06 1-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE ......... 04-07 1-6.
Page 12
CONTENTS 4. INDOOR UNITS WIRING DIAGRAMS ..............04-70 4-1. COMPACT CASSETTE TYPE ................ 04-70 4-2. CIRCULAR FLOW CASSETTE TYPE ............04-72 4-3. CASSETTE TYPE................... 04-73 4-4. MINI DUCT TYPE ................... 04-74 4-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE ......... 04-75 4-6.
Page 13
CONTENTS 4. INDOOR UNITS AIR FLOW ................04-200 NOISE LEVEL CURVE ............. 04-202 8-1. COMPACT CASSETTE TYPE ..............04-202 8-2. CIRCULAR FLOW CASSETTE TYPE ............04-204 8-3. CASSETTE TYPE..................04-206 8-4. MINI DUCT TYPE ..................04-207 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE ........04-208 8-6.
Page 14
CONTENTS 5. CONTROL SYSTEM CONTROL SYSTEM ..............05 - 01 1-1. LINE UP OF CONTROLLERS ..............05 - 01 1-2. CONTROL SYSTEM DESIGN ..............05 - 03 1-3. SYSTEM CONFIGURATION EXAMPLES ..........05 - 04 1-4. CONTROL SYSTEM FEATURES ............... 05 - 10 1-5.
Page 15
CONTENTS 5. CONTROL SYSTEM 2-15. PRESSURE SENSOR KIT ................ 05 - 102 2-16. GROUP CONTROL METHOD ..............05 - 112 2-17. COMPARISON TABLE OF CONTROLLERS ..........05 - 114 ADAPTOR / CONVERTOR UNITS ......... 05 - 116 3-1. NETWORK CONVERTOR ................. 05 - 117 3-2.
Page 16
CONTENTS CONTENTS 6. SYSTEM DESIGN 6. SYSTEM DESIGN 1. SYSTEM DESIGN ................. 06 - 01 1-1. REFRIGERANT SYSTEM ..............06 - 01 1-2. VRF NETWORK SYSTEM ..............06 - 04 1-3. MOUNTING POSITION ................06 - 10 2. PIPING DESIGN ................06 - 12 2-1.
Page 17
CONTENTS 7. FUNCTION SETTING SYSTEM SETTING ..............07 - 01 1-1. SYSTEM TYPE SETTING ................07 - 01 1-2. ADDRESS SETTING ................... 07 - 03 1-3. MANUAL ADDRESS SETTING METHOD ..........07 - 07 1-4. ADDRESS SETTING BY REMOTE CONTROLLER ........07 - 16 1-4-1.
1-2. INDOOR UNIT Various combinations of types and capacities, ranging from 4,000 to 60,000 Btu/h. LINE UP (1/3) Slim Medium Capacity Compact Circular flow duct/slim static Cassette Mini duct cassette cassette concealed pressure Model Btu/h floor duct code 4,000 7,500 9,500...
Page 26
LINE UP (2/3) Capacity High static Vertical air Compact Floor / ceiling Ceiling pressure duct handler floor Model Btu/h code 4,000 7,500 9,500 12,000 14,000 18,000 24,000 30,000 36,000 48,000 60,000 High static pressure duct Vertical air handler Compact floor ARUH36TLAV ARUV12TLAV...
Page 27
MODEL DESIGNATION Type Destination Model Model code Function Function Function Function Version AU: Cassette U: FUJITSU A: Standard (kBtu/h) T: Heat L: Inverter A: 1 Phase V: VRF (AU, AS) pump AR: Duct 7 (7.5) B: Large AB: Floor/Ceiling 9 (9.5)
1-3. CONTROLLER LINE UP Type Model System Controller UTY-APGXZ1 Option: UTY-PEGXZ1, UTY-PPGXP2 Option: UTY-PLGXA2, UTY-PLGXR2, System Controller Lite UTY-ALGXZ1 UTY-PLGXE2, UTY-PLGXP2, UTY-PLGXX2 Touch Panel Controller UTY-DTGYZ1 Option: UTY-PTGXA Central Remote Controller UTY-DCGY Wired Remote Controller (Touch panel) UTY-RNRUZ2 Wired Remote Controller UTY-RNKU Simple Remote Controller...
Page 29
MODEL DESIGNATION Series name Version Destination Type UTY : Control unit Y: FUJITSU APG: System Controller U: FUJITSU DTG: Touch Panel Controller (North American standard) DCG: Central Remote Controller X:Neutral brand RNR, RNK: Wired Remote Controller RSR, RSK: Simple Remote Controller...
Modbus ® ® open network for open network. ORKS management of small to medium- sized BMS. Thermostat Convertor Model: UTY-TTRX For control Fujitsu General products using a third-party thermostat. ® ® BACnet Gateway (Hardware) BACnet Gateway (Software) Model : UTY-VBGX...
Page 31
Service Tool Web Monitoring Tool Model : UTY-ASGXZ1 Model : UTY-AMGXZ1 Extensive monitoring and analysis Trouble free operation at all times by web monitoring system. functions for installation and The operation status of the VRF maintenance. Operation status network system within the and error history can be grasped building can be monitored in promptly and adequately.
1-5. BRANCH KIT Separation Tube Model :UTP-AX090A Liquid Pipe Gas Pipe Header Model : UTR-H0906L Model : UTR-H0908L Liquid Pipe Liquid Pipe Gas Pipe Gas Pipe - (01-11) -...
1-6. CASSETTE GRILLE Grid type grille Cassette grille Model: UTG-CCGVG Model : UTG-CCGV For Compact Cassette type For Compact Cassette type Cassette grille Cassette grille Model : UTG-LCGV Model : UTG-LCGVCW UTG-LCGVCB For Cassette type For Circular flow cassette type - (01-12) -...
1-7. OTHERS (optional parts) Flange (Square) Flange (Round) Model : UTD-SF045T Model : UTD-RF204 For Medium Static Pressure Duct type For Medium Static Pressure Duct type For Ceiling type Long-life Filter Long-life Filter Model : UTD-LF25NA Model : UTD-LF60KA For Medium Static Pressure Duct type For High Static Pressure Duct type x 2 pcs x 2 pcs...
Page 35
Panel spacer Wide panel Model : UTG-BGYA-W Model : UTG-AGYA-W For Cassette type For Cassette type For Circular flow cassette type For Circular flow cassette type Half concealed kit Model : UTR-STA For Compact Floor type IR Receiver Unit IR Receiver Unit Model : UTY-LRHYB1 Model: UTB-YWC For all Duct type...
Page 36
Fresh air intake kit Fresh air intake kit Model : UTZ-VXRA Model : UTZ-VXAA For Cassette type For Compact Cassette type For Circular flow cassette type Auto louver grille kit Auto louver grille kit Model : UTD-GXTA-W Models : UTD-GXSA-W *1 UTD-GXSB-W *2 *1 For Slim Duct (7-14 models) For Slim Duct (7-14 models)
Page 37
External connect kit External connect kit Model: UTY-XWZXZ6 Model : UTY-XWZXZ7 For Indoor unit / For Outdoor unit Central remote controller External connect kit External connect kit Model: UTY-XWZXZ8 Model : UTY-XWZXZ9 For Outdoor unit For Central remote controller External connect kit External connect kit Model : UTY-XWZXZA Model : UTY-XWZXZB...
Page 38
2. MODEL SELECTION DTV_J2U045E_05--CHAPTER02 2018.03.16...
Page 39
CONTENTS 2. MODEL SELECTION 1. MODEL SELECTION PROCEDURE..........02 - 01 2. MODEL LINE UP ................02 - 02 2-1. OUTDOOR UNIT ................02 - 02 2-2. INDOOR UNIT ................... 02 - 03 2-3. OPTIONAL PARTS ................02 - 05 3.
Page 40
CONTENTS 2. MODEL SELECTION 8. CAPACITY TABLE HEATING (INDOOR UNIT) ......02 - 51 8-1. COMPACT CASSETTE TYPE ............02 - 51 8-2. CIRCULAR FLOW CASSETTE TYPE ..........02 - 53 8-3. CASSETTE TYPE ................02 - 55 8-4. MINI DUCT TYPE ................02 - 57 8-5.
Page 41
1. MODEL SELECTION PROCEDURE See 2-2.MODEL LINE UP (INDOOR UNIT) and 3-1. SELECTION PROCEDURE OF INDOOR UNIT AND Selection of indoor units OUTDOOR UNIT Selection of required optional parts ● Cassette grille for all Cassette type See 2-3.MODEL LINE UP (OPTIONAL PARTS) See 2-1.MODEL LINE UP (OUTDOOR UNIT) and 3-1.
Page 42
2. MODEL LINE UP 2-1. OUTDOOR UNIT LINE UP Capacity Maximum connectable Indoor unit connectable (Btu/h) Model name indoor unit capacity (Btu/h) Cooling 36,000 AOU36RLAVM 18,000 to 46,800 48,000 AOU48RLAVM 24,000 to 62,400 60,000 AOU60RLAVM 30,000 to 78,000 - (02 - 02) -...
Page 43
2-2. INDOOR UNIT LINE UP Rated capacity (Btu/h) Type Model name Remarks Cooling Heating 4,000 4,400 AUUA4TLAV1 7,500 9,500 AUUA7TLAV 9,500 10,900 AUUA9TLAV Compact UTG-CCGVG (Grid type grille) 12,000 13,500 AUUA12TLAV cassette UTG-CCGV (Standard type grille) 14,000 15,600 AUUA14TLAV 18,000 20,000...
Page 44
LINE UP (2/2) Rated capacity (Btu/h) Type Model name Remarks Cooling Heating 4,000 4,400 ASUA4TLAV1 ASUA7TLAV 7,500 9,500 ASUA7TLAV1 ASUA9TLAV 9,500 10,900 ASUA9TLAV1 ASUA12TLAV 12,000 13,500 ASUA12TLAV1 Wall mounted ASUA14TLAV 14,000 15,600 ASUA14TLAV1 ASUB18TLAV 18,000 20,000 ASUB18TLAV1 ASUB24TLAV 24,000 27,000 ASUB24TLAV1...
2-3. OPTIONAL PARTS CONTROLLER Items Model name Remarks System Controller UTY-APGXZ1 Option: UTY-PEGXZ1, UTY-PPGXP2 Option: UTY-PLGXA2, UTY-PLGXR2, UTY-PLGXE2, UTY- System Controller Lite UTY-ALGXZ1 PLGXP2, UTY-PLGXX2 UTY-DTGYZ1 Option: UTY-PTGXA Touch Panel Controller UTY-DTGY Central Remote Controller UTY-DCGY Wired Remote Controller (Touch panel) UTY-RNRUZ2 2-wire type Wired Remote Controller...
Page 46
OTHERS Items Model name Remarks Flange (Square) UTD-SF045T For Medium Static Pressure Duct type For Medium Static Pressure Duct type Flange (Round) UTD-RF204 For Ceiling type UTD-LF25NA For Medium Static Pressure Duct type Air Filter UTD-LF60KA For High Static Pressure Duct type UTZ-PU1NBA For Medium Static Pressure Duct type Drain Pump Unit...
3. MODEL SELECTION AND CAPACITY CALCULATION 3-1. SELECTION PROCEDURE OF INDOOR UNIT AND OUTDOOR UNIT Please select indoor units and outdoor unit and make the capacity of each indoor unit be larger than cooling and heating load. Confirm the design indoor and outdoor temperature condition Calculate heat load of each room Select indoor unit to match the heat load for each room preliminarily Calculate the estimated capacity of each indoor units (Refer to 3-2)
Page 48
Select outdoor unit to match the total capacity of indoor units preliminarily (Confirm the rated capacity ratio of indoor and outdoor unit, the number of connectable indoor units within limit) Confirm if the capacity of outdoor unit. Calculate the compensated capacity of outdoor unit (Refer to 3-2) ●...
3-2. METHOD OF CAPACITY CALCULATION The capacity calculation method which takes the effects of air temperature, pipe length and frosting/defrosting into consideration is shown below. 1. Calculate the estimated capacity of each indoor unit. (1) Find capacity of indoor unit at rated condition (TCin)r and at design temperature (TCin)d [from 7.
3-3. THE EXAMPLE OF CALCULATION Outdoor Design conditions: unit ● Temperature Indoor : 82°FDB / 68°FWB (28°CDB / 20°CWB) Outdoor : 95°FDB (35°CDB) ● Pipe length : 229 ft. (70 m) ● Height difference : 66 ft. (20 m) (Outdoor unit upper side) Pipe length, L=229 ft.
Page 51
1) Equation for capacity calculation of outdoor unit. i) Refer to 4. CAPACIYY TABLE (OUTDOOR UNIT) to find Y and Y using X and X ii) Calculate capacity of outdoor unit using following equation: Y=(Y ) / (X ) (X-X ) + Y (X, Y) Capacity ratio of indoor units to outdoor unit, X (%)
6. CAPACITY COMPENSATION COEFFICIENT COMPENSATION COEFFICIENT OF PIPE LENGTH The tables give the compensation coefficient of pipe length owing to installation position (pipe length, height difference). Pipe length and height difference are the length and the height difference between outdoor unit and indoor unit. z Cooling ...
Page 68
COMPENSATION COEFFICIENT OF FROSTING / DEFROSTING (HEATING OPERATION) To take the effects of accumulated frost and defrosting operation on heating capacity into consideration, the capacity of outdoor unit should be corrected by compensation coefficient shown in the table below. °FDB / 5 / 3 16 / 14...
1. SPECIFICATIONS Nominal system capacity Model name AOU36RLAVM AOU48RLAVM AOU60RLAVM Power source 1 Phase 208 / 230V, 60 Hz Available voltage range 187 to 253 V Btu / h 36,000 48,000 60,000 Cooling 10.6 14.1 17.6 Capacity Btu / h 42,000 54,000 66,000...
Page 116
Defrost method Reversed cycle Compressor capacity control (Steps / Range) 81 steps / 20-100 % Connectable indoor units Number 1 - 6 1 - 8 1 - 9 Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95°F(35.0°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB.
3. INSTALLATION SPACE Caution ● The installation space shown in the following examples is based on an ambient temperature under cooling operation of 95 °F (35 °C) DB at the air intake of the outdoor unit. Provide more space around the air intake than shown in the examples if the ambient temperature exceeds 95 °F (35 °C) DB or if the thermal load of all of the outdoor units exceeds the capacity.
3-2. MULTIPLE OUTDOOR UNIT INSTALLATION ● Provide at least 1 in. (25mm) of space between the outdoor units if multiple units are installed. ● When routing the piping from the side of an outdoor unit, provide space for the piping. ...
Page 121
SYMBOL DESCRIPTION z Outdoor unit MARK DESCRIPTION Compressor (Inverter type) Heat exchanger FAN 1 Fan 1 FAN 2 Fan 2 Accumulator Oil separator SCHEX Sub-cool heat exchanger High pressure sensor Low pressure sensor HPSW High pressure sensor switch 4-way valve EEV 1 Electric expansion valve 1 EEV 2 Electric expansion valve 2...
6. OPERATION RANGE Operation range Operation mode Indoor unit Outdoor unit 65 to 89 °F DB 23 to 115°F DB Cooling / Dry 18 to 32°C DB -5 to 46°C DB R.H. 80% or less 50 to 86°F DB -4 to 70 °F DB Heating 10 to 30°C DB -20 to 21°C DB...
8. ELECTRIC CHARACTERISTICS Voltage MAX.CKT.BKR GFEB Model name AOU36RLAVM 208 / 230 30 mA AOU48RLAVM 208 / 230 0.1 sec or less AOU60RLAVM 208 / 230 MCA: Minimum Circuit Amp. MAX.CKT BKR: Maximum Circuit Braker ・ Select the appropriate breaker of the described specification according to the national or regional standards.
1. SPECIFICATIONS 1-1. COMPACT CASSETTE TYPE Model name AUUA4TLAV1 AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 4,000 7,500 9,500 12,000 14,000 Cooling Capacity Btu/h 4,400 9,500 10,900 13,500 15,600 Heating Input power...
Page 135
Model name AUUA18TLAV AUUA24TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 18,000 24,000 Cooling Capacity Btu/h 20,000 27,000 Heating Input power High (710) (1,030) Airflow rate / h) (580) (830) (400) (450) Type x Quantity Turbo ×...
1-2. CIRCULAR FLOW CASSETTE TYPE Model name AUUB18TLAV1 AUUB24TLAV1 AUUB30TLAV1 AUUB36TLAV1 AUUB48TLAV1 Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 18,000 24,000 30,000 36,000 48,000 Cooling 10.6 14.1 Capacity Btu/h 20,000 27,000 34,000 40,000 54,000 Heating...
1-3. CASSETTE TYPE Model name AUUB18TLAV AUUB24TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Capacity Btu/h 18,000 24,000 Cooling Btu/h 20,000 27,000 Heating Input power High (1,150) (1,280) Airflow rate / h) (940) (1,040) (870) (870)
Page 138
Model name AUUB30TLAV AUUB36TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Capacity Btu/h 30,000 36,000 Cooling 10.6 Btu/h 34,000 40,000 Heating 10.0 11.7 Input power 1,059 High (1,600) (1,800) Airflow rate / h) (1,300) (1,300) (1,100)
1-4. MINI DUCT TYPE Model name ARUL4TLAV1 Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Capacity Btu/h 4,000 Cooling Btu/h 4,400 Heating Input power Static pressure range in.WG(Pa) 0 to 0.12 (0 to 30) Standard static pressure in.WG(Pa) 0.04 (10)
1-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE Model name ARUL7TLAV ARUL9TLAV ARUL12TLAV ARUL14TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Capacity Btu/h 7,500 9,500 12,000 14,000 Cooling Btu/h 9,500 10,900 13,500 15,600 Heating Input power Static pressure range...
Page 141
Model name ARUL18TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Capacity Btu/h 18,000 Cooling Btu/h 20,000 Heating Input power Static pressure range in.WG(Pa) 0 to 0.36 (0 to 90) Standard static pressure in.WG(Pa) 0.10 (25) High (940)
1-6. MEDIUM STATIC PRESSURE DUCT TYPE Model name ARUM24TLAV ARUM30TLAV ARUM36TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Capacity Btu/h 24,000 30,000 36,000 Cooling 10.6 Btu/h 27,000 34,000 40,000 Heating 10.0 11.7 Input power Static pressure range in.WG(Pa) 0 to 0.60 (0 to 150)
1-7. HIGH STATIC PRESSURE DUCT TYPE Model name ARUH36TLAV ARUH48TLAV ARUH60TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 36,000 48,000 60,000 Cooling 10.6 14.1 17.6 Capacity Btu/h 40,000 54,000 67,000 Heating 11.7 15.8 19.6 Input power...
Page 144
Model name ARUH72TLAV1 ARUH96TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 72,000 96,000 Cooling 21.1 28.1 Capacity Btu/h 81,000 108,000 Heating 23.7 31.7 Input power Static pressure range in.WG(Pa) 0 to 1.2 (0 to 300) Standard static pressure in.WG(Pa) 0.60(150)
1-8. VERTICAL AIR HANDLER TYPE Model name ARUV12TLAV ARUV18TLAV ARUV24TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 12,000 18,000 24,000 Cooling Capacity Btu/h 13,500 20,000 27,000 Heating Input power 0.10 to 0.70 Static pressure range in.WG(Pa) 0.10 to 0.80 (25 to 200)
Page 146
Model name ARUV30TLAV ARUV36TLAV ARUV48TLAV ARUV60TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 30,000 36,000 48,000 60,000 Cooling 10.6 14.1 17.6 Capacity Btu/h 34,000 40,000 54,000 67,000 Heating 10.0 11.7 15.8 19.6 Input power Static pressure range in.WG(Pa)
1-9. COMPACT FLOOR TYPE Model name AGUA4TLAV1 AGUA7TLAV1 AGUA9TLAV1 AGUA12TLAV1 AGUA14TLAV1 Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 4,000 7,500 9,500 12,000 14,000 Cooling Capacity Btu/h 4,400 9,500 10,900 13,500 15,600 Heating Input power 12/14 224/253...
1-10. FLOOR / CEILING TYPE Model name ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 12,000 14,000 18,000 24,000 Cooling Capacity Btu/h 13,500 15,600 20,000 27,000 Heating Input power High (660) (780)
1-11. CEILING TYPE Model name ABUA30TLAV ABUA36TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 30,000 36,000 Cooling 10.6 Capacity Btu/h 34,000 40,000 Heating 10.0 11.7 Input power High (1,630) (1,690) Airflow rate / h) (1,370) (1,400)
1-12. WALL MOUNTED TYPE Model name ASUA4TLAV1 ASUA7TLAV1 ASUA9TLAV1 ASUA12TLAV1 ASUA14TLAV1 Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 4,000 7,500 9,500 12,000 14,000 Cooling Capacity Btu/h 4,400 9,500 10,900 13,500 15,600 Heating Input power High (430)
Page 151
Model name ASUB18TLAV1 ASUB24TLAV1 Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 18,000 24,000 Cooling Capacity Btu/h 20,000 27,000 Heating Input power High (840) (1,100) Airflow rate / h) (770) (910) (690) (730) Type x Quantity Cross flow ×...
Page 152
Model name ASUB30TLAV1 ASUB36TLAV1 Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 30,000 34,000 Cooling 10.0 Capacity Btu/h 34,000 38,000 Heating 10.0 11.2 Input power High 848 (1,440) 954/895 (1,620/1,520) Med-Hi 706 (1,200) 765 (1,300) 618 (1,050) 659 (1,120)
Page 153
Model name ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 7,500 9,500 12,000 14,000 Cooling Capacity Btu/h 9,500 10,900 13,500 15,600 Heating Input power High (490) (500) (560) (670) Airflow rate / h) (450)
Page 154
Model name ASUB18TLAV ASUB24TLAV Power source 1 Phase ~ 208/230V 60Hz Available voltage range 187 to 253 V Btu/h 18,000 24,000 Cooling Capacity Btu/h 20,000 27,000 Heating Input power High (840) (1,100) Airflow rate / h) (770) (910) (690) (730) Type x Quantity Cross flow ×...
Page 155
2. ELECTRIC CHARACTERISTICS Indoor Unit Power Supply Indoor Rated MAX.CKT. Input Voltage Frequency Current Type Model Power (Hz) (kW) AUUA4TLAV1 0.29 0.023 0.17 0.23 AUUA7TLAV 0.51 0.025 0.17 0.41 AUUA9TLAV 0.51 0.025 0.17 0.41 0.41 Compact cassette AUUA12TLAV 0.51 0.029 0.20 AUUA14TLAV 0.51...
Page 156
Indoor Unit Power Supply Indoor Rated MAX.CKT. Input Voltage Frequency Current Type Model Power (Hz) (kW) AGUA4TLAV1 0.22 0.014 0.13 0.17 AGUA7TLAV1 0.24 0.016 0.14 0.19 Compact floor AGUA9TLAV1 0.25 0.017 0.15 0.20 0.30 0.022 0.18 0.24 AGUA12TLAV1 AGUA14TLAV1 0.38 0.029 0.23 0.30...
Page 157
3. DIMENSIONS 3-1. COMPACT CASSETTE TYPE MODELS : AUUA4TLAV1, AUUA7TLAV, AUUA9TLAV, AUUA12TLAV, AUUA14TLAV, AUUA18TLAV, AUUA24TLAV Unit : in. (mm) Grid type grille 24-7/16 (620) Cassette grille Standard type Grid type 22-13/16 to 26 22-13/16 to 24 (580 to 660) (580 to 610) IR receiver Standard type grille...
Page 158
INSTALLATION LOCATION Unit : in. (mm) Strong and durable ceiling 11 (262) or more 40 (1,000) 40 (1,000) or more or more 71 (1,800) or more Obstruction Floor H (The maximum height from floor to ceiling) Model name AUUA7 AUUA9 AUUA12...
Page 160
INSTALLATION PLACE 11 in. (256 mm) or more (AUUB18,24,30) 12 in. (298 mm) or more (AUUB36,48) Strong and durable ceiling 60 in. (1,500 mm ) or more 119 in. (3,000 mm) or more 71 in. (1,800 mm) to H 40 in.
Page 162
INSTALLATION PLACE 11 in. (256 mm) or more (AUUB18,24,30) 12 in. (298 mm) or more (AUUB36,48) Strong and durable ceiling 60 in. (1,500 mm ) or more 119 in. (3,000 mm) or more 71 in. (1,800 mm) to H 40 in.
Page 163
3-3. CASSETTE TYPE MODELS : AUUB18TLAV, AUUB24TLAV Unit : in. (mm) IR receiver 37-3/8 (950) 31-5/16 (796) (Option) Hanging bolt position Drain hose View A 14-1/8 (358) (Control Box) 14-1/8 (358) 10-15/16 (278) 2-3/8 (60) 1-9/16 (40) ...
Page 164
MODELS : AUUB30TLAV, AUUB36TLAV Unit : in. (mm) IR receiver 37-3/8 (950) 31-5/16 (796) (Option) Hanging bolt position Drain hose View A 14-1/8 (358) (Control Box) 14-1/8 (358) 10-15/16 (278) 2-3/8 (60) 1-9/16 (40) Ceiling Wire hole 3-15/16 (100) 3-15/16 (100) 9-13/16 (250)
Page 165
Unit : in. (mm) INSTALLATION LOCATION Strong and durable ceiling 11 (256) or more (AUUB18,24) 12 (298) or more (AUUB30,36) (1,500) 119 (3,000) or more or more 71 (1,800) Obstruction or more Floor H (The maximum height from floor to ceiling) Model name AUUB18 AUUB24...
Page 166
3-4. MINI DUCT TYPE MODEL: ARUL4TLAV1 Unit : in. (mm) 2-1/16 22-5/8 (575) (52) Rear view View A (Drain hose) P3-15/16 (100) × 6 = 23-5/8 (600) 1-15/16 25-9/16 (650) (49) 3-1/16 29-5/8 (752) 2-3/16 1-15/16 (78) (56) (49) 2-5/8 Top view...
Page 167
Unit : in. (mm) INSTALLATION PLACE Strong and durable ceiling Indoor unit Left Right side side 16 (400) 6 (150) or or more more 16 (400) or more when drain from drain pipe • When intaking air from back 12 (300) or more 1 (5) or more 1 (20) or more...
Page 168
3-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE MODELS : ARUL7TLAV, ARUL9TLAV, ARUL12TLAV, ARUL14TLAV Unit : in. (mm) 22-5/8 (574) 2 (51) View A Rear view (Drain hose) Drain port 3-15/16 (100) x 6 = 23-5/8 (600) 1-7/8 (47) 2-3/16 (55) 25-9/16 (650) 3-1/16 (78)
Page 169
MODEL : ARUL18TLAV Unit : in. (mm) 2 (51) 30-1/2 (774) Rear view View A (Drain hose) Drain port 1-7/8 (47) 3-15/16 (100) x 8 = 31-1/2 (800) 2-3/16 (55) 3-1/16 (78) 33-7/16 (850) 3-1/2 (89) 36-3/4 (934) 4-11/16 (119) 3-7/16 (87) Top view...
Page 170
INSTALLATION LOCATION Unit : in. (mm) 12 (300) or more Strong and durable ceiling 1 (20) or more Indoor unit Left Right side side 1 (20) or more 16 (400) 6 (150) Service access Ceiling or more or more Floor 1 (10) 1 (10)
Page 171
MAINTENANCE SPACE Unit : in. (mm) Provide a service access for inspection purposes as shown below. Do not place any wiring or illumination in the service space, as they will impede service Service space [Top view] 16 (400) or more Indoor unit Service access...
Page 173
Unit : in. (mm) INSTALLATION LOCATION 1 Strong and durable ceiling 1 When drain pump is used, leave the space required for service and maintenance (Refer to chapter 10. 9-1. DRAIN PUMP UNIT) 2 When drain hose is connected, the required dimension is 16 (400) or more.
Page 174
3-7. HIGH STATIC PRESSURE DUCT TYPE MODELS : ARUH36TLAV, ARUH48TLAV, ARUH60TLAV Unit : in. (mm) Rear view 42-1/2 (1080) 39-3/8 (1000) 33-15/16 (862) : Inlet dimension Inlet dimension 6-1/8 (155) Drain port 12-Ø1/8 (3) P4-3/4 (120) x 2 Side view (R) = 9-7/16 (240) 1-1/8 (28)
Page 175
INSTALLATION LOCATION Unit : in. (mm) Strong and durable ceiling MAINTENANCE SPACE Provide a service access for inspection purposes as shown below. Do not place any wiring or illumination in the service space, as they will impede service.
Page 178
INSTALLATION LOCATION Unit : in. (mm) (a) When service access will be carried out above the indoor unit a recommended installation space of 18in.(450mm) is required. 18(450) more Service space 18(450) or more (b) Installation by which service is carried out from the bottom of the unit 1(20) Service space...
Page 179
3-8. VERTICAL AIR HANDLER TYPE MODEL: ARUV12TLAV Unit : in. (mm) Bottom view Top view Front view Side view ARUV12 Liquid ø 1/4 (6.35) Refrigerant pipe flare connection ø 1/2 (12.70) Drain port ø 3/4 (I.D.) ...
Page 180
MODELS: ARUV18TLAV, ARUV24TLAV Unit : in. (mm) Bottom view Top view Front view Side view ARUV18, ARUV24 Liquid ø 3/8 (9.52) Refrigerant pipe flare connection ø 5/8 (15.88) Drain port ø 3/4 (I.D.) - (04-47) -...
Page 181
MODEL: ARUV30TLAV Unit : in. (mm) Bottom view Top view Side view Front view ARUV30 Liquid ø 3/8 (9.52) Refrigerant pipe flare connection ø 5/8 (15.88) Drain port ø 3/4 (I.D.) - (04-48) -...
Page 182
MODEL: ARUV36TLAV Unit : in. (mm) Bottom view Top view Front view Side view ARUV36 Liquid ø 3/8 (9.52) Refrigerant pipe flare connection ø 3/4 (19.05) Drain port ø 3/4 (I.D.) - (04-49) -...
Page 183
MODELS: ARUV48TLAV, ARUV60TLAV Unit : in. (mm) Bottom view Top view Front view Side view ARUV48, ARUV60 Liquid ø 3/8 (9.52) Refrigerant pipe flare connection ø 3/4 (19.05) Drain port ø 3/4 (I.D.) - (04-50) -...
Page 184
INSTALLATION LOCATION Unit : in. (mm) Top view 2 (51) or more 3 (76) or more 3 (76) or more 6 (152) or more 36 (914) or more 6 (152) 6 (152) or more or more 36 (914) or more 36 (914) or more...
Page 186
INSTALLATION PLACE Unit : in. (mm) 4 (100) or more 4 (80) or more 4 (80) or more 2 (50) or more (Wall cap) 6 (150) or below from the floor 4 (100) or more 4 (80) or more 4 (80) or more Indoor Upper air outlet...
Page 188
INSTALLATION LOCATION Unit : in. (mm) Left Right 12 (300) or more 12 (300) or more Ceiling Ceiling Left Right Indoor unit 91 (2300) 6 (150) or more 12 (300) or more 1 (20) or more or more Floor 39 (990) 9-5/8...
Page 190
INSTALLATION LOCATION Unit : in. (mm) Ceiling Ceiling panel INDOOR UNIT INDOOR UNIT Ceiling Ceiling panel 4 (80) 6 (150) 4 (80) 6 (150) or more or more or more or more 1 (10) or more 1 (10) or more 99 (2500) or more 99 (2500)
Page 191
3-12. WALL MOUNTED TYPE MODELS: ASUA4TLAV1, ASUA7TLAV1, ASUA9TLAV1 Unit : in. (mm) 32-5/16 (820) 8-1/8 (206) 16-15/16 (431) 1/8 (3) 19-3/16 (487) 15/16 (24) 26-9/16 (675) 32-5/16 (820) 1-7/8 (48) 14 (355) 13-9/16 (345) 2-13/16 (72) Outline of unit 3-9/16 (91) 12-5/16 (312) 12-5/8 (321)
Page 192
INSTALLATION PLACE Unit : in. (mm) Outline of unit 8 (200) or more 3 (70) or more 60 (1,500) or more - (04-59) -...
Page 193
MODELS: ASUA12TLAV1, ASUA14TLAV1 Unit : in. (mm) 33-1/16 (840) 8 (203) 33-1/16 (840) 16-1/8 (410) 16-15/16 (430) 12-3/16 (310) 11-5/8 (295) Gas pipe: 12-3/8 (315) Liquid pipe: 15 (381) ø2-9/16 (65) ø2-9/16 (65) for pipe inlet for pipe inlet 6-1/2 (165) 5-11/16 (144) 9-3/16 (233)
Page 194
INSTALLATION PLACE Unit : in. (mm) 1 (25) 5 (122) 3 (70) 8 (200) 60 (1,500) - (04-61) -...
Page 196
INSTALLATION PLACE Unit : in. (mm) Outline of unit 6 (133) 1 (22) or more or more 8 (200) or more 2 (50) or more 60 (1500) or more - (04-63) -...
Page 198
INSTALLATION PLACE Unit : in. (mm) Outline of unit 3 (59) 5 (120) or more or more 3 (70) 8 (200) or more or more 60 (1500) or more - (04-65) -...
Page 199
MODELS : ASUA7TLAV, ASUA9TLAV, ASUA12TLAV, ASUA14TLAV Unit : in. (mm) 8-7/16 (215) 31-1/8 (790) 18-1/2 (470) 20-7/8 (530) 26 (660) 15/16 (24) 18-1/2 (470) 20-7/8 (530) 14-7/8 (378) 16-1/4 (412) 3/16 x 3/4 (5 x 19) (hole) for bolt 9-15/16 (252.5) 8-1/16 (204) 7-1/2 (191)
Page 200
INSTALLATION LOCATION Unit : in. (mm) Outline of unit 2 (49) or more 2 (44) or more 3 (60) or more 4 (90) or more 60 (1500) or more - (04-67) -...
Page 201
MODELS : ASUB18TLAV, ASUB24TLAV Unit : in. (mm) 39-5/16 (998) 20-1/2 (520) 23-1/4 (590) 9 (228) 1 (25) 28-3/8 (721) 20-1/2 (520) 13/16 (20) 1-7/16 (37) Unit center 15-3/4 (400) 17-5/16 (439) 11/16 x 7/16 (18 x 11) hole 5/8 (16) 4-7/16 (113) 15-1/4 (387)
Page 202
INSTALLATION PLACE Unit : in. (mm) Outline of unit 1 (22) or more 6 (133) or more 2 (50) or more 8 (200) or more 60 (1500) or more - (04-69) -...
Page 222
5. AIR VELOCITY AND TEMPERATURE DISTRIBUTIONS 5-1. COMPACT CASSETTE TYPE Conditions MODEL: AUUA4TLAV1 Fan speed : High Operation mode : Fan Voltage : 230V z Air velocity distribution Top view Vertical airflow direction louver : Up (ft.) Unit : ft./s (m/s) 1 (0.25) 2 (0.5)
Page 223
Conditions Fan speed : High Operation mode : Heat Voltage : 230V z Air velocity distribution Reference Data Side view Vertical airflow direction louver : Down (ft.) Unit : ft./s (m/s) 7 (2.0) 5 (1.5) 3 (1.0) 2 (0.5) 1 (0.25) (ft.) z Air temperature distribution...
Page 224
Conditions MODEL : AUUA7TLAV Fan speed : High Operation mode : Fan z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 13 4 10 3 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) 2 (0.5) 7 (2.0) 7 (2.0) 3 (1.0) 3 (1.0)
Page 225
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 9 2.7 8 2.5 7 (2.0) 5 (1.5) 3 (1.0) 2 (0.5) 1 (0.25) (ft.) z Air temperature distribution ...
Page 226
Conditions Fan speed : High MODEL : AUUA9TLAV Operation mode : Fan z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 13 4 10 3 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) 2 (0.5) 3 (1.0) 7 (2.0) 7 (2.0) 1 (0.25)
Page 227
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 9 2.7 8 2.5 7 (2.0) 5 (1.5) 3 (1.0) 2 (0.5) 1 (0.25) (ft.) z Air temperature distribution ...
Page 228
Conditions Fan speed : High MODEL : AUUA12TLAV Operation mode : Fan z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 13 4 1 (0.25) 10 3 2 (0.5) 3 (1.0) 7 (2.0) 2 (0.5) 7 (2.0) 1 (0.25) 7 (2.0) 1 (0.25)
Page 229
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 9 2.7 8 2.5 5 (1.5) 3 (1.0) 2 (0.5) 1 (0.25) (ft.) z Air temperature distribution (ft.) (m) Unit : °F...
Page 230
Conditions Fan speed : High MODEL : AUUA14TLAV Operation mode : Fan z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 13 4 1 (0.25) 10 3 2 (0.5) 3 (1.0) 7 (2.0) 2 (0.5) 7 (2.0) 1 (0.25) 2 (0.5) 1 (0.25)
Page 231
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 9 2.7 8 2.5 7 (2.0) 5 (1.5) 3 (1.0) 2 (0.5) 1 (0.25) (ft.) z Air temperature distribution ...
Page 232
Conditions Fan speed : High MODEL : AUUA18TLAV Operation mode : Fan z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 13 4 10 3 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) 7 (2.0) 2 (0.5) 7 (2.0) 1 (0.25) 3 (1.0)
Page 233
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 9 2.7 8 2.5 7 (2.0) 5 (1.5) 3 (1.0) 2 (0.5) 1 (0.25) (ft.) z Air temperature distribution ...
Page 234
Conditions Fan speed : High MODEL : AUUA24TLAV Operation mode : Fan z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 13 4 1 (0.25) 2 (0.5) 10 3 3 (1.0) 7 (2.0) 3 (1.0) 7 (2.0) 7 (2.0) 3 (1.0) 2 (0.5)
Page 235
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 9 2.7 8 2.5 7 (2.0) 5 (1.5) 3 (1.0) 2 (0.5) 1 (0.25) (ft.) z Air temperature distribution ...
Page 236
5-2. CIRCULAR FLOW CASSETTE TYPE Conditions Fan speed : High Operation mode : Fan MODEL: AUUB018TLAV1 z Air velocity distribution Top view Vertical airflow direction louver : Up (ft.) Unit: ft./s (m/s) 2 (0.5) 3 (1.0) 7 (2.0) 3 (1.0) 1 (0.25) (0.25)
Page 237
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution Side view Vertical airflow direction louver : Down Unit: ft./s (m/s) (ft.) 7 (2.0) 7 (2.0) 3 (1.0) 3 (1.0) 2 (0.5) 2 (0.5) 1 (0.25) 1 (0.25) (ft.)
Page 238
Conditions Fan speed : High MODEL: AUUB24TLAV1 Operation mode : Fan z Air velocity distribution Top view Vertical airflow direction louver : Up (ft.) Unit: ft./s (m/s) 2 (0.5) (1.0) 7 (2.0) 1 (0.25) 1 (0.25) 2 (0.5) 3 (1.0) 3 (1.0) 2 (0.5)
Page 239
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution Side view Vertical airflow direction louver : Down Unit: ft./s (m/s) (ft.) 7 (2.0) 7 (2.0) 3 (1.0) 3 (1.0) 2 (0.5) 2 (0.5) 1 (0.25) 1 (0.25) (ft.)
Page 240
Conditions Fan speed : High MODEL: AUUB30TLAV1 Operation mode : Fan z Air velocity distribution Top view Vertical airflow direction louver : Up (ft.) Unit: ft./s (m/s) 2 (0.5) 3 (1.0) 7 (2.0) 1 (0.25) 1 (0.25) 2 (0.5) 3 (1.0) 3 (1.0)
Page 241
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution Side view Vertical airflow direction louver : Down Unit: ft./s (m/s) (ft.) 7 (2.0) 7 (2.0) 3 (1.0) 3 (1.0) 2 (0.5) 2 (0.5) 1 (0.25) 1 (0.25) (ft.)
Page 242
Conditions Fan speed : High MODEL: AUUB36TLAV1 Operation mode : Fan z Air velocity distribution Top view Vertical airflow direction louver : Up (ft.) Unit: ft./s (m/s) 2 (0.5) 3 (1.0) 7 (2.0) 1 (0.25) 1 (0.25) 2 (0.5) 2 (0.5) 3 (1.0)
Page 243
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution Side view Vertical airflow direction louver : Down (ft.) Unit: ft./s (m/s) 7 (2.0) 7 (2.0) 3 (1.0) 3 (1.0) 2 (0.5) 2 (0.5) 1 (0.25) 1 (0.25) (ft.)
Page 244
Conditions Fan speed : High MODEL: AUUB48TLAV1 Operation mode : Fan z Air velocity distribution Top view Vertical airflow direction louver : Up (ft.) Unit: ft./s (m/s) 3 (1.0) 2 (0.5) 1 (0.25) 1 (0.25) 7 (2.0) 2 (0.5) 7 (2.0) 3 (1.0)
Page 245
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution Side view Vertical airflow direction louver : Down (ft.) Unit: ft./s (m/s) 7 (2.0) 7 (2.0) 3 (1.0) 3 (1.0) 2 (0.5) 2 (0.5) 1 (0.25) 1 (0.25) (ft.)
Page 246
5-3. CASSETTE TYPE Conditions MODEL : AUUB18TLAV Fan speed : High Operation mode : Fan z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 1 (0.25) 13 4 2 (0.5) 3 (1.0) 7 (2.0) 1 (0.25) 2 (0.5) 1 (0.25) 2 (0.5)
Page 247
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 10 3 7 (2.0) 5 (1.5) 3 (1.0) 2 (0.5) 1 (0.25) (ft.) z Air temperature distribution (ft.) (m) Unit : °F...
Page 248
Conditions Fan speed : High MODEL : AUUB24TLAV Operation mode : Fan z Air velocity distribution Unit : ft./s (m/s) (ft.) (m) 1 (0.25) 13 4 2 (0.5) 3 (1.0) 7 (2.0) 1 (0.25) 2 (0.5) 2 (0.5) 1 (0.25) 3 (1.0) 7 (2.0)
Page 249
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 10 3 7 (2.0) 5 (1.5) 3 (1.0) 2 (0.5) 1 (0.25) (ft.) z Air temperature distribution (ft.) (m) Unit : °F...
Page 250
Conditions Fan speed : High MODEL : AUUB30TLAV Operation mode : Fan z Air velocity distribution Unit : ft./s (m/s) (ft.) (m) (0.25) 13 4 2 (0.5) 3 (1.0) 7 (2.0) 1 (0.25) 2 (0.5) 1 (0.25) 2 (0.5) 7 (2.0) 3 (1.0)
Page 251
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 10 3.2 7 (2.0) 5 (1.5) 3 (1.0) 2 (0.5) 1 (0.25) (ft.) z Air temperature distribution (ft.) (m) Unit : °F...
Page 252
Conditions Fan speed : High MODEL : AUUB36TLAV Operation mode : Fan z Air velocity distribution Unit : ft./s (m/s) (ft.) (m) (0.25) 13 4 2 (0.5) 3 (1.0) 7 (2.0) 1 (0.25) 2 (0.5) 2 (0.5) 1 (0.25) 7 (2.0) 3 (1.0)
Page 253
Conditions Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution (ft.) (m) Unit : ft./s (m/s) 10 3.2 7 (2.0) 5 (1.5) 3 (1.0) 2 (0.5) 1 (0.25) (ft.) z Air temperature distribution (ft.) (m) Unit : °F...
Page 254
5-4. MINI DUCT TYPE with Auto louver grille kit MODEL: ARUL4TLAV1 (UTD-GXTA-W) Note: This data is measured with the Auto louver grille kit(option) installed. z Air velocity distribution Conditions Fan speed : High Operation mode : Fan (ft.) Unit: ft./s (m/s) Top view...
Page 255
Conditions Fan speed : High Operation mode : Heat z Air velocity distribution Reference Data (ft.) Unit: ft./s (m/s) 7 (2.0) Side view Vertical airflow direction louver: Down 3(1.0) Horizontal airflow direction louver: Center 2 (0.5) (ft.) z Air temperature distribution ...
Page 256
5-5. SLIM DUCT TYPE with Auto louver grille kit Conditions Fan speed : High MODEL : ARUL7TLAV (UTD-GXSA-W) Operation mode : Fan Note: Velocity distribution data based on measurements with Auto louver grille kit installed. z Air velocity distribution ...
Page 257
Note: Velocity distribution data based on measurements with Auto louver Conditions grille kit installed. Fan speed : High Operation mode : Heat Reference Data z Air velocity distribution Unit: ft./s (m/s) (ft.) Side view Vertical airflow direction 3 (1.0) louver : Down Horizontal airflow direction 7 (2.0)
Page 258
Conditions Fan speed : High Operation mode : Fan MODEL : ARUL9TLAV (UTD-GXSA-W) Note: Velocity distribution data based on measurements with Auto louver grille kit installed. z Air velocity distribution (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction 7 (2.0) 3 (1.0) 2 (0.5)
Page 259
Conditions Fan speed : High Note: Velocity distribution data based on measurements with Auto louver grille kit Operation mode : Heat installed. Reference Data z Air velocity distribution Unit: ft./s (m/s) (ft.) Side view Vertical airflow direction 3 (1.0) louver : Down Horizontal airflow direction 7 (2.0)
Page 260
Conditions Fan speed : High Operation mode : Fan MODEL : ARUL12TLAV (UTD-GXSA-W) Note: Velocity distribution data based on measurements with Auto louver grille kit installed. z Air velocity distribution (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction 7 (2.0) 3 (1.0) 2 (0.5)
Page 261
Conditions Fan speed : High Note: Velocity distribution data based on measurements with Auto louver grille kit Operation mode : Heat installed. Reference Data z Air velocity distribution Unit: ft./s (m/s) (ft.) Side view Vertical airflow direction 3 (1.0) louver : Down Horizontal airflow direction 7 (2.0)
Page 262
Conditions Fan speed : High Operation mode : Fan MODEL : ARUL14TLAV (UTD-GXSA-W) Note: Velocity distribution data based on measurements with Auto louver grille kit installed. Air velocity distribution (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction 7 (2.0) 3 (1.0) 2 (0.5)
Page 263
Conditions Fan speed : High Note: Velocity distribution data based on measurements with Auto louver grille kit Operation mode : Heat installed. Reference Data z Air velocity distribution Unit: ft./s (m/s) (ft.) Side view Vertical airflow direction 3 (1.0) louver : Down Horizontal airflow direction 7 (2.0)
Page 264
Conditions Fan speed : High Operation mode : Fan MODEL : ARUL18TLAV (UTD-GXSB-W) Note: Velocity distribution data based on measurements with Auto louver grille kit installed. (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction 7 (2.0) 3 (1.0) 2 (0.5) louver : Up Horizontal airflow direction...
Page 265
Conditions Fan speed : High Note: Velocity distribution data based on measurements with Auto louver grille kit Operation mode : Heat installed. Reference Data Air velocity distribution Unit: ft./s (m/s) (ft.) Side view Vertical airflow direction 3 (1.0) louver : Down Horizontal airflow direction 2 (0.5) 7 (2.0)
Page 266
5-6. COMPACT FLOOR TYPE MODEL: AGUA4TLAV1 Conditions: Fan speed : HI Operation mode : FAN Fan select : UPPER&LOWER (ft.) Unit : ft./s (m/s) : UPPER FAN : LOWER FAN 3 (1.0) 2 (0.5) Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center LOWER UPPER...
Page 267
MODEL: AGUA7TLAV1 Conditions: Fan speed : HI Operation mode : FAN Fan select : UPPER&LOWER (ft.) Unit : ft./s (m/s) : UPPER FAN : LOWER FAN 3 (1.0) 2 (0.5) Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center LOWER UPPER (ft.)
Page 268
MODEL: AGUA12TLAV1 Conditions: Fan speed : HI Operation mode : FAN Fan select : UPPER&LOWER (ft.) Unit : ft./s (m/s) : UPPER FAN : LOWER FAN 3 (1.0) 2 (0.5) Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center UPPER LOWER (ft.)
Page 269
MODEL: AGUA14TLAV1 Conditions: (ft.) Unit : ft./s (m/s) Fan speed : HI Operation mode : FAN Fan select : UPPER&LOWER 2 (0.5) : UPPER FAN 3 (1.0) : LOWER FAN Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center LOWER UPPER (ft.)
Page 270
5-7. FLOOR / CEILING TYPE MODELS : ABUA12TLAV, ABUA14TLAV (FLOOR CONSOLE) Conditions Fan speed : High Operation mode : Fan (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction louver : Down Horizontal airflow direction 7 (2.0) 3 (1.0) 1 (0.25) 2 (0.5) louver : Center...
Page 271
MODELS : ABUA12TLAV, ABUA14TLAV (UNDER CEILING) Conditions Fan speed : High (ft.) Unit: ft./s (m/s) Operation mode : Fan Top view Vertical airflow direction louver : UP 7 (2.0) 3 (1.0) 2 (0.5) 1 (0.25) Horizontal airflow direction louver : Center (ft.) Unit: ft./s (m/s)
Page 272
Conditions MODEL : ABUA18TLAV (FLOOR CONSOLE) Fan speed : High Operation mode : Fan (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction louver : Down Horizontal airflow direction 7 (2.0) 3 (1.0) 2 (0.5) 1 (0.25) louver : Center (ft.) Unit: ft./s (m/s) (ft.)
Page 273
Conditions MODEL : ABUA18TLAV (UNDER CEILING) Fan speed : High Operation mode : Fan (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction louver : UP 7 (2.0) 3 (1.0) 1 (0.25) Horizontal airflow direction 2 (0.5) louver : Center (ft.) Unit: ft./s (m/s) (ft.)
Page 274
Conditions MODEL : ABUA24TLAV (FLOOR CONSOLE) Fan speed : High Operation mode : Fan (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction louver : Down Horizontal airflow direction 7 (2.0) 3 (1.0) 1 (0.25) 2 (0.5) louver : Center (ft.) Unit: ft./s (m/s) (ft.)
Page 275
Conditions MODEL : ABUA24TLAV (UNDER CEILING) Fan speed : High Operation mode : Fan (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction louver : UP Horizontal airflow direction 7 (2.0) 3 (1.0) 1 (0.25) 2 (0.5) louver : Center (ft.) Unit: ft./s (m/s) (ft.)
Page 276
5-8. CEILING TYPE Conditions MODEL : ABUA30TLAV Fan speed : High Operation mode : Fan Unit: ft./s (m/s) (ft.) Top view Vertical airflow direction louver : Up 3 (1.0) 1 (0.25) Horizontal airflow direction louver : Center 2 (0.5) 7 (2.0) (ft.) Unit: ft./s (m/s)
Page 277
Conditions MODEL : ABUA36TLAV Fan speed : High Operation mode : Fan Unit: ft./s (m/s) (ft.) Top view Vertical airflow direction louver : Up 3 (1.0) 1 (0.25) Horizontal airflow direction louver : Center 2 (0.5) 7 (2.0) (ft.) Unit: ft./s (m/s) (ft.)
Page 278
5-9. WALL MOUNTED TYPE Conditions Fan speed : High Operation mode : Fan MODEL: ASUA4TLAV1 Voltage : 230V (ft.) Unit : ft./s (m/s) 3 (2.0) 2 (1.0) Top view Vertical airflow direction louver: Up 1 (0.5) Horizontal airflow direction louver: Center 26 (ft.) (ft.) Unit : ft./s (m/s)
Page 279
Conditions Fan speed : High Operation mode : Fan MODEL: ASUA7TLAV1 Voltage : 230V (ft.) Unit : ft./s (m/s) 1 (2.0) 2 (1.0) Top view 1 (0.5) Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 26 (ft.) (ft.) Unit : ft./s (m/s) 10 3...
Page 280
Conditions Fan speed : High Operation mode : Fan MODEL: ASUA9TLAV1 Voltage : 230V (ft.) Unit : ft./s (m/s) 7 (2.0) Top view 1 (0.5) Vertical airflow direction louver: Up 3 (1.0) Horizontal airflow direction louver: Center 26 (ft.) (ft.) Unit : ft./s (m/s) 10 3...
Page 281
Conditions Fan speed : High Operation mode : Fan MODEL: ASUA12TLAV1 Voltage : 230V (ft.) Unit : ft./s (m/s) 7 (2.0) Top view 1 (0.5) 3 (1.0) Vertical airflow direction louver: Up Horizontal airflow direction louver: Center (ft.) (ft.) Unit : ft./s (m/s) 10 3...
Page 282
Conditions Fan speed : High Operation mode : Fan MODEL: ASUA14TLAV1 Voltage : 230V (ft.) Unit : ft./s (m/s) 3 (1.0) 7 (2.0) Top view 1 (0.5) Vertical airflow direction louver: Up Horizontal airflow direction louver: Center (ft.) (ft.) Unit : ft./s (m/s) 10 3...
Page 283
Conditions MODEL: ASUB18TLAV1 Fan speed : High Operation mode : Fan Voltage : 230V (ft.) Unit : ft./s (m/s) Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 3 (1.0) 7 (2.0) 1 (0.5) (ft.) (ft.) Unit : ft./s (m/s) 1 (0.5)
Page 284
Conditions MODEL: ASUB24TLAV1 Fan speed : High Operation mode : Fan Voltage : 230V (ft.) Unit : ft./s (m/s) Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center (ft.) (ft.) Unit : ft./s (m/s) Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Right &...
Page 285
Conditions MODEL: ASUB30TLAV1 Fan speed : High Operation mode : Fan Voltage : 230V (ft.) Unit : ft./s (m/s) Top view 7 (2.0) 3 (1.0) 4 (1.5) Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 1 (0.5) (ft.) (ft.) Unit : ft./s (m/s)
Page 286
Conditions MODEL: ASUB36TLAV1 Fan speed : High Operation mode : Fan Voltage : 230V (ft.) Unit : ft./s (m/s) 1 (0.5) Top view 7 (2.0) 4 (1.5) 3 (1.0) Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 10 11 13 14 15 16 20 23 26...
Page 287
Conditions MODELS : ASUA7TLAV, ASUA9TLAV Fan speed : High Operation mode : Fan (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction louver : Up 7 (2.0) 3 (1.0) 2 (0.5) 1 (0.25) Horizontal airflow direction louver : Center (ft.) (ft.) Unit: ft./s (m/s)
Page 288
Conditions MODEL : ASUA12TLAV Fan speed : High Operation mode : Fan (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction louver : Up 7 (2.0) 3 (1.0) 1 (0.25) 2 (0.5) Horizontal airflow direction louver : Center (ft.) (ft.) Unit: ft./s (m/s)
Page 289
Conditions MODEL : ASUA14TLAV Fan speed : High Operation mode : Fan (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction louver : Up 7 (2.0) 3 (1.0) 1 (0.25) 2 (0.5) Horizontal airflow direction louver : Center (ft.) (ft.) Unit: ft./s (m/s)
Page 290
Conditions MODEL : ASUB18TLAV Fan speed : High Operation mode : Fan (ft.) Unit: ft./s (m/s) Top view Vertical airflow direction 7 (2.0) louver : Up 3 (1.0) 2 (0.5) Horizontal airflow direction louver : Center (ft.) Unit: ft./s (m/s) (ft.) 7 (2.0) 2 (0.5)
Page 291
Conditions MODEL : ASUB24TLAV Fan speed : High Operation mode : Fan Unit: ft./s (m/s) (ft.) Top view Vertical airflow direction louver : Up 7 (2.0) 3 (1.0) 2 (0.5) Horizontal airflow direction louver : Center (ft.) Unit: ft./s (m/s) (ft.) 7 (2.0) 2 (0.5)
Page 292
6. FAN PERFORMANCE CURVE 6-1. MINI DUCT TYPE MODEL: ARUL4TLAV1 0.24 (60) 0.20 (50) SP mode03 Hi (SP mode03) 0.16 (40) upper limit SP mode03 Normal SP lower limit 0.12 (30) upper limit Lo (SP mode03) Hi (Normal SP) 0.08 (20) SP mode00 Normal SP...
6-5. VERTICAL AIR HANDLER TYPE MODEL : ARUV12TLAV 1.00 (250) Hi (SP mode27) 0.80 (200) Hi SP upper limit Hi (Hi SP) 0.60 (150) Normal SP Hi SP lower upper limit limit Med (Lo SP) Hi (Normal SP) Lo (Hi SP) Lo (Normal SP) 0.40 (100)
Page 319
MODEL : ARUV18TLAV 1.00 (250) Hi (SP mode27) 0.80 (200) Hi SP Hi (Hi SP) upper limit Normal SP Hi SP lower 0.60 (150) upper limit limit Med (Lo SP) Lo (Hi SP) Hi (Normal SP) Lo (Normal SP) 0.40 (100) Normal SP Lo SP...
Page 321
MODEL : ARUV24TLAV 1.00 (250) Hi (SP mode27) 0.80 (200) Hi SP Hi (Hi SP) upper limit Normal SP 0.60 (150) upper limit Hi SP lower Med (Lo SP) limit Lo (Hi SP) Hi (Normal SP) Lo (Normal SP) 0.40 (100) Lo SP upper limit...
Page 323
MODEL : ARUV30TLAV 1.00 (250) Hi (SP mode27) 0.80 (200) Hi SP Hi (Hi SP) upper limit Hi SP lower 0.60 (150) Normal SP limit upper limit Med (Lo SP) Hi (Normal SP) Lo (Hi SP) Lo (Normal SP) 0.40 (100) Lo SP upper limit...
Page 325
MODEL : ARUV36TLAV 1.00 (250) Hi (SP mode27) 0.80 (200) Hi SP Hi (Hi SP) upper limit Normal SP upper limit 0.60 (150) Med (Lo SP) Hi (Normal SP) Lo (Hi SP) Lo (Normal SP) Hi (Lo SP) Med (Hi SP) 0.40 (100) Med (Normal SP)
Page 327
MODEL : ARUV48TLAV 1.00 (250) Hi (SP mode27) 0.80 (200) Hi SP Hi (Hi SP) upper limit Normal SP Hi (Normal SP) upper limit 0.60 (150) Hi SP lower limit Med (Lo SP) Lo (Hi SP) 0.40 (100) Hi (Lo SP) Lo (Normal SP) Med (Hi SP)
Page 329
MODEL : ARUV60TLAV 1.00 (250) Hi (SP mode27) Hi SP Normal SP 0.80 (200) upper limit upper limit Hi (Hi SP) Hi (Normal SP) 0.60 (150) Med (Lo SP) Hi (Lo SP) Lo (Hi SP) Med (Hi SP) Lo (Normal SP) Med (Normal SP) 0.40 (100)
Page 331
6-6. CEILING TYPE (FRESH AIR) MODELS : ABUA30TLAV, ABUA36TLAV z Air flow volume - Static pressure of Fresh air intake characteristic 0.020 (5) 0.016 (4) 0.012 (3) 0.008 (2) AB30 0.004 (1) AB36 0 (0) Air flow [CFM (m /min)] z Installation ...
Page 332
6-7. CASSETTE TYPE (FRESH AIR) MODELS : AUUB18TLAV, AUUB24TLAV, AUUB30TLAV, AUUB36TLAV z Fresh Air volume & Static Pressure required at Fresh Air intake. 0.39 (98) Unit : in. (mm) Duct (Inside Dia. ø2-3/4 (70)) 0.20 (49) Duct Fan 0 (0) 11.0 14.1...
Page 333
7. AIR FLOW Airflow Airflow Type Model Type Model High High AUUA4 450/420 125/117 265/247 Me-Hi 350/300 97/83 206/177 ARUL4 Mini duct High Lo-Hi AUUA7 High High AUUA9 ARUL7 High High Compact AUUA12 ARUL9 Cassette Slim Duct High High / Slim AUUA14 ARUL12 Concealed...
Page 334
Airflow Airflow Type Model Type Model High 380/430 106/119 224/253 High Me-Hi Me-Hi ASUA4 AGUA4 TLAV1 Lo-Hi Lo-Hi High High Me-Hi Me-Hi ASUA7 AGUA7 TLAV1 Lo-Hi Lo-Hi High High Me-Hi Me-Hi ASUA9 Compact AGUA9 TLAV1 floor Lo-Hi Lo-Hi High High Me-Hi Me-Hi ASUA12...
Page 335
8. NOISE LEVEL CURVE 8-1. COMPACT CASSETTE TYPE MODEL : AUUA4TLAV1 z COOLING z HEATING N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 N C -50 N C -50 N C -45 N C -45 N C -40...
Page 336
MODEL : AUUA12TLAV MODEL : AUUA14TLAV N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 N C -50 N C -50 N C -45 N C -45 H igh H igh N C -40 N C -40...
Page 338
MODEL: AUUB36TLAV1 MODEL: AUUB48TLAV1 NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 High NC-40 NC-40 High NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz - (04-205) -...
Page 339
8-3. CASSETTE TYPE MODEL : AUUB18TLAV MODEL : AUUB24TLAV N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 N C -50 N C -50 H igh N C -45 N C -45 M ed H igh...
Page 340
8-4. MINI DUCT TYPE MODEL: ARUL4TLAV1 NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 High NC-25 NC-20 NC-15 1,000 2,000 4,000 8,000 Octave band center frequency, Hz - (04-207) -...
Page 341
8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE MODEL : ARUL7TLAV MODEL : ARUL9TLAV NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 High NC-30 NC-30 High NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000...
Page 342
MODEL : ARUL18TLAV NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 High NC-30 NC-25 NC-20 NC-15 1,000 2,000 4,000 8,000 Octave band center frequency, Hz - (04-209) -...
Page 343
8-6. MEDIUM STATIC PRESSURE DUCT TYPE MODEL : ARUM24TLAV MODEL : ARUM30TLAV NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 High High NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000...
Page 344
8-7. HIGH STATIC PRESSURE DUCT TYPE MODEL : ARUH36TLAV MODEL : ARUH48TLAV NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 High High NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000...
Page 345
MODEL : ARUH72TLAV1 MODEL : ARUH96TLAV NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 High NC-50 NC-50 NC-45 NC-45 High NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
Page 346
8-8. VERTICAL AIR HANDLER TYPE MODEL : ARUV12TLAV MODEL : ARUV18TLAV NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 High NC-45 High NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
Page 347
MODEL : ARUV36TLAV MODEL : ARUV48TLAV NC-65 NC-65 NC-60 NC-60 High NC-55 NC-55 High NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
Page 354
MODEL: ASUB18TLAV1 MODEL: ASUB24TLAV1 NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 High NC-45 NC-45 NC-40 NC-40 High NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 Octave band center frequency, Hz Octave band center frequency, Hz 1,000 2,000 4,000...
Page 355
MODEL : ASUA7TLAV MODEL : ASUA9TLAV N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 N C -50 N C -50 N C -45 N C -45 N C -40 N C -40 H igh H igh...
Page 356
MODEL : ASUB18TLAV MODEL : ASUB24TLAV NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 High NC-45 NC-45 NC-40 NC-40 High NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
SOUND LEVEL CHECK POINT z All cassette type z All duct type 78-3/4in. 39-3/8in. (1m) (2m) z Floor / Ceiling type z Compact floor type z Ceiling type Microphone ● Airflow 39-3/8in. (1m) 39-3/8 in. (1 m) Airflow 39-3/8 in.
9. SAFETY DEVICES Fan motor thermal Terminal Float Model and type Fuse protector thermal fuse switch AUUA4TLAV1 Activate at AUUA7TLAV 280.4±27°F (138±15°C): AUUA9TLAV 250V Fan motor stop ○ Compact cassette AUUA12TLAV ― Reset at 3.15A AUUA14TLAV 221±36°F (105±20°C): AUUA18TLAV Fan motor restart AUUA24TLAV AUUB18TLAV1 Activate at...
Page 359
Fan motor thermal Terminal Float Model and type Fuse protector thermal fuse switch Activate at ARUH36TLAV 250V 3.15A 293 ± 9°F ARUH48TLAV ― ― (145 ± 5°C): 250V 10A * ARUH60TLAV Fan motor stop Activate at High static pressure °F ARUH72TLAV1 (100 °C):...
Page 360
Fan motor thermal Terminal Float Model and type Fuse protector thermal fuse switch ASUA4TLAV1 Activate at 221±18°F ASUA7TLAV1 (105±10°C): Fan motor stop ASUA9TLAV1 ― ― Reset at 194±18°F ASUA12TLAV1 (90±10°C): Fan motor restart ASUA14TLAV1 Activate at 302±27°F ASUB18TLAV1 (150±15°C): 250V Activate at Fan motor stop 215.6°F...
Page 361
5. CONTROL SYSTEM DTV_VR2U025E_14--CHAPTER05 2018.03.16...
Page 362
CONTENTS 5. CONTROL SYSTEM CONTROL SYSTEM ..............05 - 01 1-1. LINE UP OF CONTROLLERS ..............05 - 01 1-2. CONTROL SYSTEM DESIGN ..............05 - 03 1-3. SYSTEM CONFIGURATION EXAMPLES ..........05 - 04 1-4. CONTROL SYSTEM FEATURES ............... 05 - 10 1-5.
1. CONTROL SYSTEM 1-1. LINE UP OF CONTROLLERS FEATURES OF CONTROL SYSTEM Reduced Installation Time Expandable System Configuration Various controls combinations meet most Simplified wiring, using a standard 22ga L applications and allow for future expansion. communication cable, reduces installation cost.
Page 365
Air Conditioning Central Control Air Conditioning Individual Control System Controller, System Controller Lite, Touch Panel A range of Remote Controllers suitable for a wide range Controller and Central Remote Controller specially of individual control situations, using various built-in designed for centralized control. timers System Controller Wired Remote Controller (Touch panel)
1-2. CONTROL SYSTEM DESIGN ADVANCED INTEGRATED CONTROL SYSTEM Building Air Conditioning Air Conditioning System Management Central Control Individual Control General-purpose Building BACnet® Gateway Wired Remote Controller Control Controller USB *2 To Outdoor units Adaptor Connectable to various sized (Locally BMS/BAS *1 purchased)
1-3. SYSTEM CONFIGURATION EXAMPLES INDIVIDUAL CONTROL Wired Remote Controller (Touch panel) Single control Multiple control for ● Up to 16 indoor units can be controlled with one wired for private room meeting room etc. remote controller. ● Wired (Touch panel) and wireless remote controllers can be used jointly.
Page 368
External Switch Controller Single control for hotel room with switch ● Up to 16 indoor units can be controlled with one external switch controller. Ext.SW ● In combination with a locally purchased card-key Controller switch or other sensor, External switch controller Ext.SW Ext.SW allows control of basic functions by the hotel or office...
Page 369
CENTRAL CONTROL Central Remote Controller ● Up to 100 indoor units / 16 groups can be controlled with one central remote controller. ● The sum total of the Touch panel controller, Central remote controller, Modbus® convertor, and Network convertor for LONWORKS®...
Page 370
System Controller Lite ● UP to 400 indoor units / 400 groups can be controlled with one System Controller Lite. Administrator's room System USB Adaptor Controller Lite Commercial building (Medium class) To outdoor units Office floor Up to 100 outdoor units Office floor Tenant floor Tenant floor...
Page 371
System Controller can perform as an on-site central control or as a remote central control. On site central control ( Max. 4 VRF network systems) Server & Client USB Adaptor USB Port System Controller 1 VRF Max. controllable Max. transmission line length network 11,811 system...
-Multiple Touch Panel Controllers may be sued to provide convenient control for multiple convertor (Refer to 3-1.) - Can control Fujitsu mini-split and HFI models using a Network Convertor (Refer to 3-1.) ● System Controller allows to control up to 4 VRF network systems (Max.1,600 indoor units), ...
1-5. WIRING SYSTEM ● Wiring configulation of the control system is made of power source wiring, transmission wiring and remote controller wiring. ● Total wiring length (total length of transmission line) can be extended up to 11,811 ft. (3,600 m) (by using signal amplifiers). Max.
1-6. CONTROL EQUIPMENT DESIGN LIMITATION Connectable Manageable Connectable Necessary Model number per indoor unit outdoor unit equipment system number number UTY-APGXZ1 1,600 System Controller USB Adaptor 1 / system UTY-APGX (4 VRF Networks) (4 VRF Networks) UTY-ALGXZ1 System Controller Lite USB Adaptor 1 / system UTY-ALGX...
2. CONTROL UNITS The following types of controllers are available with the FUJITSU GENERAL LIMITED VRF System : z System Controller z System Controller Lite z Touch Panel Controller z Central Remote Controller z Wired Remote Controller ...
2-1. SYSTEM CONTROLLER 2-1-1. MODEL: UTY-APGXZ1 (Option: UTY-PEGXZ1, UTY-PPGXP2) This system realizes the advanced general monitoring & control of VRF system from small scale buildings to large scale buildings. ● Maximum of 4 network systems, 1600 indoor units can be controlled. ●...
Page 378
SYSTEM DIAGRAM ● System controller may be used on site or remotely over various networks for remote central control. ● System controller consists of VRF Controller software and VRF Explorer software, both software are working together. ● VRF Controller software runs in the background and communicate with VRF System. ●...
Page 379
SOFTWARE CONFIGURATION VRF Controller VRF Explorer White USB Key UTY-APGXZ1 White USB Key unnecessary White USB Key UTY-PEGXZ1, UTY-PPGXP2 Local Site Remote Site Option (VRF network system side) (Monitoring center side) Any number can be installed in remote site personal computers System Controller UTY-APGXZ1 can be installed in the local site PCs (VRF Controller) con- nected to the VRF network system, and multiple remote site PCs (VRF Explorer) can be con- nected to VRF Controller via Internet or LAN.
Page 380
SPECIFICATION SUMMARY UTY- UTY- UTY- PEGXZ1 PPGXP2 Type Function Remark APGXZ1 Option Option Max. System Controller per VRF Network Site with up to 4 VRF networks may be Max. VRF networks supported administered with 1 System Controller System Max.
Page 381
UTY- UTY- UTY- PEGXZ1 PPGXP2 Type Function Remark APGXZ1 Option Option External device control function WEB Operation User control Authorization level setting. Database import / export (manual) Periodical backup The refrigerant systems of non-operation Others status function Auto Start Setting English, Chinese, French, German, Spanish, Multiple language display Russian, Polish.
2-1-2. MODEL: UTY-APGX (Option: UTY-PEGX) This advanced system has the capability for monitoring and control of small and large buildings. ● Up to a maximum of 4 network systems, 1,600 indoor units can be controlled. ● Provides energy saving functions along with precision temperature control, central remote control, electricity charge calculation and schedule management.
Page 383
SYSTEM DIAGRAM ● System controller may be used on site or remotely over various networks for remote central control. ● System controller consists of VRF Controller software and VRF Explorer software running simultaneously. ● VRF Controller software runs in the background and communicate with VRF System. ●...
Page 384
SOFTWARE CONFIGURATION VRF Controller VRF Explorer WIBU-Key UTY-APGX WIBU-Key unnecessary WIBU-Key UTY-PEGX Local Site Remote Site Option (VRF network system side) (Monitoring center side) Any number can be installed in remote site personal computers. System Controller UTY-APGX can be installed in the local site PCs (VRF Controller) connected to the VRF net- work system and the multiple remote site PCs (VRF Explorer) connected to those computers via the Internet or LAN.
Page 385
SPECIFICATION SUMMARY UTY-PEGX Type Function UTY-APGX Remark *1 Option Max. System Controller per VRF Network Site with up to 4 VRF networks may be Max. VRF networks supported administered with 1 System Controller System specification Max. indoor units / remote controller groups per VRF network Max.
2-2. SYSTEM CONTROLLER LITE 2-2-1. MODEL: UTY-ALGXZ1 (Option: UTY-PLGXA2, UTY-PLGXR2, UTY-PLGXE2, UTY-PLGXP2, UTY-PLGXX2) System Controller Lite is advanced software of central controller for small and medium buildings. It can be supported by additional options, electricity charge apportionment, remote monitoring, and energy saving in order to meet your demands. ●...
Page 387
SYSTEM DIAGRAM ● System controller may be used on site or remotely over various networks for remote central control. * ● System controller consists of VRF Controller software and VRF Explorer software, both software are working together. ● VRF Controller software runs in the background and communicate with VRF System. ●...
Page 388
PACKING LIST Name and shape Quantity Application Software protection key to be connected to an USB port on the PC that the System Controller is installed. System Controller WHITE-USB-KEY runs only on a PC with this . However, this WHITE-USB-KEY WibuKey is not required for remote VRF Explorer software.
Page 389
PERSONAL COMPUTER SYSTEM REQUIREMENTS ® ® • Microsoft Windows 7 Home Premium (32-bit or 64-bit) SP1 ® ® • Microsoft Windows 7 Professional (32-bit or 64-bit) SP1 ® ® • Microsoft Windows 8.1 (32-bit or 64-bit) • Microsoft ®...
Page 390
SPECIFICATION SUMMARY UTY- UTY- UTY- UTY- UTY- UTY- PLGXA2 PLGXR2 PLGXE2 PLGXP2 PLGXX2 Type Function Remark ALGXZ1 Option Option Option Option Option Max. System Controller Lite per VRF Network Max. VRF networks supported System specification Max. indoor units / remote controller groups per VRF network Max.
Page 391
UTY- UTY- UTY- UTY- UTY- UTY- PLGXA2 PLGXR2 PLGXE2 PLGXP2 PLGXX2 Type Function Remark ALGXZ1 Option Option Option Option Option External device control function WEB Operation User control Authorization level setting. Database import / export Periodical backup The refrigerant systems of non- Others operation status function Auto Start Setting...
Page 392
2-2-2. MODEL: UTY-ALGX (Option: UTY-PLGXA1, UTY-PLGXR1, UTY-PLGXE1) System Controller Lite is advanced software of central controller for small and medium buildings. It can be supported by additional options, electricity charge apportionment, remote monitoring, and energy saving in order to meet your demands. ●...
Page 393
SYSTEM DIAGRAM ● System controller may be used on site or remotely over various networks for remote central control. * ● System controller consists of VRF Controller software and VRF Explorer software, both software are working together. ● VRF Controller software runs in the background and communicate with VRF System. ●...
Page 394
PACKING LIST Name and shape Quantity Application DVD-ROM * Includes the software and manuals for System Controller Lite. Both VRF Controller and VRF Explorer software are included. Wibu Key Software protection key to be inserted in a USB slot running System Controller.
Page 395
PERSONAL COMPUTER SYSTEM REQUIREMENTS • Microsoft ® Windows ® 7 Home Premium (32-bit or 64-bit) SP1 ® ® • Microsoft Windows 7 Professional (32-bit or 64-bit) SP1 • Microsoft ® Windows ® 8.1 (32-bit or 64-bit) ® ® •...
Page 396
SPECIFICATION SUMMARY UTY- UTY- UTY- UTY- PLGXA1 PLGXR1 PLGXE1 Type Function Remark ALGX Option Option Option Max. System Controller Lite per VRF Network Max. VRF networks supported Max. indoor units / remote controller groups per System specification VRF network Max.
2-3. TOUCH PANEL CONTROLLER MODEL: UTY-DTGYZ1 (Option: UTY-PTGXA) MODEL: UTY-DTGY ● Large 7.5-inch TFT color display ● LCD touch panel operation ● Stylish shape and design to suit all application ● No additional component is required for installation ●...
Page 398
FUNCTIONS z MODEL: UTY-DTGYZ1 Item Description Main unit PC / Tablet Indoor unit registration. Max. 400 units. Indoor unit registration (Set data can be written to and read from USB flash drive) Installation Temperature set point limitation, external input, central Functions setting operation on/off setting.
Page 399
Item Description Main unit PC / Tablet Input: Batch operation/stop, emergency stop, electricity meter Others External input/output Output: Operation monitoring, error ● When Start/Stop, operation mode setting, room temp. setting, fan speed setting, airflow direction setting, swing setting, economy mode, and anti freeze setting are changed frequently by using the central controller like System Controller, Touch Panel Controller, etc.
Page 400
z MODEL: UTY-DTGY Item Description Language setting Design considering multi-language correspondence. * Indoor unit registration. Max. 400 units. Indoor unit registration Installation (Set data can be written to and read from USB flash drive) Temperature set point limitation, external input, central operation Functions setting on/off setting.
Page 401
STATE TRANSITION DIAGRAM Power ON Finish Indoor unit registration Installer setting ● Language setting ● Time zone setting *1 ● Date and time setting ● Touch panel address setting ● Indoor unit registration ● Function settings of Touch Panel Controller Monitor &...
Page 402
MAIN FUNCTIONS AND SCREEN EXAMPLES z Monitor display example An easy-to-use display mode can be selected. Easy-to-understand GUI of adopted icon. Icon display List display example z Operation setting example Large button is designed for easy to access. Operation setting display Optional setting display - (05 - 39) -...
Page 403
z Group setting Groups can be arbitrarily set in easy to manage units as shown in the figure. Control and monitoring are performed in these group units. Group: Hallway Group: 3F Group: Group: Division A Group: Division B Division C Touch Panel Group: 2F Controller...
Page 404
z System schedule timer Annual schedule can be set of a maximum 30 items. Schedule setting screen z History recording and display Error, status and operation histories can be recorded. Each recording can be also written to USB memory. ●...
Page 405
SCREEN EXAMPLES (For Remote monitoring) z Main screens of Monitor Mode example Icon display List display z Main screens of Control example Operation setting display - (05 - 42) -...
Page 406
INSTALLATION z Installation space When installing multiple Touch Panel Controllers, the following clearances must be maintained. 4 in. (100 mm) or more 8 in. 8 in. 8 in. (200 mm) (200 mm) (200 mm) or more or more or more Wall 4 in.
Page 407
z Terminal names Names of connection terminals inside rear cover. Power supply cable Transmission cable through hole connection terminals Transmission cable Power supply cable through hole connection terminals EXTERNAL INPUT POWER SUPPLY TRANSMISSION X1 X2 K1 K2 K1 K2 External input Power supply ®...
Page 408
z Installation method Refer to an installation manual for the details. Transmission Transmission Power supply cable power supply cable cable cable Switch box Switch box Hole in wall Hole in wall Installation plate Installation plate Power supply power supply cable cable Screw...
Page 409
DIMENSIONS Unit : in.(mm) Top view Touch pen 9-11/16 (246) 2-1/8 (54) Touch panel USB port Front view Side view Side view 7-13/16 (198) 2-5/8 (66) 2-ø11/16 (17) Installation plate Rear view PACKING LIST Name and shape Quantity Application For Touch Panel Controller installation...
Page 410
WIRING SPECIFICATIONS Size Wire type Remarks 16 AWG 1 ø AC100 - 240 V 50/60 Hz, Maximum (1.25 mm Power supply cable 245 IEC 57 or equivalent 2 Wire + ground 20 AWG (Always ground the unit) Minimum (0.5 mm LEVEL4 (NEMA) non-polar 2 22AWG...
Page 411
PERSONAL COMPUTER SYSTEM REQUIREMENTS When using for touch panel controller, the following personal computer system requirement is necessary. 2 GHz or higher Memory 2 GB or more 10 GB or more of free space Display 1,366 × 768 or higher resolution •...
2-4. CENTRAL REMOTE CONTROLLER MODEL: UTY-DCGY ● Individual control and monitor of 100 indoor units. ● 5 inch TFT color screen. ● User friendly view and easy operation. ● External input / output contact. ● Detachable power supply unit. ●...
Page 413
MAIN FUNCTIONS AND SCREEN EXAMPLES z Individual control zRemote controller prohibition (On / Off, Mode, Set Temp, Fan Speed, (All, On / Off, Mode, Temp, Timer, Filter): Airflow Direction, Anti Freeze, Economy) R.C prohibition setting prohibits individual remote control operation from this controller z Room temperature set point ...
Page 414
z Automatic clock adjustment The time setting can be adjusted for all indoor units in one batch function. z Error history ● Last 200 errors are stored in memory. ● Error history can be analyzed to determine proper maintenance schedule. z Main screen display auto switching ...
Page 415
INSTALLATION z Installation space When installing controller, provide a service space as shown. Service space z Terminal names ● Power supply unit Power supply terminal POWER SUPPLY Screw size: M4 Earth (Ground) Power supply cable Reley connector output: DC 5 V Power supply 1ø...
Page 416
z Installation method Setting pattern 1: Integrated type Setting pattern 2: Separate type Ceiling Power supply unit Power supply unit Wall Extension cable Control panel (Service parts) Wall Control panel ● Integrated type Refer to an installation manual for the details. Transmission cable Power supply cable One touch bush...
Page 417
● Separate type Screw × 2 (Accessories) Screw × 2 Screw × 4 Screw × 2 (Accessories) Ceiling Screw × 2 Power unit cover One touch bush × 2 Holder Cutting out Wall (When wiring a transmission cable up Extension cable Cable Tie ×...
Page 418
DIMENSIONS Unit : in. (mm) z Control unit z Power supply unit 1 (25.7) 1-1/8 (29) 3-7/8 (99) Top view 1-13/16 (46) 1-13/16 (46) 6-3/8 (162) Front view Side view 4-5/8 (118) 3/16 (5) 2-Ø3/16 (5) 5-5/16 (135) 1-9/16 (39.2) Front view...
Page 419
WIRING SPECIFICATIONS Size Wire type Remarks 16 AWG 1 ø AC100 - 240 V 50/60 Hz, Maximum (1.25 mm Power supply cable 245 IEC 57 or equivalent 2 Wire + ground 20 AWG (Always ground the unit) Minimum (0.5 mm LEVEL4 (NEMA) non-polar 2 22AWG...
2-5. WIRED REMOTE CONTROLLER (Touch panel) MODEL: UTY-RNRUZ, UTY-RNRU ● Easy finger touch operation with LCD panel ● Built-in weekly/Daily timer(ON/OFF,Temp.,Mode) Office Fri 10:00AM ● Backlight enables easy operation in a darkened room Mode Set Temp. Cool 80°F Custom Auto ●...
Page 421
FUNCTIONS 1 Room temperature sensor (inside) 2 On/Off button: It is possible to operate only while displaying the Monitor Mode screen. Office Fri 10:00AM Mode Set Temp. 3 LED lamp (Operation indicator) 80°F Cool Custom Auto 4 Touch panel display Auto 74°F Heat...
Page 422
SYSTEM DIAGRAM z Multiple remote control Up to 4 remote controllers can be used to operate the indoor units. I.U. I.U. I.U. I.U. Master Master Slave Master Slave Slave Master Slave Slave Slave A, B, C, D : Remote controller cable. (Refer to Chapter6. 4-4 for detail specifications) A≤1,640 ft.
Page 423
ELECTRICAL WIRING z Single control z Multiple remote control Indoor unit Y2 Y3 Indoor unit When there is afunctional earthing When there is afunctional earthing (Accordance with the regional (Accordance with the regional cable standard.) cable standard.) Remote Remote Remote controller...
Page 424
z Connection Pattern NOTE: Connection pattern is different according to type of Indoor unit. Indoor unit types Connection Pattern All Cassette type All Duct type Pattern A All Ceiling type Wall Mounted type Pattern B z Pattern A Connect the end of remote controller cable directly to the exclusive terminal block.
Page 426
SPECIFICATIONS UTY-RNRYZ , UTY-RNRU Model name DC 12 Input voltage Max. 0.3 Input power 3.8 inch FSTN LCD (255 × 160 dots) with Touch panel Display 32 to 104 (0 to 40) Usage temperature range: °F (°C) 20 to 90 (no condensation) Usage humidity range 14 to 140 (-10 to 60)
2-6. WIRED REMOTE CONTROLLER MODEL: UTY-RNKU ● Various timer setup options (ON / OFF / WEEKLY) are possible. ● Weekly timer as standard function. (Start / Stop function twice per day for a week) ● When setting up a timer, start/stop and a temperature setup can be changed.
Page 428
FUNCTIONS START/STOP button Pressed to start and stop operation. Set Temperature button Display Selects the setting temperature. Operation mode button 2 Selects the operating mode (AUTO 1, COOL , DRY , 3, HEAT 4). Fan control button Selects the fan speed (AUTO , LOW , MED...
Page 429
SYSTEM DIAGRAM z 1 remote controller z 2 remote controllers Indoor unit Indoor unit A , B , C : Remote controller cable. Refer to chapter 6. 4-4 for detail specifications. Master Slave A ≤ 1,640 ft. (500 m) ; B+C≤ 1,640 ft. (500 m) Remote controller Remote controllers ...
Page 430
INSTALLATION z Connection Pattern NOTE: Connection pattern is different according to type of Indoor unit. Indoor unit types Connection Pattern All Cassette type All Duct type Pattern A All Ceiling type Wall Mounted type Pattern B z Pattern A ...
Page 431
PACKING LIST Name and shape Quantity Application Screw For installing the remote controller (M4 × 16 mm) For securing controller cable Cable Tie Installation manual Operating manual WIRING SPECIFICATIONS Cable size Wire type Remarks 22AWG Remote controller cable Polar 3 core Use sheathed PVC cable.
2-7. SIMPLE REMOTE CONTROLLER (With Operation mode) 2-7-1. MODEL: UTY-RSRY ● Easy operation. ● Stylish design ● Large LCD screen & simple operation buttons ● Built-in background light function. ● Easy installation with a slim shape with no bulge in the back. ●...
Page 433
FUNCTIONS START/STOP button Pressed to start and stop operation. LED lamp Lights during operation. Operation mode button Selects the operating mode Set temperature button Selects the setting temperature.(18-30°C[COOL], 10-30°C[HEAT]) Fan control button Selects the fan speed Louver button Set the airflow direction.
Page 434
SYSTEM DIAGRAM z 1 remote controller z 4 remote controllers Indoor unit Indoor unit Master Slave Slave Slave Remote controller Remote controllers A , B , C , D , E : Remote controller cable. Refer to 6-4-4 for detail specifications. <...
Page 435
INSTALLATION z Connection Pattern NOTE: Connection pattern is different according to type of Indoor unit. Indoor unit types Connection Pattern All Cassette type All Duct type Pattern A All Ceiling type All Compact Floor type Wall Mounted type Pattern B z Pattern A ...
Page 436
PACKING LIST Name and shape Quantity Application Wired remote controller Installation manual Operating manual CD-ROM For installing the remote controller Screw (M4 × 16 mm) For binding remote controller and Cable tie remote controller cable WIRING SPECIFICATIONS ...
2-7-2. MODEL: UTY-RSKU ● Easy operation. ● Built-in background light function. ● Easy installation with a slim shape with no bulge in the back. ● Error history. (Last 16 error codes can be accessed.) ● Up to 16 indoor units can be simultaneously controlled. ●...
Page 438
SYSTEM DIAGRAM z 1 remote controller z 2 remote controllers Indoor unit Indoor unit Master Slave Remote controller Remote controllers A , B , C : Remote controller cable. Refer to chapter 6. 4-4 for detail specifications. A ≤...
Page 439
INSTALLATION z Connection Pattern NOTE: Connection pattern is different according to type of Indoor unit. Indoor unit types Connection Pattern All Cassette type All Duct type Pattern A All Ceiling type Wall Mounted type Pattern B z Pattern A ...
Page 440
PACKING LIST Name and shape Quantity Application For connecting the remote controller Remote controller cable [33 ft. (10 m)] Screw For installing the remote controller (M4 × 16 mm) For securing controller cable Cable Tie Installation manual Operating manual ...
2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode) 2-8-1. MODEL: UTY-RHRY ● Easy operation. ● Stylish design ● Large LCD screen & simple operation buttons ● Built-in background light function. ● Easy installation with a slim shape with no bulge in the back. ●...
Page 442
FUNCTIONS START/STOP button Pressed to start and stop operation. LED lamp Lights during operation. Set temperature button Selects the setting temperature.(18-30°C[COOL], 10-30°C[HEAT]) Fan control button Selects the fan speed Louver button Set the airflow direction. Room temperature sensor(inside) Operating mode indicator (AUTO * 1, COOL...
Page 443
SYSTEM DIAGRAM z 1 remote controller z 4 remote controllers Indoor unit Indoor unit Master Slave Slave Slave Remote controller Remote controllers A , B , C , D , E : Remote controller cable. Refer to 6-4-4 for detail specifications. <...
Page 444
INSTALLATION z Connection Pattern NOTE: Connection pattern is different according to type of Indoor unit. Indoor unit types Connection Pattern All Cassette type All Duct type Pattern A All Ceiling type All Compact Floor type Wall Mounted type Pattern B z Pattern A ...
Page 445
PACKING LIST Name and shape Quantity Application Wired remote controller Installation manual Operating manual CD-ROM For installing the remote controller Screw (M4 × 16 mm) For binding remote controller and Cable tie remote controller cable WIRING SPECIFICATIONS ...
2-8-2. MODEL: UTY-RHKU This controller cannot select mode. An additional controller is required for the user to select heating or cooling mode. ● Easy operation. ● Built-in Backgroud Light function. ● Easy installation with a slim shape with no bulge in the back. ●...
Page 447
SYSTEM DIAGRAM z 1 remote controllers z 2 remote controllers Indoor unit Indoor unit Master Slave Remote controller Remote controllers A , B , C : Remote controller cable. Refer to chapter 6. 4-4 for detail specifications. A ≤...
Page 448
INSTALLATION z Connection Pattern NOTE: Connection pattern is different according to type of Indoor unit. Indoor unit types Connection Pattern All Cassette type All Duct type Pattern A All Ceiling type Wall Mounted type Pattern B z Pattern A ...
Page 449
PACKING LIST Name and shape Quantity Application For connecting the remote controller Remote controller cable [33 ft. (10 m)] Screw For installing the remote controller (M4 × 16 mm) For securing controller cable Cable Tie Installation manual Operating manual ...
2-9. WIRELESS REMOTE CONTROLLER MODEL: UTY-LNHU ● Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible. ● Up to 16 indoor units connected within the remote controller group can be simultaneously controlled. ● Can be used jointly with wired remote controllers . ●...
Page 451
FUNCTIONS OPERATION MODE button Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT ). /Start / end R.C. custom code change. (Max 4 types) Economy button Set temp. button ( ▲ / ▼ ) Set remote controller custom code buttons Sets the indoor temp./ Sets R.C.
Page 452
SYSTEM DIAGRAM Signal receiver ● Control signal might not be recognized in following cases: window (i) A curtain or a wall, etc. exists between transmitter and receiver. Signal transmitter (ii) There is an instant-start type (inverter type, etc.) fluorescent lamp in the room.
Page 453
PACKING LIST Name and shape Quantity Application Installation manual Operating manual Use as remote controller holder Remote controller holder Screw For remote controller holder installation (M3 × 12 mm) Battery For remote controller [ 1.5V (R03 / AAA) ] ...
2-10. IR RECEIVER UNIT (for ALL DUCT TYPE) MODEL: UTB-YWC Duct type indoor unit can be controlled with wireless remote controller if the IR receiver unit is used. FUNCTIONS OPERATION LAMP TIMER LAMP FILTER SIGN MANUAL AUTO SIGNAL RECEIVER ...
Page 455
ELECTRICAL WIRING Indoor unit control box PC board Connected to PC board *2 Connection cable A 2-3/8 in. × 4-3/4 in. [L = 16 ft. (5 m)]... Standard accessory (60 mm × 120 mm) Connection cable C hole [L = 33 ft.
Page 456
PACKING LIST Name and shape Quantity Application Installation manual Cover For receiver unit Insulation For receiver unit Small:1 Cable Tie For receiver unit Medium:1 Screw For installing receiver unit to wall, etc. (M4 × 20 mm) Screw For attaching the hook metal to the holder cover (M4 ×...
2-11. IR RECEIVER UNIT (for CASSETTE TYPE) MODEL: UTY-LRHYB1 Cassette type indoor unit can be controlled with wireless remote controller if the IR receiver unit is used. FUNCTIONS Filter lamp (Red) Timer lamp (Orange) Operation lamp (Green) Manual auto Signal receiver ...
Page 458
DIMENSIONS Unit : in. (mm) 7-5/8 (193.9) 1-1/4 (31.2) Front View Side View PACKING LIST Name and shape Quantity Application Installation manual Strap Prevent receiver kit from falling down SPECIFICATIONS Model name UTY-LRHYB1 × ×...
2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE) MODELS: UTY-LBHXD Cassette type indoor unit can be controlled with wireless remote controller if the IR receiver unit is used. FUNCTIONS Remote control signal receiver and Manual Auto button FILTER Indicator lamp (RED) OPERATION Indicator lamp (GREEN)
Page 460
DIMENSIONS Unit: in. (mm) 6-1/2 (22.6) (164.5) Front View Side View PACKING LIST Name and shape Quantity Application For receiving the signal from the remote IR receiver unit control unit Prevent IR receiver unit Strap from falling down Cable tie For electrical wiring ...
2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE) MODEL: UTY-SHZXC Motion sensor save operation catches the movements of people for wide area and operation stop is also judged automatically. ELECTRICAL WIRING Wire from Human sensor unit Strap Hook Strap...
Page 462
DIMENSIONS Unit: in. (mm) 6-1/2 1-1/16 (164.5) (27.5) Side View Front View PACKING LIST Name and shape Quantity Application Human sensor unit For detection of movement Cable tie For binding wires Strap To prevent Human sensor unit from falling Insulation To fasten the Human sensor wire ...
2-14. REMOTE SENSOR UNIT MODEL: UTD-XSZX The remote sensor unit allows for flexible temperature sensing for optimum temperature control. ELECTRICAL WIRING ● Remove the screws from the remote sensor, and remove the cover. ● Connect the cable to the remote sensor as shown below. ●...
Page 464
z When the cable is buried in the wall ● Remove the material (thinner than the surrounding material) in the wiring hole in the remote sensor using a pair of cutters. ● Drill a hole in the wall for the cable. ●...
2-15. PRESSURE SENSOR KIT MODEL: UTY-SPWX ● Only for V-II series system ● It is used when the outdoor unit is installed higher than the indoor unit and the height difference exceeds 164ft (50m). ● Attach the sensor part to the liquid pipe near the indoor unit. ●...
Page 466
SPECIFICATIONS z Control unit Power supply (V) DC 12 Current (A) 0.10 Power consumption (W) Operating 32 to 114 (0–46) Temperature [°F (°C)] Packaged 14 to 140 (-10–60) Humidity (%) Packaged 0–95 (RH) No condensation 1-11/16 × 4-5/8 × 5-1/2 Dimensions [H ×...
Page 467
DIMENSIONS Unit: in (mm) 3-Ø3/16 (4.5) 1-11/16 (43) For M4x16 mm 4-5/8 (117) screws 2-Ø3/8 (10) For code (> Ø1/4 (7)) Hole: 2-Ø1/4 (7) For code ( Ø1/4 (7)) 2-Ø5/16 (8) For code (> Ø3/165) Hole: 2-Ø3/165 For code ( Ø3/165) Hole: 1/16 x 5/16 (2 x 8) 3-7/8 (98) For open case...
Page 468
WIRING SPECIFICATIONS Size Cable type Remarks Power cable (using 16 to 22 AWG Non-polar 2 core, twisted Maximum cable length: remote control (0.33 to 1.25 mm²) pair sheathed PVC cable 32ft (10m) cable) 22AWG LEVEL 4 (NEMA) ®...
Page 469
WIRING DIAGRAM Only one pressure sensor kit is installed in each refrigerant system. Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 (Master unit) (Slave unit 1) (Slave unit 2) Transmission Control unit of sensor kit Refrigerant pressure sensor (accessories) Indoor unit Indoor unit...
Page 470
INSTALLING THE SENSOR z Installing the refrigerant pressure sensor Installing the sensor between the indoor unit and the separation tube (or outdoor unit). Sensor Separation tube Indoor unit Indoor unit Indoor units installed same floor 45° or 45°...
Page 471
INSTALLING THE CONTROLLER UNIT Remote controller Transmission Cable of refrigerant pressure cable sensor (accessories) cable Cable tie (accessories) Fix the cable with cable tie using 3 fixing holes. Fix the connection cable even outside this product as necessary. Cable tie (accessories) Holes for fixing cable tie (3 places) - (05 - 108) -...
Page 472
INSTALLATION z Connection Pattern NOTE: Connection pattern is different according to type of Indoor unit. Indoor unit types Connection Pattern All Cassette type All Duct type All Ceiling type Pattern A All Compact Floor type Compact Floor type Wall Mounted type Pattern B z Pattern A...
Page 473
DIP SWITCH SETTING z Controller unit Setting of DIP switch is unnecessary. z Outdoor unit (Master unit only) Change setting the DIP switch of the outdoor unit as shown below. Factory setting Outdoor unit PCB - (05 - 110) -...
Page 474
LED DISPLAY z Positions z Normal code Flashng Flashng During initialization sequence Normally operating z Error code ● ● ○ Communication error between outdoor units ● ● ○ Outdoor unit pressure sensor error ● : 0.5s ON / 0.5s OFF ○...
2-16. GROUP CONTROL METHOD REMOTE CONTROLLER GROUP Wired, Simple and Wireless Remote Controllers can be used simultaneously in the following combinations. Example of combination for "Remote controller group" Without Remote Controller ........Max 16 indoor units Connectable indoor unit : 1-16 Connectable remote controller : 0 - 2 z Notes...
Page 476
GROUP This function is used when operating a multiple number of remote controller group at a time from the System Controller or Touch Panel Controller or Central Remote Controller. z Example Refrigerant system 1 Heat Recovery system Refrigerant system 2 Heat pump...
For connection between VRF network system and a L open network for ORKS management of small to medium-sized BMS. • Thermostat Convertor (UTY-TTRX) For control Fujitsu General products using a third-party thermostat controller. ® • BACnet Gateway (UTY-VBGX : Hardware) ®...
Page 480
3-1. NETWORK CONVERTOR MODEL: UTY-VTGX ● With this network convertor, single split type and multi system air conditioners can be controlled by Central remote controller, Touch panel controller, System controller in VRF network system or by wired remote controller that is connected to the Network convertor. ●...
Page 481
APPLICABLE MODELS z Connectable remote controllers 3 types of wired remote controller shown in the table below can be connected to this unit. The indoor unit that can be connected is the indoor unit that can connect to following remote controller.
Page 482
ELECTRICAL WIRING z For non-polar 2 wire Wired Transmission remote Cable controller Indoor unit Office Fri 10:00AM Mode Set Temp. Fa n Custom Cool 80° F Auto Auto Heat 74° F Cool 84° F Room Temp. Away 76°...
Page 483
LIMITED WIRING LENGTH z For non-polar 2 wire Indoor unit Network convertor A, B, C, D, E : Remote controller cable. (Refer to Chapter6. 4-4 for detail specifications.) A ≤ 6 ft. (2 m) and A+B+C+D+E ≤ 1,640 ft. (500 m). z For polar 3 wire ...
Page 484
DIMENSIONS Unit : in. (mm) 3-Ø3/16 (4.5) 1-11/16 (43) For M4x16 mm 4-5/8 (117) screws 2-Ø3/8 (10) For code (> Ø1/4 (7)) Hole: 2-Ø1/4 (7) For code ( Ø1/4 (7)) 2-Ø5/16 (8) For code (> Ø3/165) Hole: 2-Ø3/165 For code ( Ø3/165) Hole: 1/16 x 5/16 (2 x 8) 3-7/8 (98)
Page 485
3-2. NETWORK CONVERTOR MODEL: UTY-VGGXZ1 For connecting single split type system [ A change of DIP switch setting is necessary] ● With this network convertor, single split type, multi system and HFI system air conditioners can be controlled by Touch panel controller, System controller in VRF network system or by wired remote controller that is connected to the Network convertor.
Page 486
ELECTRICAL WIRING Transmission Line to VRF System Transmission Line to VRF System Wired Remote Controller FUSE (3 A) 1Ø 50/60 Hz 208-240 V SWITCH (Disconnect switch) Indoor Unit Y1 Y2 Y3 K1 K2 K3 TRANSMISSION REMOTE INDOOR UNIT POWER REMOTE CONTROLLER LINE Power Supply...
Page 487
APPLICABLE MODELS ○ ○ Single Split type Wired Remote Controller model × Wireless Remote Controller model z Connectable remote controllers 3 types of wired remote controller shown in the table below can be connected to this unit. Model name RC number Model name...
Page 488
DIMENSIONS Unit : in. (mm) Ø1-1/8 (28) Ø 1-1/8(28) For dust proof 3-1/2 3-1/2 For dust proof bushing (89.5) (89.5) bushing 2-Ø5 (3/16) For M4x20mm Ø7/8 (22.2) For conduit screws 9-1/2 (241.6) 10-11/16 (272) Hole pitch 2-5/8 11-5/16 (288) (67) 4 - Ø3/16 (5) For M4x20mm screws ...
Page 489
® 3-3. MODBUS CONVERTOR FOR VRF MODEL: UTY-VMGX ● The convertor for connecting VRF network system to the BMS system built ® by Modbus open network, for manage small to medium sized BMS and VRF network system. SYSTEM DIAGRAM ...
Page 490
FUNCTIONS z Indoor unit control ● Individual control Commands from Modbus ® Network are sent to the respective indoor units. (Modbus ® Network → respective indoor units of VRF Network) ● Batch control ® Commands from Modbus Network are sent to all indoor units connected to VRF Network.
Page 491
CONTROL AND MONITORING ITEMS NOTE: For detailed information, check the Interface Specification. Item Function Description ON/OFF Command Start / Stop operation Operation Mode Setting Cooling / Heating / Auto / Fan / Dry Temperature Setting Set room temperature Airflow Mode Setting Set airflow Set Point Temperature Limit Setting...
Page 492
Item Function Description Maintenance Mode Status Maintenance status Emergency STOP Setting Status Emergency STOP setting status Indoor Unit Monitoring ON / OFF Status The indoor unit which is now operating can be (Batch) monitored in all indoor units Error Status The indoor unit which is now error can be monitored in all indoor units Outdoor Unit Low Noise...
Page 493
To protect the compressor of the outdoor unit, carefully read and understand the following cautions that may affect the operation of the compressor before executing the setting. When performing periodical settings like schedule settings for the following functions, perform the setting to all the ...
Page 494
PACKING LIST Name and shape Quantity Application Installation manual Use during installation. For mounting the power supply cable and Cable tie transmission cable. Screw For mounting the network convertor. (M4 × 16 mm) For initial setting. For connecting the cable and attaching the ®...
Page 495
DIMENSIONS Unit : in.(mm) 3/8(10) 3/16 x 13/16=3-1/8 (4 x 20=80) 2-11/16(69) Hole pitch Ø7/8(22) For conduit 5-Ø1/2(13) For dust proof 2-Ø3/16(5) bushing For M4 x 16 mm screws 8-7/8(225) 2-1/8(54) 9-1/2(241) Hole pitch 10-1/4(260) 4-Ø3/16(5) For M4 x 16 mm screws ...
Page 496
WIRING SPECIFICATIONS Size Wire type Remarks 16AWG Maximum 1 ø AC208-240 V 50/60 Hz, (1.25 mm Power supply cable 60245 IEC 57 or equivalent 2-Wire + ground 20AWG (Always ground the unit) Minimum (0.5 mm LEVEL4 (NEMA) non-polar ®...
Page 497
® PROCEDURE IN BRIEF REGISTER DATA TO MODBUS CONVERTOR FOR VRF (UTY-VMGX) Address initial settings are 3 methods as follows. (1) Default addresses of indoor unit and outdoor unit are used. (Initial setting is not necessary) Default address value ([RefNo.—NodeNo.]) Indoor unit: [00―00] [00―01] •••...
® 3-4. NETWORK CONVERTOR FOR L ORKS MODEL: UTY-VLGX ● The convertor for connecting VRF network system to the BMS ® system built by L open network, for manage small to ORKS medium sized BMS and VRF network system. ●...
Page 499
z Improper system diagram ● Example 1 (Prohibited) Maximum 100 outdoor units Network Maximum 128 convertor for indoor units ® ORKS (UTY-VLGX) ® ORKS Network VRF network system 1 Maximum 100 outdoor units Network Maximum 128 convertor for indoor units ®...
Page 500
FUNCTIONS z Indoor unit control ● Individual control ® ® Commands from L Network are sent to the respective indoor units. (L ORKS ORKS Network → respective indoor units of VRF Network) ● Batch control ® Commands from L Network are sent to all indoor units connected to VRF Network.
Page 501
CONTROL AND MONITORING ITEMS NOTE: For detail information, check the Interface Specification. Item Function Description ON/OFF Command Start / Stop operation Operation Mode Setting Cooling / Heating / Auto / Fan / Dry Temperature Setting Set room temperature Airflow Mode Setting Set airflow Set Point Temperature Limit Setting...
Page 502
To protect the compressor of the outdoor unit, the following precautions must be followed prior to setting the system. When making changes to system settings, such as the schedule, it is necessary to change the settings of all indoor units on the same refrigerant circuit at the same time. <Corresponding function>...
Page 503
SPECIFICATIONS z Environmental specifications Power supply 1ø AC 208 - 240 V 50/60 Hz Input Power (W) Operating 32 to 114.8 (0 to 46) Temperature: °F (°C) Packaged 14 to 140 (-10 to 60) 0 to 95 (RH) ; Humidity (%) Packaged No condensation...
Page 504
PERSONAL COMPUTER SYSTEM REQUIREMENTS To install Tool for Network Convertor (UTY-VLGX), applicable PC needs to satisfy the following system requirements. ® ® • Microsoft Windows 7 Professional (32-bit) ® ® • Microsoft Windows 8.1 Pro (32-bit) ® ® •...
Page 505
DIMENSIONS Unit : in. (mm) Ø1-1/8 (28) Ø 1-1/8(28) For dust proof 3-1/2 3-1/2 For dust proof bushing (89.5) (89.5) bushing 2-Ø5 (3/16) For M4x20mm Ø7/8 (22.2) For conduit screws 9-1/2 (241.6) 10-11/16 (272) Hole pitch 2-5/8 11-5/16 (288) (67) 4 - Ø3/16 (5) For M4x20mm screws ...
Page 506
Indoor unit address Making XIF of Network Convertor using a Tool Binding VRF with BMS for network convertor (Software) provided by (By Network Integrator) Fujitsu General. (Job is done by Network Integrator) PCB FOR NETWORK CONVERTOR (UTY-VLGX) PC Control...
Page 507
SIMPLE PROCEDURE FOR CREATING XIF AND REGISTER DATA FOR NETWORK CONVERTOR (UTY-VLGX) NOTE: For detail information, check the Application Manual which is included inside packaged CD-ROM. The following is the on-line procedure. It is also possible to create XIF & Register Data off-line.
Page 508
Important: Network Convertor will not operate if, ● VRF network system address (Outdoor & Indoor units address) allocation information are not registered to Network Convertor. ● XIF data information and VRF network system address allocation information must not be same. ●...
3-5. THERMOSTAT CONVERTOR MODEL: UTY-TTRX ● Thermostat convertor can control Fujitsu General products using a third-party thermostat controller. ● Up to 16 indoor units can be connected with one thermostat convertor. SYSTEM DIAGRAM Multi split system...
Page 510
FUNCTIONS Function Remarks Operation mode setting Cooling, Heating, Fan Fan speed setting High, Med, Low, Auto Air conditioning Stage 1 (Cooling), Stage 1 (Heating) control function Temperature setting Stage 2 (Cooling), Stage 2 (Heating) Communication error detection Indoor unit error monitoring Maintenance Control target error indication function...
Page 511
ELECTRICAL WIRING Connection method differs by the type of thermostat controller. z Two-stage Cooling and Heating Example: Remote controller for 3-wire type Thermostat controller AC 24 V Indoor unit Max. 16 units Thermostat convertor AC 24 V Transformer* (Locally purchased) AC 208/230 V...
Page 512
z Single-stage Cooling and Heating with Dedicated Fan speed Relays Example: Remote controller for 2-wire type controller Thermostat Indoor unit AC 24 V Max. 16 units Thermostat convertor AC 24 V Transformer* (Locally purchased) AC 208/230 V Install the transformer, as necessary, per building code and manufacturer’s installation instructions.
Page 513
DIMENSIONS Unit : in (mm) 3-7/16 (86.7) Upper side 1-1/16 (27) 1/4 (7) 2-7/8 (72.7) Bottom side SPECIFICATIONS Max. connectable indoor unit number Input Power (W) Temperature: °F Operating 32 to 114 (0 to 46) (°C) Packaged 14 to 140 (-10 to 60) 0 to 95 (RH);...
Page 514
LED DISPLAY z Positions z Normal code LED1 LED2 LED3 LED4 Contents (Green) (Orange) (Red) (Blue) ● ● During initialization sequence Normally operating ● : 1 s ON / 1 s OFF z Error code LED1 LED2 LED3...
Page 515
® 3-6. BACnet GATEWAY (HARDWARE) MODEL: UTY-VBGX ● The convertor for connecting VRF network system to the BMS ® system using BACnet protocol. ® ● Maximum of 128 indoor units can be connected to one BACnet Gateway. ● VRF system can be centrally controlled or monitored from BMS via UTY-VBGX.
Page 516
FUNCTIONS z Indoor unit control ● Individual control ® ® Commands from BACnet Network are sent to the respective indoor units. (BACnet Network → respective indoor units of VRF Network) ● Batch control ® Commands from BACnet Network are sent to all indoor units connected to VRF Network.
Page 517
CONTROL AND MONITORING ITEMS WITH OBJECT TYPES NOTE: For detailed information, check the Instruction Manual. Category Bacnet Object Function Name Remark Target Monitor Control Type Operation Setting ○ Operation Mode ○ Temperature Setting ○ Fan Speed ○ R/C Prohibition ○...
Page 518
To protect the compressor of the outdoor unit, carefully read and understand the following cautions that may affect the operation of the compressor before executing the setting. When performing periodical settings like schedule settings for the following functions, perform the setting to all the ...
Page 519
PACKING LIST Name and shape Quantity Application Includes the software and manuals of Tool for USB memory ® BACnet Gateway. Connector cable For initial setting. Dust proof bushing For connecting the power supply cable. PERSONAL COMPUTER SYSTEM REQUIREMENTS ...
Page 520
DIMENSIONS Unit : in.(mm) 10-5/8(270.4) R2.5 8-7/8(225.4) 8-11/16(220) 15/16(23.3) 1(25.2) ELECTRICAL WIRING General purpose building control computer 1Φ 50/60 Hz 208-240 V (BMS) SWITCH TRANSMISSION CABLE FUSE (1.25 A) POWER SUPPLY CABLE BACnet Gateway ® INDOOR UNIT RJ45 B SGND TRANSMISSION CABLE...
Page 521
WIRING SPECIFICATIONS Size Wire type Remarks 16 AWG Maximum 1 ø AC208-240 V 50/60 Hz, (1.25 mm Power supply cable 60245 IEC 57 or equivalent 2-Wire + ground 20 AWG Minimum (Always ground the unit) (0.5 mm Ethernet category 5 or higher Transmission cable Straight cable STP LAN cable with RJ45...
Page 522
5. Execute the Configuration Tool from the PC and perform necessary settings. For detail,refer to the Instruction Manual, 6. Perform scan from the Configuration Tool, and check that all VRF indoor/outdoor units are detected and available. 7. Remove the USB cable from the Gateway, and close the case. ®...
Page 523
SWITCH AND CONNECTOR ETC. LOCATION ON PCB VRF Network connector (LonWorks ® AC power fuse BMS Network connector (Ethernet) Battery for clock LED_PWR LED_ERR PC connector (USB) NOTE: Ensure proper space for all connectors when mounted. CAUTION: Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the instructions.
® 3-7. BACnet GATEWAY (SOFTWAER) 3-7-1. MODEL: UTY-ABGXZ1 ® ● It is possible to connect medium to large sized BMS to VRF network system via BACnet global standard for open networks. ● A maximum of 1600 indoor units with 4 VRF network systems (a maximum of 400 indoor ®...
Page 525
® BACnet OBJECT LIST z Type : Indoor Unit Object Code Function Inactive Active name (II) Text-1 Text-2 Text-3 Text-4 Text-5 Text-6 Text-7 Set temp. status Degree Space temp. Degree Auto temp. (Low limit status) Degree Auto temp. (High limit status) Degree Cool/Dry temp.
Page 526
z Type : Outdoor Unit Object Code Function Inactive Active name (II) Text-1 Text-2 Text-3 Text-4 Text-5 Text-6 Text-7 Text-8 Outdoor unit error status Normal Fault Forced OFF status Reset Forced OFF setting Reset Outdoor unit priority Cool Heat Neutral None operation status *1...
Page 527
When performing periodical settings like schedule settings for the following functions, perform the setting to all the indoor units in the same refrigerant system simultaneously, conforming to the timing restriction described below. <Corresponding function> More than 10 minutes must elapse ·...
Page 528
INSTALLATION PROCEDURE Before installation, connect between the VRF Network System and the USB Adaptor. Brief installation steps are as follows: (For detail, check the Instruction Manual.) Step1: Install an appropriate driver for the USB Adaptor to the PC. *In this step, do not connect the USB Adaptor to the PC.
3-7-2. MODEL: UTY-ABGX ® ● It is possible to connect medium to large sized BMS to VRF network system via BACnet global standard for open networks. ● A maximum of 1,600 indoor units with 4 VRF network systems (a maximum of 400 indoor ®...
Page 530
® BACnet OBJECT LIST z Type : Indoor Unit Object Code (II) Function Inactive Active name Text-1 Text-2 Text-3 Text-4 Text-5 Text-6 Set temp. status °F Space temp. °F Auto temp. (Low limit status) °F Auto temp. (High limit status) °F Cool/Dry temp.
Page 531
z Type : Outdoor Unit Object Code Function Inactive Active name (II) Text-1 Text-2 Text-3 Text-4 Text-5 Text-6 Text-7 Text-8 Outdoor unit error status Normal Fault Forced OFF status Reset Forced OFF setting Reset Outdoor unit priority Cool Heat Neutral None operation status *...
Page 532
• When regularly making the following settings to the same outdoor unit by using schedule function etc., leave the following interval. <Corresponding function> More than 6 minutes must elapse ·Reset outdoor unit forced off mode · Set outdoor unit forced off mode More than 3 minutes must elapse ...
Page 533
PERSONAL COMPUTER SYSTEM REQUIREMENTS • Microsoft ® Windows ® 7 Home Premium (32-bit or 64-bit) SP1 ® ® • Microsoft Windows 7 Professional (32-bit or 64-bit) SP1 • Microsoft ® Windows ® 8.1 (32-bit or 64-bit) ® ® •...
Page 534
3-8. SIGNAL AMPLIFIER MODEL: UTY-VSGXZ1 If the total length of transmission line exceeds 1,640ft. (500m), or the number of units exceeds 64 units, A signal amplifier will be required. ● Transmission line length can be extended up to 11,811 ft. (3,600m) with multiple signal amplifier. ●...
Page 535
z Case of VR-II (321 or more indoor units are installed) Signal amplifier (Filter mode : OFF) 1Ø 50/60Hz FUSE 208-240 V (3 A) Terminal resistor Switch (Disconnect switch) Other RB unit RB unit or indoor unit Refrigerant system 1 Outdoor unit Network segment 1 Network segment 2...
Page 536
z Filter mode setting Set the Filter mode to suppress an increase of the amount of communication information in the VR-II system. ● Filter mode is turned on by inserting the accessory connecting wire at the CN4 connector on the PCB. ●...
Page 537
PACKING LIST The following installation parts are supplied. Use them as required. Name and shape Quantity Application Installation manual Cable Tie For securing controller cable. Screw For mounting the signal amplifier. (M4 × 20 mm) Terminal resistor For connecting the power supply cable. (Except in Dust proof bushing U.S.A.
3-9. EXTERNAL SWITCH CONTROLLER 3-9-1. MODEL: UTY-TERX ● Switching of air conditioner settings can be performed using an external switch controller and a third-party device. ● ON/OFF, Temperature, Fan Speed, Operating and Remote controller prohibition Mode can be switched using external devices, such as a room card-key.
Page 539
Connection to external contacts Select low current use contacts (usable at DC 5 V, 2 mA or less). Switch Switch Short circuit detection resistance (R ON): ≤ 500 (Ω). Open circuit detection resistance (R OFF): ≥ 100 (kΩ). External switch controller A twister pair cable 16 to 22AWG (0.33 to 1.25 mm²) should be use.
Page 540
Case 2: For polar 3 wire Modify the cable as per below methods. Use a tool to cut off the terminal on the end of the remote controller cable, and then remove the insulation from the cut end of the cable as shown in Fig. 1. Connect the remote controller cable and connecting cable as shown in Fig.
Page 541
PACKING LIST Name and shape Quantity Application Installation manual Screw For installing the external switch controller (M4 × 16 mm) Cable Tie For securing controller cable. WIRING SPECIFICATIONS Size Cable type Remarks Remote controller cable 16 to 22AWG Sheathed Non-polar 2 core, twisted pair (2-wire type)
Page 542
EXAMPLE Application Setting Wiring Operation example When controlling MODE0 P1 : ON, COOL, 80°F (26°C) P2 : OFF the individual P1: Arbitrary Indoor SW1 ON unit operation states operation state with two external Contact OFF→ON External contact P2: Arbitrary SW2 ON SW controller operation state...
Page 543
Application Setting Wiring Operation example When a MODE1 Indoor P1 : ON, COOL, 80°F (26°C) temperature sensor OFF output: unit P2 : ON,HEAT, 70°F (21°C) switch is connected Enabled and cooling and P1 : ON, COOL or heating switching is HEAT performed.
3-9-2. MODEL: UTY-TEKX ● Switching of air conditioner settings can be performed using an external switch controller and a third-party device. ● ON/OFF, Temperature, Fan Speed and Operating Mode can be switched using external devices, such as a room card-key. ●...
Page 545
DIMENSIONS Unit: in. (mm) 1-3/16 (30) 2-15/16 (75) 2-3/8 (60) 5 - ø1/4 (7) 11/16 (18) Left view Front view Rear view INSTALLATION z Connection Pattern NOTE: Connection pattern is different for different indoor unit types. Indoor unit types Connection Pattern All Cassette type...
Page 546
2) Connect the remote controller cable to the connecting cable, and insert it to the connector. Set the DIP switch (SW1) to "3WIRE" on the PCB of the indoor unit. Set to "3WIRE" the DIP switch (SW1) Connect to earth Functional earthing Indoor unit (ground) screw...
Page 547
EXAMPLE Application Setting Wiring Operation example When controlling MODE0 P1 : ON, COOL, 80°F (26°C) P2 : OFF the individual P1: Arbitrary Indoor SW1 ON operation states operation state unit with two external Contact OFF→ON contact P2: Arbitrary External SW2 ON SW controller...
4. SERVICE & WEB MONITORING TOOL 4-1. SERVICE TOOL 4-1-1. MODEL: UTY - ASGXZ1 Extensive monitoring and analysis functions for installation and maintenance. Operation status and error history can be grasped promptly and adequately. FUNCTIONS 1) System List Displays the overall operation status of all or specified units in the system in a list form.
Page 549
6) Error History Displays the error information for each unit. The error information can sequentially be displayed up to 50 items as they occur starting with the latest error. 7) Graph Displays the sensor values of outdoor unit and indoor units in more detail and more easier to see.
Page 550
15) Error Memory Reader When an error occurs at an outdoor unit, the operation data records before the error are acquired over a network and saved to a CSV file. NOTE: To perform "Error Memory Reading", Service Tool and the corresponding outdoor unit must be connected directly with each other.
Page 551
SYSTEM DIAGRAM Remote Side VRF System Side Personal Computer (Locally purchased) Software & protection key for Service Tool * (UTY-ASGXZ1) Personal Computer Internet (Locally purchased) USB Adaptor (Locally purchased) Up to 1 PC VRF network system can be connected simultaneously. WibuKey of UTY-ASGX can be used.
Page 552
SYSTEM REQUIREMENTS ● For VRF System Side PC •Microsoft® Windows® 7 Professional (32/64-bit) SP1 Operating system •Microsoft® Windows® 8.1 Pro (32-bit or 64-bit) •Microsoft® Windows® 10 Pro (32-bit or 64-bit) 1 GHz or higher Memory • 1 GB or more (Windows® 7, 8.1, 10 [32-bit]) •...
Page 553
4-1-2. MODEL: UTY - ASGX Provides extensive monitoring and analysis functions to ensure the proper installation and maintenance of VRF systems. All performance data can be saved for further review and troubleshooting. Files can be shared for further evaluation. FUNCTIONS ...
Page 554
* Limits are deleted from controller and will need to be reprogrammed, if desired. 12) Model Name Writer A Fujitsu model number can be assigned to each target unit. 13) Error Memory Reader When an error occurs at an outdoor unit, the system retains operation data for the 5 minutes preceding the error.
Page 555
14) Time Guard Information * Reference data for determining the maintenance schedule for indoor and outdoor units (operation time for compressor, fan, etc.) can be output into a CSV file. *: Supported by Ver. 1.1 or later SYSTEM DIAGRAM ...
Page 556
OTHER REQUIRED DEVICES (LOCALLY PURCHASED) ● Personal computer that satisfies the following system requirements ® ● Echelon U10 USB Network Interface – TP/FT-10 Channel (Model number: 75010R) (Required for each VRF Network.) PERSONAL COMPUTER SYSTEM REQUIREMENTS ...
Page 557
4-2. WEB MONITORING TOOL 4-2-1. MODEL: UTY-AMGXZ1 SYSTEM DIAGRAM z System components Remote Side VRF System Side Software & Personal protection key for Computer (Locally Web Monitoring purchased) Tool * (UTY-AMGXZ1) Personal Computer Internet USB Adaptor (Locally purchased) (Locally purchased) Up to 2 PCs...
Page 558
PACKING LIST Name and shape Quantity Application Includes the software and manuals for Web Monitoring Tool. Additionally, it works as the software protection key. WHITE-USB-KEY Software protection key to be connected to an USB port on the PC that the Web Monitoring Tool is installed.
Page 559
COMPARISON TABLE Service Tool Web Monitoring Tool UTY-ASGXZ1 UTY-AMGXZ1 Item VRF system VRF system Remote Side Remote Side Side Side ● ● ● ● System List ● ● ● ● Equipment Detail (Diagram) ● ● ● ● Equipment Detail (Status List) ●...
Page 560
4-2-2. MODEL: UTY-AMGX SYSTEM DIAGRAM z System components Monitoring Side VRF System Side Software (UTY-AMGX) Personal Computer (Locally purchased) Software Protection Key Internet Personal Computer USB Adaptor (Locally purchased) Public Telephone LIne VRF network system z Support 4 VRF network system ...
Page 561
PACKING LIST Name and shape Quantity Application Includes the software and manuals for DVD-ROM Web Monitoring Tool Software protection key to be inserted in a USB slot running Web Wibu key Monitoring Tool. Web Monitoring Tool may only run on a PC with (Software protection key) Wibu Key.
Page 562
COMPARISON TABLE Web Monitoring Tool Service Tool UTY-AMGX Item UTY-ASGX Monitoring Side VRF network system Side ● ● ● Interchangeability of equipment ● ● ● Indication of equipment list ● ● Operation control — ● ● ● Indication of refrigerant circuit diagram ●...
Page 563
6. SYSTEM DESIGN DTV_J2U045E_05--CHAPTER06 2017.12.26...
Page 564
CONTENTS CONTENTS 6. SYSTEM DESIGN 6. SYSTEM DESIGN 1. SYSTEM DESIGN ................. 06 - 01 1-1. REFRIGERANT SYSTEM ..............06 - 01 1-2. VRF NETWORK SYSTEM ..............06 - 04 1-3. MOUNTING POSITION ................06 - 10 2. PIPING DESIGN ................06 - 12 2-1.
Page 565
1. SYSTEM DESIGN 1-1. REFRIGERANT SYSTEM CONNECTABLE UNIT WITHIN 1 REFRIGERANT SYSTEM Unit Quantity Remarks Outdoor unit 1 unit 1 to Max. 6 units 3 ton (AOU36RLAVM) Indoor unit 1 to Max. 8 units 4 ton (AOU48RLAVM) 1 to Max. 9 units 5 ton (AOU60RLAVM) z Table ...
Page 566
EXAMPLE OF REFRIGERANT SYSTEM z Example 1 (OK) Outdoor unit Capacity ratio Indoor unit 1 Indoor unit 2 Total Connectable indoor Capacity Model capacity unit capacity Judgement (Btu/h) (Btu/h) Min. Max. Outdoor unit AOU60R 60,000 60,000 ≤ ≤...
Page 567
z Example 4 (OK) Outdoor unit Capacity ratio Indoor unit 1 Connectable indoor Total Capacity Model capacity unit capacity Judgement (Btu/h) (Btu/h) Min. Max. Outdoor unit AOU60R 60,000 60,000 ≤ ≤ 50% 130% 30,000 <...
Page 568
1-2. VRF NETWORK SYSTEM MAXIMUM WIRING LENGTH OF VRF NETWORK SYSTEM Maximum wiring length Transmission line ft. (m) Total wiring length of transmission 11,811 (3,600) Maximum wiring length between units 1,312 (400) Total wiring length in 1 segment * 1,640 (500) VRF network system segment *...
Page 569
CONTROLLER AND CONVERTOR Maximum connectable Model Remarks units in one VRF network system Max.controllable VRF network system : 4 Max.controllable remote controller groups : 1600 per 4 VRF network system System *1:Note UTY-APGXZ1 Max.controllable indoor unit : 1,600 per 4 Controller VRF network system Max.controllable groups : 1,600 per 4...
Page 570
Maximum connectable Model Remarks units in one VRF network system The signal amplifier is required when Signal 1,640 ft.(500 m) or more in transmission UTY-VSGXZ1 Amplifier line length or connected unit exceeds 64units. Total number Max connectable Single split or Multi UTY-VTGX of refrigerant type : 16 units.
Page 571
MAXIMUM CONNECTION OF NETWORK SEGMENT z Network segment : divided network by signal amplifier ● In the following case, signal amplifier is required. (1) When the total length of the transmission line exceeds 1,640 ft. (500 m) (2) When the number of total unit*1 exceed over 64 units.
Page 572
z Meaning of unit Model name Unit ○ 3 ton AOU36RLAVM ○ Outdoor unit 4 ton AOU48RLAVM ○ 5 ton AOU60RLAVM ○ All indoor unit ○ System controller UTY-APGXZ1 ○ System controller Lite UTY-ALGXZ1 ○ Touch panel controller UTY-DTGYZ1 ○...
Page 573
THE MAXIMUM WIRING LENGTH OF UNIT Name Model Maximum wiring length ft. (m) Remote controller to Network convertor 328 (100) UTY-VGGXZ1 Used for single split Network convertor Airconditioner UTY-VTGX Indoor unit to Network convertor 328 (100) Signal amplifier UTY-VSGXZ1 In each network segment 1,640 (500)
Page 574
1-3. MOUNTING POSITION OUTDOOR UNIT For the air conditioner to operate satisfactorily, install it as outlines in installation manual. z Outdoor unit mounting position chapter ● A position where satisfies the mounting space described in “ 3. 3 Installation space". ●...
Page 575
INDOOR UNIT For the air conditioner to operate satisfactorily, install it as outlines in installation manual. z Indoor unit mounting position ● Decide the mounting position with the customer ● Install the unit level on a strong wall, floor, ceiling which is not subject to vibration. ●...
Page 576
2. PIPING DESIGN 2-1. IMPORTANT ITEMS WHEN USING REFRIGERANT R410A R410A operates at higher pressure and has less solubility with mineral oil than traditional R22 refrigerant. Therefore, the lubricant and a part of pipe material are different. Some special tools are necessary. ...
Page 577
WORK FLOW (EXAMPLE) Preparations Prepare Project Schedule ● Always check the refrigerant to be used. Refrigerant check ● Always use the specified refrigerant. ● Prepare materials / tools matched to the refrigerant. Operation chart preparation Start of work Indoor unit installation ●...
Page 578
2-2. PIPING LIMITATION LIMITATION Limitation: ft. (m) Diagram Total pipe length 590 (180) or less * Total Between outdoor unit and the farthest indoor unit 393 (120) or less a + b Between the first separation tube and the farthest indoor unit 131 (40) or less Between outdoor unit and the nearest indoor unit 17 (5) or more...
Page 579
CAUTION Keep the "piping limitation" for correct operation. z Allowable height difference: If the height difference between the indoor unit and outdoor unit is larger than the allowable value: ¾ The pressure loss will be larger → Insufficient cooling and heating ...
Page 580
2-3. PIPE SIZE Outdoor unit Pipe size (table"A") separation tube (optional) First separation tube (optional) header (optional) Pipe size (table"B") Pipe size (table"C") PIPE SIZE SELECTION ● Caution After referring to "COOLING CAPACITY TABLE" followed, select each Pipe size, Separation tube and Header from "COOLING CAPACITY TABLE"...
Page 581
z Pipe size table "B" (Between separation tube to separation tube (header)) Outside diameter in. (mm) Total cooling capacity of indoor unit (Btu/h) Liquid pipe Gas pipe 15,000 to 35,999 3/8" (9.52) 5/8" (15.88) 36,000 to 78,000 3/8" (9.52) 3/4"...
Page 582
INDOOR SIDE BRANCH KIT z Separation tube Separation tube UTP-AX090A z Header Header 3-6 Branches 3-8 Branches UTR-H0906L UTR-H0908L - (06 - 18) -...
Page 583
COOLING CAPACITY TABLE z Outdoor unit Cooling capacity Model name (Btu/h) 36,000 AOU36RLAVM 48,000 AOU48RLAVM 60,000 AOU60RLAVM z Indoor unit Cooling capacity Cooling capacity Type Model name Type Model name (Btu/h) (Btu/h) 12,000 ARUV12TLAV 4,000 AUUA4TLAV 18,000 ARUV18TLAV 7,500...
Page 584
2-4. SELECTION OF PIPE HEAT INSULATING MATERIAL ● Always insulate the refrigerant pipe to prevent condensation and water droplets by the refrigerant pipe. ● Decide the thickness of the heat insulating material by referring to the recommended minimum thickness in Table 1. (For installation condition T=90°F DB (32°C DB), humidity≤70%, humidity≤75%, humidity≤80%, humidity≤85%) ●...
Page 585
2-5. ADDITIONAL CHARGE CALCULATION ● The outdoor unit is charged refrigerant at the factory. ● Additional refrigerant required to be charged on site depending on pipe length. ● The additional refrigerant charge amount is calculated according to the following formula. ●...
Page 586
2-6. EXAMPLE OF PIPING DESIGN REFRIGERANT SYSTEM 1 Outdoor unit Total cooling capacity of indoor units connected downwards to the pipe. (62.0kBtu/h)(52.5kBtu/h) (45.0kBtu/h) (37.5kBtu/h)(30.0kBtu/h) (22.5kBtu/h) (15.0kBtu/h) (7.5kBtu/h) (9.5kBtu/h) (7.5kBtu/h) (7.5kBtu/h) (7.5kBtu/h) (7.5kBtu/h) (7.5kBtu/h) (7.5kBtu/h) (7.5kBtu/h) Indoor Indoor Indoor Indoor Indoor Indoor...
Page 588
REFRIGERANT SYSTEM 2 Outdoor unit Total cooling capacity of indoor units connected downwards to the pipe. (58.0Btu/h) (44.0kBtu/h) (22.5kBtu/h) (21.5Btu/h) (9.5kBtu/h) (7.5kBtu/h) (7.5kBtu/h) (7.5kBtu/h) (14kBtu/h) (12kBtu/h) (14kBtu/h) (12kBtu/h) (9.5kBtu/h) (7.5kBtu/h) (7.5kBtu/h) (7.5kBtu/h) Indoor Indoor Indoor Indoor Indoor Indoor unit unit unit...
Page 590
3. PIPING CONNECTION 3-1. CAUTION OF PIPING CAUTION Keep the permissible length of every piping limitation to prevent a defect or cooling/heating failure. z Piping material ● Use the designated size ( Diameter & thickness ) of refrigerant pipes. ●...
Page 591
CAUTION z Brazing While brazing the pipe, be sure to blow dry nitrogen gas through the pipes. If not used, it will be caused to damage for compressor and clog the strainer and electronic expansion valve. Example) Inside state of brazing pipe section Nitrogen gas used but not sufficient Nitrogen gas used Nitrogen gas does not used...
Page 592
3-2. PIPING TO OUTDOOR UNIT OPENING A KNOCKOUT HOLE CAUTION ● Be careful not to deform or scratch the panel while opening the knock out holes. ● To protect the piping insulation after opening a knock out hole, remove any burrs from the edge of the hole.
Page 593
PIPE CONNECTION CAUTION ● Be sure to install the pipe against the port on the indoor unit and the outdoor unit correctly. If the centering is improper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
Page 594
In the case of AOU60RLAVM ● It is necessary to change a connection pipe diameter by using Reducer. (1) Reducer must be brazed outside of the outdoor unit. (2) Distance between 3-Way-Valve and Reducer ≤ 3 ft. (1m) (3) The part of Reducer do insulation processing after brazing . Brazing 3 ft.
Page 595
3-3. SEPARATION TUBE INSTALLATION z Separation tube Separation tube UTP-AX090A z Installation Select the connections with the pipe diameters that match the selected pipe sizes from the separation tubes, and cut them with a pipe cutter. Joint pipe (Separation tube) Field pipe 0 to 1/8 in.
Page 596
z Restriction when install Be sure following restriction. 1) Installation angle Place the separation tubes horizontally or vertically so that the refrigerant separates evenly. Good Good Prohibited Prohibited Horizontal Vertical CAUTION ● If it is placed horizontally, keep it within ± 15°. Otherwise, it will not separate the refrigerant evenly, causing a reduction in performance.
Page 597
z Heat insulation installation After brazing the pipes, and leak check use the supplied insulation to insulate them. 1) Remove the protective sheet from the double-stick tape that is affixed to the heat insulation. Double-stick tapes 2) Be sure to install the tape (accessory) in each heat insulation to the 2 positions as shown in the following figure.
Page 598
3-4. HEADER HEADER INSTALLATION z Header selection Header 3 - 6 Branches 3 - 8 Branches UTR-H0906L UTR-H0908L When Separate into two branches, use a separation tube instead. z Installation (1) Connecting the connection pipes from the indoor units. Always have at least one indoor unit connected to Always have at least one...
Page 599
(4) Connecting pipe locally purchased from outdoor unit, cut the pipe end to connect the pipe and close the opposite end. Cut 1 in. (25mm) Liquid pipe Field piping Pipe cutter (5) Use header support as necessary. Ceiling Ceiling Gas pipe Liquid pipe Hanging metal Hanging metal...
Page 600
2) Straight tube length A straight tube (minimum length 2 ft. (0.5 m) is necessary before header in order to separate the refrigerant exactly. 2 ft. (0.5 m) or more 2 ft. (0.5 m) or more Main pipe To indoor unit To indoor unit To indoor unit z Heat insulation installation...
Page 601
● When approved for use in local code, we suggest installing Ground Fault Equipment Breaker (GFEB). In that case, GFEB shall be per Fujitsu recommended capacity in order to prevent malfunction of breaker device. ● Always use a dedicated power circuit for each condensing unit (outdoor unit). Never use a power supply shared by another appliance.
Page 602
WIRING SYSTEM OUTLINE (Remote / Monitoring USB adaptor side) *1 (locally purchased) Case of UTY-ALGX *1: Option is necessary. Outdoor unit power supply cable Touch Panel *2: Can not be used. 1ø 60 Hz 208 / 230 V Controller (Remote / NW2 *2...
Page 603
4-2. POWER SUPPLY CABLE WIRING POWER SUPPLY CABLE SPECIFICATIONS Use a separate power supply for the outdoor unit and indoor unit. z Outdoor unit Selection of the power supply cable and breaker when connecting single outdoor unit. Refer to the table for the breaker specifications of each installation condition.
Page 604
z Meaning of "Units" Model name "Units" Count Indoor unit AUUA4TLAV1 (Except Vertical air handler type) AUUA7-24TLAV AUUB18-48TLAV1 AUUB18-36TLAV ARUL4TLAV1 ARUL7-18TLAV ARUM24-36TLAV ARUH36-60TLAV AGUA4-14TLAV1 ABUA12-36TLAV ASUA4-14TLAV1 ASUB18-36TLAV1 ASUA7-14TLAV ASUB18-24TLAV Indoor unit ARUV12-60TLAV (Vertical air handler type) Example 1) Connectable indoor unit : ASUA9TLAV x 4 + AUUB18TLAV x 2 + ARUL9TLAV Amount of "Units"...
Page 605
● Regulation of wire size and circuit breaker differs from each locality, refer in accordance with the regional standard. ● When approved for use in local code, we suggest installing Ground Fault Equipment Breaker (GFEB). In that case, GFEB shall be per Fujitsu recommended capacity in order to prevent malfunction of breaker device. Outdoor units...
Page 606
4-3. TRANSMISSION LINE TRANSMISSION WIRING SPECIFICATIONS Size Wire type Remarks LEVEL 4 (NEMA) 22AWG ® ORKS Transmission cable non-polar 2core, twisted pair solid core (0.33 mm compatible cable diameter 0.65 mm Use the shielded wire specified and always ground it both end. 22AWG (0.65 mm) Level 4 cable with shielded (National Electrical Manufacturers Association (NEMA) Differs from the Category 4 specification proposed by the Electronic Industries Association / Telecommunication Industry Association (EIA/TIA)
Page 607
WIRING RULES ● In the following cases, Signal Amplifier is required. 1) When the total length of the transmission line exceeded 1,640 ft. (500 m) AB+BC+BD+DE+EF > 1,640 ft. (500 m) (Fig. 1) 2) When the total number of units *1 is over 64. ●...
Page 608
TRANSMISSION WIRING FLOW z Step 1 : Decide to use feature of Automatic Address Setting depending on system design Decide to use Automatic Address Setting or Manual Address Setting. ● Automatic Address Setting → Step 2 (1) ...
Page 609
(2) Manual Address Setting Connect the transmission cable like as Fig 4-1, 4-2. Refrigerant system 1 Transmission line Refrigerant system 2 Transmission line Transmission line Refrigerant system 3 Fig. 4-1 Refrigerant system 1 Outdoor unit Indoor unit Indoor unit Indoor unit Refrigerant system 2 Indoor unit Indoor unit...
Page 610
z Step 4 : Confirm how to install Signal Amplifier When Signal Amplifier is installed, network is divided into two network segments. In a network segment (NS) divided by a Signal Amplifier, it has to keep the following facts. 1)Total transmission line length: MAX 1,640 ft.
Page 611
TRANSMISSION LINE SEPARATION RULES ● The transmission line between indoor unit, outdoor unit and controllers can be connected by one cable. ● Terminal board available on the market or the ones inside the indoor unit or outdoor should ...
Page 612
Example 3 : Separation wiring from one terminal board radially. Terminal board Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 System controller Example 4 : Combination of example 2 and 3 Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 Terminal board System controller...
Page 613
WIRING METHOD Practical transmission wiring method is shown below. Each terminal has to be connected the following rules. To other refrigerant circuit outdoor unit Power supply 208/230V 1ø 60Hz Breaker 2 Breaker 1 Outdoor unit Transmission Indoor unit Indoor unit Indoor unit Transmission...
Page 614
4-4. CONTROLLER CABLE WIRING WIRING SPECIFICATIONS Model type Connection to Wire Size Specification System Controller USB Adaptor USB cable System Controller Lite USB Adaptor USB cable Touch Panel Controller Transmission line Refer to 4-3 Central Remote Controller Transmission line Refer to 4-3 22 to 16 Sheathed, Non-polar...
Page 615
WIRED REMOTE CONTROLLER (2-WIRE) WIRING SPECIFICATION Note: UTY-RNRUZ2 only Maximum connectable number of remote controllers by cable size and the length. Cable size Max.connectable number of remote controllers 328 ft. (100 m) < *L ≤ 820 ft. (250 m) < *L ≤ *L ≤...
Page 616
5. DRAIN CONNECTION 5-1. OUTDOOR UNIT CAUTION Perform drain work in accordance with this Manual, and ensure that the drain water is properly drained. If the drain work is not carried out correctly, water may drip down from the unit, wetting the furniture. When the outdoor temperature is 32 °F (0 °C) or less, do not use the accessory drain pipe and drain cap.
Page 617
5-2. INDOOR UNIT GENERAL RULES OF DRAIN PIPING ● Install the drain pipe with downward slope (1/100 or more) and so there are no rises in the pipe. ● Use general hard polyvinyl chloride pipe (ø3/4 [I.D.] ; ø1-1/16 [O.D.]) and connect it with ...
Page 618
CIRCULAR FLOW CASSETTE TYPE / CASSETTE TYPE 11 in. (300 mm) Downward 60 to 78 in. (1.5 to 2.0 m) or less Pipe Hanger slope1/100 or more ø3/4 [I.D.] ; ø1-1/16 [O.D.] drain hose (Locally purchased) (accessory) Attached band ø3/4 [I.D.] ;...
Page 619
MINI DUCT TYPE GOOD PROHIBITED Gap of 60 to 79 in. (1.5 to 2 m) Air bleeding Rise Supporter Locally arranged pipe VP25 [O.D 2 in. Max. 12 in. (300 mm) (32 mm) Trap or more] 28 in. (700 mm) or less Horizontal or upward gradient...
Page 620
SLIM DUCT / SLIM CONCEALED FLOOR TYPE z Ceiling concealed setting Supporter Drain hose Drain cap 60 to 79 in.(1.5 to 2.0 m) Arrange the drain hose lower than this position Prohibited Air vent Rise Trap Prohibited...
Page 621
MEDIUM STATIC PRESSURE DUCT TYPE Downward gradient 1/100 or more Arrange the drain hose lower than this position Attached drain hose Supporter Attached band 60 to 79 in. (1.5 to 2.0 m) Prohibited Trap Rise Air bleeding There is a drain port on the left and right sides.
Page 622
HIGH STATIC PRESSURE DUCT TYPE z Main drain pipe Unit Drain hose (main) Drain pipe (main) Trap 60 to 79 in. (1.5 to 2.0 m) H1 = 4 in. (100 mm) or more H2 = 2 - 4 in. (50-100 mm) ●...
Page 623
VERTICAL AIR HANDLER TYPE On the main drain, provide 1 trap near the indoor unit. This unit has a primary and a secondary drain port. A: 3-15/16 in. (100 mm) (Approx.) B: 1-15/16 to 3-15/16 in. (50 to 100 mm) Indoor unit Downward gradient 1/100 Base or return plenum...
Page 624
COMPACT FLOOR TYPE drain cap drain hose The drain hose can be connected at either side of the indoor unit. drain pan drain pan drain hose No gap Drain cock Hexagon Drain cap drain holder wrench Screw drain cap For connection from the left rear Left piping Cable...
Page 625
FLOOR / CEILING TYPE z Under ceiling setting Remove the hole cover Prohibited Drain hose Arrange the drain hose lower than this position When drain hose is arranged backward. Secure the drain hose with the VT wire. Piping hole Base (Bottom) VT wire...
Page 626
CEILING TYPE Drain hose Supporter Arrange the drain hose 60 to 79 in. (1.5 to 2.0 m) lower than this position Prohibited Rise Trap End in water Fasten the drain pipe with VT wire so that the pipe slopes correctly within the indoor unit . VT wire Drain hose Indoor unit (rear view)
Page 627
WALL MOUNTED TYPE (4-14 Models) Installation method of Drain cap For left outlet piping, cut off the piping outlet cutting groove with a hacksaw. No gap No gap Remove the drain cap by pulling at the projection at the end of the cap with pliers, etc.
Page 628
CENTRAL DRAIN PROCESS When converging multiple drain pipes , install according to the procedure shown below. z For Compact Cassette type, Circular Flow Cassette type, Cassette type T-joint converging drain pipes VP30 (O.D. 1-1/2 [38 mm]) or more Downward gradient 1/100 to 1/50 Compact Cassette type 28 in.
Page 629
DRAIN INSULATION ● Confirm water flows into Drain pan of the indoor unit, and drains from the pan once the drain hose is connected. ● Check drain pipes for leaks. ● Insulate the drain to prevent condensation. ...
Page 630
6. STANDARD ACCESSORIES The following installation parts are supplied. Use them as required. Do not discard any accessories until the installation work has been completed. 6-1. OUTDOOR UNIT Name and shape Q'ty Application Name and shape Q'ty Application Specifications Cable tie For binding power cable and transmission cable manual...
Page 631
6-2. INDOOR UNIT COMPACT CASSETTE TYPE INDOOR UNIT ACCESSORIES CASSETTE GRILLE ACCESSORIES Name and shape Q'ty Application Name and shape Q'ty Application Operating Connector cover For covering connector manual Installation Tapping screw For mounting cassette grille manual (M5 × 12 mm) Cable Tie(s) For securing the Tapping screw...
Page 632
CIRCULAR FLOW CASSETTE TYPE Name and shape Q'ty Application Name and shape Q'ty Application Operating Template (Carton top) For installing indoor unit. manual Installation Washer For installing indoor unit manual Cable tie (Large) For fixing the connection Insulation For installing drain pipe pipe (Large and Small) Push mount cable tie...
Page 633
CASSETTE TYPE Name and shape Q'ty Application Name and shape Q'ty Application Operating Template (Carton top) For installing indoor unit. manual Installation Washer For installing indoor unit manual Cable Tie(s) For securing the Insulation For installing drain hose refrigerant connection (Large) pipes.
Page 634
MINI DUCT TYPE Name and shape Q'ty Application Name and shape Q'ty Application Operating Filter manual Installation Drain hose For installing drain hose manual Template (Carton top) For ceiling openings Band For installing drain hose cutting Also used as packing Washer For installing indoor unit Drain hose insulation B...
Page 635
SLIM DUCT / SLIM CONCEALED FLOOR TYPE Name and shape Q'ty Application Name and shape Q'ty Application Operating Filter (Small) manual (AR07/09/ 12/14) Installation Filter (Big) manual (AR18) Installation template For positioning the indoor unit Drain hose For securing the refrigerant connection Washer For installing indoor unit...
Page 636
MEDIUM STATIC PRESSURE DUCT TYPE Name and shape Q'ty Application Name and shape Q'ty Application Operating Special nut A For suspending the indoor unit from ceiling manual (Large flange) Installation Special nut B manual (Small flange) Cable Tie(s) For securing the Hanger For suspending the...
Page 637
HIGH STATIC PRESSURE DUCT TYPE z Models : ARUH36, ARUH48, ARUH60 Name and shape Q'ty Application Name and shape Q'ty Application Operating Special nut A For suspending the indoor unit from ceiling manual (Large flange) Installation Special nut B manual (Small flange) Cable Tie(s)
Page 638
VERTICAL AIR HANDLER TYPE Name and shape Q'ty Application Operating manual Installation manual Cable Tie For transmission and remote controller cable (Medium) binding. Gas pipe heat insulation For gas pipe at the unit inside - (06 - 74) -...
Page 639
COMPACT FLOOR TYPE Name and shape Q'ty Application Name and shape Q'ty Application Operating Tapping screw For wall hook bracket installation manual Installation Cloth tape For indoor unit installation manual Push mount cable tie For transmission and remote controller Wall hook bracket For indoor unit cable binding...
Page 640
FLOOR / CEILING TYPE Name and shape Q'ty Application Name and shape Q'ty Application Operating Tapping screw For fixing the wall bracket manual Installation Pipe Insulation For indoor piping connection manual Cover plate (left) Cable Tie(s) For securing the refrigerant connection Large pipes.
Page 641
CEILING TYPE Name and shape Q'ty Application Name and shape Q'ty Application Operating Cable Tie(s) Extra For securing the large refrigerant connection manual pipes. Large For securing the power Installation supply, transmission manual cable and remote control cable. Do not run power Medium cable and transmission cable together, electrical...
Page 642
WALL MOUNTED TYPE z Models : ASUA4, 7, 9TLAV1 Name and shape Q'ty Application Name and shape Q'ty Application Operating Tapping screw For wall hook bracket installation manual Installation Cloth tape For indoor unit installation manual Wall hook bracket For indoor unit installation z Models : ASUA12, 14TLAV1...
Page 643
z Models : ASUB18, 24TLAV1 Name and shape Q'ty Application Name and shape Q'ty Application Operating Tapping screw For wall hook bracket installation manual Installation Air cleaning filter For installation, refer to the "CLEANING AND manual CARE" in the operating manual.
Page 644
z Models : ASUA7, 9, 12, 14TLAV Name and shape Q'ty Application Name and shape Q'ty Application Operating Tapping screw For wall hook bracket installation manual (M4 x 25mm) Installation Connecting Cable For wired remote control cable connection and manual simple remote controller cable connection.
Page 645
7. FUNCTION SETTING DTV_VR2U025E_12--CHAPTER07 2018.03.16...
Page 646
CONTENTS 7. FUNCTION SETTING SYSTEM SETTING ..............07 - 01 1-1. SYSTEM TYPE SETTING ................07 - 01 1-2. ADDRESS SETTING ................... 07 - 03 1-3. MANUAL ADDRESS SETTING METHOD ..........07 - 07 1-4. ADDRESS SETTING BY REMOTE CONTROLLER ........07 - 16 1-4-1.
1. SYSTEM SETTING 1-1. SYSTEM TYPE SETTING Set the DIP switch to the corresponding system type as shown in the table. Do not change DIP switch setting not specified below. NOTE Perform the system setting and address setting , before turning on the power. ¾...
Page 649
INDOOR UNIT SETTING Refer to the correct SW position for 2. Function Setting. <Step 1> Refrigerant circuit address setting Set the Rotary SW REF AD x10 & x1. For details, refer to "1-2. Address setting". <Step 2> Indoor unit address setting Set the Rotary SW IU AD x10 &...
1-2. ADDRESS SETTING For this system, each address should be preset before operation. Refer following table for outdoor unit, indoor unit, RB unit and each remote controller. KINDS OF ADDRESS AND SETTING RANGE SETTING UNIT SETTING TYPE OF SWITCH REMARKS RANGE Setting...
Page 651
KINDS OF ADDRESS AND SETTING RANGE SETTING UNIT SETTING TYPE OF SWITCH REMARKS RANGE n Manual address setting Arbitrary numbers can be set in range of 00-99. Setting Refrigerant See the setting method 2-9. 00 ~ 99 example REF AD REF AD circuit address...
1-3. MANUAL ADDRESS SETTING METHOD ADDRESS SETTING DESCRIPTION z Refrigerant circuit address (Set A, Set D and Set O) In case of 2 or more refrigerant system in VRF network system, each refrigerant system should be set an exclusive refrigerant circuit address. Refrigerant system : It means same refrigerant circuit which has connected between outdoor unit and indoor unit by piping.
Page 655
z Outdoor unit address (Set B) This function is available VR-II and V-II series. Set the outdoor unit address for each outdoor unit. Outdoor unit is preset "0" , at factory setting. No change to this setting needed for 1 Outdoor Unit systems. In case of 2 or 3 outdoor units connected in same refrigerant circuit, set the slave unit which has installed farther from master unit to Slave2 setting "2".
Page 656
z Number of outdoor units installed (Set L) This function is available VR-II and V-II series. The number of outdoor units installed in one refrigerant system must be set. Set for all outdoor units. Number of outdoor unit SW SET5-1 OFF SW SET5-2 OFF Master Number of outdoor unit...
Page 657
z Indoor unit address (Set E) Each indoor unit on the same refrigerant system should be set to a different indoor unit address. Rotary SW setting Indoor unit address IU AD x10 IU AD x1 *Setting range 00 - 63(Arbitrary numbers can be set) *Do not set indoor unit address to the range of 64 from 99.
Page 658
z Remote controller address (Set F) One individual remote controller can control up to a max of 16 indoor units with a connecting cable. All units connected to the same remote control area considered a remote control group. i) 3 wire type Only for manual address setting R.C.line: 3 wire 3 wire type R.C.
Page 659
z RB unit address (Set P) Each RB unit in same refrigerant system should be set an exclusive RB unit address. 00 00 00 01 00 00 00 01 00 02 00 13 Rotary SW setting RB unit address RB AD x10 RB AD x1 *Setting range 00 - 63(Arbitrary numbers can be set)
Page 660
z Touch panel controller setting (Set G) Touch panel controller (Max. 16) *1 NOTE: Set Touch panel controller address first, to conduct the initial setting of it. Refer to the "setting manual" for details. *1 : The total of the Touch panel controller, Central remote controller and Network convertor for L ®...
Page 661
z Dual remote control switch for Wired remote controller, Simple remote controller (Set I) When 2 wired remote controllers are connected to the remote control group, select the. ● Slave remote controller cannot be used for timer setting. ●...
Page 662
z Network convertor for L setting (Set M) ORKS ® Network convertor for ORKS ® NOTE: Setting up more than one Network Convertor in one VRF network system is prohibited. *1 : The total of the Touch panel controller, Central remote controller and Network convertor for L ®...
1-4. ADDRESS SETTING BY REMOTE CONTROLLER 1-4-1. WIRELESS REMOTE CONTROLLER ● A wireless remote controller is required to set the infrared address setting. ● This function is available in all indoor unit with infrared signal receiver. ● Infrared address setting for duct type and cassette type models can be made possible by ...
Page 664
SWITCHING SELECTION OF ADDRESS SETTING MODE (3) Press and hold the “MANUAL/AUTO” (4) Press and hold the “FAN” and the “ SET button for 3 seconds. TEMP. ” buttons. While holding these 2 buttons, press the "RESET" button. Pi Pi Pi SET TEMP.
Page 665
BUTTON NAME AND FUNCTION ● Refer to “1-2" for an outline of the address setting. ● It does not matter whether the refrigerant circuit address or indoor unit address is set first. (The method shown here sets the indoor unit address first.) ●...
Page 666
ADDRESS SETTING z INDOOR UNIT ADDRESS SETTING (7) Press the “MODE” button to access the (8) Make sure the function number is ‘01’. If the address setting mode. number is other than ‘01’, press the “ ” or the “...
Page 667
z REFRIGERANT CIRCUIT ADDRESS SETTING NOTE: The refrigerant circuit address is displayed when the following operations are performed even while indoor unit address is displayed on LED display of indoor unit. (14) Press the “FAN” button to select the (15) Press the "...
Page 668
COMPLETION OF ADDRESS SETTING MODE (21) Press and hold the “MANUAL/AUTO ” (22) Press the “RESET” button. button for 3 seconds. Pi Pi Pi After pressing the RESET button, set the custom code again if b,c,d setting. MANUAL AUTO RESET IR RECEIVER UNIT MANUAL...
Page 669
SETTING UP EACH INDOOR UNIT 01-01 01-02 01-03 Repeat steps (1) through to (25). Steps (1) through to (6) and (21) to (25) only need to carried out if the custom code is different to the factory setting of “A”. ...
Page 670
1-4-2. WIRED REMOTE CONTROLLER (UTY-RNKU) ● Indoor unit addresses and refrigerant circuit addresses can be set up using wired remote controllers. ● This function allows setting the addresses of all indoor units to which a wired remote controller is being connected.
Page 671
SWITCHING SELECTION OF ADDRESS SETTING MODE 4) To activate the address setting mode, hold down the three buttons of SET TEMP. V, SET TEMP. Λ and FAN at the same time for 5 seconds or longer. Address setting mode initial display ...
Page 672
ADDRESS SETTING z Indoor unit address setting 5) Pressing the SET BACK button, select a remote controller address (select the indoor unit you want to operate). Remote controller address Ex.) When remote controller address “01” is selected 6) Pressing the SET TIME <...
Page 673
z Refrigerant circuit address setting 9) Pressing the SET BACK button, select a remote controller address (select the indoor unit you want to operate). Remote controller address Ex.) When remote controller address “01” is selected *If the indoor unit you want to operate has already been selected, skip step 9) 10) Pressing the SET TIME <...
COMPLETION OF ADDRESS SETTING MODE 13) To clear the address setting mode and return to the regular display, hold down the three buttons of SET TEMP. V, SET TEMP. Λ and FAN at the same time. Normal mode display ¾...
Page 675
1-4-3. WIRED REMOTE CONTROLLER (UTY-RNRUZ*) ● Indoor unit addresses and refrigerant circuit addresses can be set up using wired remote controllers. ● This function allows setting the addresses of all indoor units to which a wired remote controller is being connected.
Page 676
PREPARATION 3) Turn on the power to the indoor unit. ● By turning on the power indoor units initializes EEV, so make sure the piping air-tight test and vacuuming have been conducted before turning on the power. ● Also check again to make sure no wiring mistakes were made before turning on the power. Breaker ON Indoor Indoor...
Page 677
ADDRESS SETTING z Indoor unit address setting 5) Touch the [Address] on the “Function 6) “Address” screen is displayed. Select the Setting” screen. address of the indoor unit whose function number is to be set by touching [▲] or [▼]. Function Setting Address [002–01]...
Page 678
z Refrigerant circuit address setting 12) Touch the [Address] on the “Function 13) “Address” screen is displayed. Select the Setting” screen. address of the indoor unit whose function number is to be set by touching [▲] or [▼]. Function Setting When setting at all the indoor units, touch Address [002–01]...
Page 679
COMPLETION OF ADDRESS SETTING MODE 19) When the [Back] on the “Function Setting” screen is touched, the display returns to the “Maintenance” screen. Function Setting Address [002–01] Function No. [02] Setting No. [18] Back Setting SETTING UP EACH INDOOR UNIT ...
Page 680
1-4-4. SIMPLE REMOTE CONTROLLER (UTY-RSRY, UTY-RHRY) ● Indoor unit addresses and refrigerant circuit addresses can be set up using simple remote controllers. ● This function allows setting the addresses of all indoor units to which a simple remote controller is being connected.
Page 681
3) Turn on the power to the indoor unit. ● By turning on the power indoor units initializes EEV, so make sure the piping air-tight test and vacuuming have been conducted before turning on the power. ● Also check again to make sure no wiring mistakes were made before turning on the power. Breaker ON Indoor Indoor...
Page 682
9) Select the “13” in Menu 2-F1 Settings. Then press the “ ” button. ADDRESS SETTING z INDOOR UNIT ADDRESS SETTING 10) Select the 2-wire remote controller address with the SET TEMP. “ ” or SET TEMP. “ ” button.
Page 683
13) Setting results are displayed after data transmission. Indoor unit address Ex.) When indoor unit address data "12" is set up ERROR GOOD ● When indoor unit address data was not ● When indoor unit address data was set up on the indoor unit (-- is displayed.) normally set up on the indoor unit.
Page 684
17) Set the setting number with the SET TEMP. “ ” or SET TEMP. “ ” button. Then press the “ ” button. Refrigerant circuit address 18) Setting results are displayed after data transmission. Refrigerant circuit address Ex.) When indoor unit address data "18"...
SETTING UP EACH INDOOR UNIT Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Simple remote Simple remote Simple remote controller controller controller Repeat the procedures in steps 1) through 13), and set up the indoor units requiring address setting.
Page 686
1-4-5. SIMPLE REMOTE CONTROLLER (UTY-RSKU, UTY-RHKU) ● Indoor unit addresses and refrigerant circuit addresses can be set up using simple remote controllers. ● This function allows setting the addresses of all indoor units to which a simple remote controller is being connected.
Page 687
SWITCHING SELECTION OF ADDRESS SETTING MODE 4) To activate the address setting mode, hold down the three buttons of SET TEMP. q , SET TEMP. p and FAN at the same time for 5 seconds or longer. Address setting mode initial display ...
Page 688
ADDRESS SETTING z Indoor unit address setting 5) Pressing the SET TEMP. p button or SET TEMP. q button, select a remote controller address (select the indoor unit you want to operate). Remote controller address Ex.) When remote controller address “01” is selected 6) Press the FAN button so that the “Function number”...
Page 689
z Refrigerant circuit address setting 9) Pressing the SET TEMP. p button or SET TEMP. q button, select a remote controller address (select the indoor unit you want to operate). Remote controller address Ex.) When remote controller address “01” is selected *If the indoor unit you want to operate has already been selected, skip step 9).
Page 690
COMPLETION OF ADDRESS SETTING MODE 13) Press the three buttons of SET TEMP. p, SET TEMP. q and FAN at the same time for 5 seconds or longer. The address setting mode will be cleared and the regular display will be restored.
1-5. AUTOMATIC ADDRESS SETTING The addresses of signal amplifiers, indoor units and RB units can be set automatically. Caution Following are cautions when performing AUTOMATIC ADDRESS SETTING. 1. The Controller cannot be used. 2. AUTOMATIC ADDRESS SETTING may take about 30 minutes. 3.
Page 692
SWITCH POSITION 7 Segment LED lamp LED Lamp Rotary switch POWER ERROR MODE LED101 LED102 (GREEN) (RED) REF AD LED105 LED104 X 10 SW106 SW105 MODE SET1 SET2 SET3 SET4 SELECT ENTER /EXIT SW107 SW108 SW109 Push button DIP switch SET5 SW110...
1-5-1. SIGNAL AMPLIFIER AUTOMATIC ADDRESS SETTING CAUTION ● The Signal Amplifier Automatic Address Setting function can be used for a maximum of 40 signal amplifiers installed within the same network. ● Perform the automatic address setting of signal amplifiers on only one outdoor unit (master unit) within the same network.
Page 694
6) When automatic address setting is completed, the number of signal amplifier is displayed on the LED104. Verify that the count matches the number of signal amplifiers being installed. LED105 LED104 LED105 LED104 Ex.) When eight signal amplifiers are being connected 7) To exit automatic address setting, press the ENTER button (SW109) in the setting completed status shown in step 6) above.
1-5-2. INDOOR UNIT AUTOMATIC ADDRESS SETTING Caution ● The Indoor Unit Automatic Address Setting function can be used for a maximum of 64 indoor units installed within the same refrigerant system. However, a maximum of 45 indoor units can be installed within the same refrigerant system. ●...
Page 696
5) When “11” appears on the LED105, hold down the ENTER button (SW109) for at least 3 seconds.(Unless it is held down for at least 3 seconds, the selection will not be confirmed.) LED105 LED104 LED105 LED104 When the Automatic Address Setting function is activated, the display changes to “run.” 6) When automatic address setting is completed, the number of indoor units of which automatic address setting succeeded is displayed on the LED105, and the number of indoor units of which automatic address setting failed is displayed on the LED104.
1-5-3. RB UNIT AUTOMATIC ADDRESS SETTING This function is available VR-II series. Caution ● Be sure to finish address setting of outdoor unit and indoor unit before performing the automatic address setting of RB unit. ● The RB Unit Automatic Address Setting function can be used for a maximum of 64 RB units installed within the same refrigerant system.
Page 698
5) When “22” appears on the LED105, hold down the ENTER button (SW109) for at least 3 seconds.(Unless it is held down for at least 3 seconds, the selection will not be confirmed.) LED105 LED104 LED105 LED104 When the Automatic Address Setting function is activated, the display changes to “run.” 6) When automatic address setting is completed, the number of RB units of which automatic address setting succeeded is displayed on the LED105, and the number of RB units of which automatic address setting failed is displayed on the LED104.
1-5-4. EXAMPLE FLOW z Example 1 : To automatically set the addresses of signal amplifiers, indoor units and RB units Follow the step below Heat Recovery system Signal amplifier Master unit RB unit address No. Refrigerant circuit address No. ...
Page 700
CAUTION ● Before activating the Automatic Address Setting function, be sure to finish setting the refrigerant circuit addresses of outdoor units. ● Setting the addresses of indoor units automatically does not necessary mean that addresses are assigned sequentially starting from the indoor unit which is located the closest to the outdoor units (instead, addresses are assigned randomly).
Page 701
z Example 2 : To automatically set the addresses of signal amplifiers only (When the addresses of indoor units and RB units will be set manually) Follow the step below Heat Recovery system Master unit Refrigerant system1 Heat Recovery system Refrigerant system2 Heat Pump system...
1-6. TERMINAL RESISTOR SETTING CAUTION Be sure to set the terminal resistor according to specifications. Set the terminal resistor for every network segment (NS). ● If terminal resistor is set in multiple devices, the overall communication system may be damaged. ●...
1-7. INDOOR UNIT CONNECTION CHECK This function is available J-II series. NOTE ● It is necessary to stop SERVICE TOOL (UTY-ASGX) and WEB MONITORING TOOL (UTY-AMGX), when you will carry out indoor unit connection check. 1) After verifying that the system is normally, press the MODE/EXIT button (SW107) once. LED105 LED104 LED105...
Page 704
7) When the number of indoor units appear on the LED104, LED105, press the SELECT button (SW108), the display changes to volume ratio of the indoor units. LED105 LED104 LED105 LED104 Ex.) When volume ratio of the indoor units is 120 %. 8) When “the number of indoor units”...
2. FUNCTION SETTING 2-1. OUTDOOR UNIT SWITCH POSITION 7 Segment LED Lamp LED lamp Rotary switch POWER ERROR MODE LED101 LED102 (GREEN) (RED) REF AD LED105 LED104 SW106 SW105 X 10 MODE SET1 SET2 SET3 SET4 SELECT ENTER /EXIT SW107 SW108...
Page 706
FUNCTION SETTING 1) After verifying that the system is operating normally, press the MODE/EXIT button (SW107) once. LED105 LED104 LED105 LED104 2) Press the SELECT button (SW108), and display “F2” on the LED104. (Monitoring mode) (Setting mode) (Function mode) (Error history mode) LED105 LED104...
Page 707
5) Again, referring to the Settings List shown below, press the SELECT button (SW108), and display the code number of the function you want to set on the LED104. Ex.) To select the Emergency Stop function LED105 LED104 LED105 LED104 Next, press the ENTER button (SW109), and confirm the selection of the function you want to set.
2-1-1. VR-II series SETTINGS LIST Outdoor unit LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting Master Slave Standard (131 to 213ft.) (40 to 65m) Short (less than 131ft.) (less than 40m) Pipe length means the length Pipe length Medium (213 to 295ft.) between master outdoor unit...
Page 709
Outdoor unit LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting Master Slave This mode selects the pattern of the stop function to be operated by the external input terminal (CN134). Batch stop •Batch stop: The stop of all indoor units connected to same refrigerant system due to input signal coming from CN134.
Page 710
Outdoor unit LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting Master Slave Level 1 (stop) The capacity limit can be selected by the external Level 2 (operated at input terminal (CN133) when 40% capacity) operating with the “Energy Energy saving Level 3 (operated at Saving Peak Cut function.”...
Page 711
Outdoor unit LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting Master Slave If the cooling/heating Off (quiet priority) performance becomes insufficient when the low noise Capacity mode is set, it is possible to priority setting set “capacity priority”...
Page 712
Outdoor unit LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting Master Slave Setting number x00 Setting number x01 Electricity meter ▪ ▪ ▪ Set the ones digit and tens digit No. setting 1 ▪ ▪ ▪...
2-1-2. V-II (230V) series SETTINGS LIST LED105 Outdoor unit LED104 Factory CODE Setting Mode Setting Function Remarks CODE No. setting Master Slave Standard (131 to 213ft.) (40 to 65m) Short (less than 131ft.) (less than 40m) Pipe length means the length Pipe length Medium (213 to 295ft.) between master outdoor unit...
Page 714
LED105 Outdoor unit LED104 Factory CODE Setting Mode Setting Function Remarks CODE No. setting Master Slave Select the priority setting of the operation mode. Priority given to the first •Priority given to the first command command: Priority is given to the operation mode which is set first.
Page 715
Outdoor unit LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting Master Slave Celsius (°C) Change of unit ¡ ¡ (Temperature) Fahrenheit (°F) Change of unit ¡ ¡ (Pressure) Level 1 (stop) The capacity limit can be selected by the external Level 2 (operated at input terminal (CN133) when...
Page 716
Outdoor unit LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting Master Slave Setting number xx00 Setting number xx01 Electricity meter Set the ones digit and tens ▪ ▪ ▪ pulse setting 1 digit of the No. of the electricity ▪...
2-1-3. V-II (460V) series SETTINGS LIST LED105 Outdoor unit LED104 Factory CODE Setting Mode Setting Function Remarks CODE No. setting Master Slave Standard (131 to 213ft.) (40 to 65m) Short (less than 131ft.) (less than 40m) Pipe length means the length Medium (213 to 295ft.) Pipe length between master outdoor unit...
Page 718
LED105 Outdoor unit LED104 Factory CODE Setting Mode Setting Function Remarks CODE No. setting Master Slave This mode selects the pattern of the stop function to be operated by the external input terminal (CN134). Batch stop •Batch stop: The stop of all indoor units connected to same refrigerant system due to input signal coming from CN134.
Page 720
Outdoor unit LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting Master Slave Setting number x00 Setting number x01 Electricity meter ▪ ▪ ▪ Set the ones digit and tens digit No. setting 1 ▪ ▪ ▪...
Page 721
2-1-4. J-II series SETTINGS LIST LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting Standard (131 to 213ft.) (40 to 65m) Short (less than 131ft.) (less than 40m) Pipe length Pipe length means the length between outdoor Medium (213 to 295ft.) setting unit and the nearest indoor unit.
Page 722
LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting This mode selects the pattern of the stop function to be operated by the external input terminal (CN134). Batch stop •Batch stop: The stop of all indoor units connected to same refrigerant system due to Switching input signal coming from CN134.
Page 723
LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting Celsius (°C) Change of unit (Temperature) Fahrenheit (°F) Change of unit (Pressure) Level 1 (stop) The capacity limit can be selected by the Level 2 external input terminal (CN133) when operating Outdoor unit with the “Outdoor unit capacity save function.”...
Page 724
LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting 42.8°F (6°C) 14.0°F (-10°C) 17.6°F (-8°C) 21.2°F (-6°C) 24.8°F (-4°C) 28.4°F (-2°C) Setting required if changing of the outdoor temperature setting for heat pump only zone is 32.0°F (0°C) Outdoor required when heater selection control using...
Page 725
LED105 LED104 Factory Setting Mode Setting Function Remarks CODE No. CODE No. setting Setting number x00 Setting number x01 Electricity meter ▪ ▪ ▪ No. setting 1 Set the ones digit and tens digit of the No. of ▪ ▪ ▪...
2-2. INDOOR UNIT (setting by switch) SWITCH POSITION Type of PCB Type of Indoor unit Compact cassette, Cassette, Mini duct, Slim duct/Slim concealed floor, Type 1 Medium static pressure duct, High static pressure duct, Floor/ceiling, Ceiling, Vertical air handler Type 2 Wall mounted (ASUB18, 24) Type 3...
Page 727
z Type 2 DIP switch (type B) Rotary switch (type C) SW PCB SET1 SET2 SW604 SW605 SW606 SW607 SW608 DIP switch (type A) SW601 SW602 DIP switch Rotary switch (type A) (type D) Main PCB z Type 3 ...
Page 728
z Type 4 DIP switch (type A) SET1 SET2 Main PCB Rotary switch (type C) DIP switch (type A) z Type 5 DIP switch (type A) Rotary switch (type C) switch (type A) z Type 6 Rotary switch (type C) DIP switch (type A)
Page 729
z Type 7 Rotary switch DIP switch switch (type A) (type A) (type C) SWITCH TYPE Rotary switch Rotary switch DIP switch DIP switch (type C) (type D) (type A) (type B) 2WIRE 3WIRE - (07 - 82) -...
Page 730
SWITCH TABLE Prohibited (Indoor unit capacity setting) Prohibited (Indoor unit capacity setting) SET1 Prohibited (Indoor unit capacity setting) Prohibited (Indoor unit capacity setting) Prohibited (Indoor unit capacity setting) External input select "edge/pulse" SET2 Indoor unit fan setting for external heater Prohibited type A DIP-SW...
Page 731
DIP SWITCH SETTING z SET2 setting ●External input select “Edge/Pulse” (u...Factory setting) SET2-2 External input select Edge Pulse ●Indoor unit fan setting for external heater It is a function to delay the stop of cooling fan when the air conditioner is stopped. When external heater is connected, turn "ON"...
Page 732
z SET3 setting ●Wireless remote controller custom code switch This DIP switch sets the custom code of the wireless remote controller of an indoor unit. If multiple indoor units are being installed in the same room, switch the custom codes of the corresponding wireless remote controllers in order to prevent their signals from being mixed.
Page 733
z SET4 setting ●Drainage function switch (Slim duct type only) If contained drain pump is not used, set the drainage function to "Disable" in the drainage function switching. (u...Factory setting) SET4-1 Drainage function Enable Disable *NOTE: Always confirm proper setting. Incorrect setting may cause damage from water leakage.
Page 734
z SW1 setting ●Remote controller wire type setting switch (u...Factory setting) Remote controller wire type 2WIRE 2 Wire type 3WIRE 3 Wire type ROTARY SWITCH SETTING z IU AD setting ●Indoor unit address switch Sets the indoor unit addresses. Refer to "1-3.
Page 735
z RC AD setting ●Remote controller address switch When the indoor unit is wired by remote controller group, to identity the indoor unit in the remote controller group, the number (remote controller address) in the remote controller group is set. i) 3 wire type Only for manual address setting Set the remote controller address in the 0.1.2,~,15 order (Blank is not allowed)
2-3. INDOOR UNIT (setting by wireless remote controller) ● This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. ● After the power is turned on, perform the “FUNCTION SETTING” according to the ...
Page 737
SWITCHING SELECTION OF FUNCTION SETTING MODE (2) Press and hold the “MANUAL/AUTO” (3) Press and hold the “FAN” and the “ SET button for 3 seconds. TEMP. ” buttons. While holding these 2 buttons, press the "RESET" button. Pi Pi Pi SET TEMP.
Page 738
BUTTON NAME AND FUNCTION ● During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to FUNCTION DETAILS MODE button Setting number - Start the function setting mode Refer to FUNCTION DETAILS - Changes the display digits FAN button START/STOP button...
Page 739
FUNCTION SETTING (6) Press the “MODE” button to access the (7) Press the “ ” or the “ ” buttons to function setting mode. select the function number. Each time the “MODE” button is pressed, it switches between the one's place and the ten's place positions.
Page 740
Case2 : When setting number is two digits. (11-2) Indoor unit will display the function setting number on "OPERATION"(GREEN), "TIMER "(ORANGE) and "FILTER "(RED) light. Phase1 (Example) Function number : 26, Setting number : 31 OPERATION TIMER FILTER 0.5sec ON / 0.5sec OFF (GREEN) (ORANGE) (RED)
Page 741
COMPLETION OF FUNCTION SETTING MODE (13) Press and hold the “MANUAL/AUTO ” (14) Press the “RESET” button. button for 3 seconds. After pressing the RESET Pi Pi Pi button, set the custom code again if b,c,d setting. MANUAL AUTO RESET IR RECEIVER UNIT MANUAL...
Page 742
SETTING UP EACH INDOOR UNIT 01-01 01-02 01-03 Repeat steps (1) through to (16). Steps (1) through to (5) and (13) to (16) only need to carried out if the custom code is different to the factory setting of “A”. ...
2-4. INDOOR UNIT (setting by wired remote controller [Touch panel]) ● This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. ● After the power is turned on, perform the “FUNCTION SETTING” according to the ...
Page 744
SWITCHING SELECTION OF FUNCTION SETTING MODE 3) When the [Function Setting] on the “Maintenance” screen is touched, the “Installer Password Verification” screen is displayed. Enter the Installer Password, and touch the [OK]. “Function Setting” screen is displayed. Maintenance Function Setting Page 2/ 3 R.C.
Page 745
8)Touch the [Setting] on the “Function Setting” 9) Setting screen of “Setting No.” is displayed. screen. Set the Setting No. with the [▲] or [▼]. Function Setting Function Setting Address [002–01] Address [002–01] Function No. [30] Setting No. Function No. [30] Setting No.
Page 746
COMPLETION OF FUNCTION SETTING MODE 11) When the [Back] on the “Function Setting” screen is touched, the display returns to the “Maintenance” screen. Function Setting Address [002–01] Function No. [30] Setting No. [01] Back Setting SETTING UP EACH INDOOR UNIT ...
2-5. INDOOR UNIT (setting by wired remote controller) ● This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. ● After the power is turned on, perform the “FUNCTION SETTING” according to the ...
Page 748
SWITCHING SELECTION OF FUNCTION SETTING MODE 3) To activate the function setting mode, hold down the three buttons of SET TEMP. V, SET TEMP. Λ and FAN at the same time for 5 seconds or longer. Address setting mode initial display ...
Page 749
FUNCTION SETTING 4) Pressing the SET BACK button, select a remote controller address (select the indoor unit you want to operate) Remote controller address Ex.) When remote controller address “01” is selected 5) Pressing the SET TIME < button or the SET TIME > button, to select the function number. Function number 6) Pressing the SET TEMP.
Page 750
COMPLETION OF FUNCTION SETTING MODE 8) To clear the function setting mode and return to the regular display, hold down the three buttons of SET TEMP. V, SET TEMP. Λ and FAN at the same time. Normal mode display ¾...
2-6. INDOOR UNIT (setting by UTY-RSRY, UTY-RHRY) ● This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. ● After the power is turned on, perform the “FUNCTION SETTING” according to the ...
Page 752
SWITCHING SELECTION OF ADDRESS SETTING MODE 3) With “Monitor Mode” screen displayed, press and hold the SET TEMP. “ ” button and FAN “ ” button simultaneously for at least 2 seconds. 4) The Menu 1 screen is displayed. Press and hold the FAN “ ” button for at least 2 seconds. Setting mode selection screen is displayed.
Page 753
FUNCTION SETTING This procedure changes the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the system to malfunction. Perform the “Function setting” according to the installation conditions using the remote controller. ●...
Page 754
13) Press the “ ” button to return to the 2-wire remote controller address selection screen of (2). If setting has been completed, press the FAN “ ” button to return to the Menu 2-F1 item selection screen. NOTE: ● This item cannot be set from slave remote controllers. ...
2-7. INDOOR UNIT (setting by UTY-RSKU, UTY-RHKU) ● This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. ● After the power is turned on, perform the “FUNCTION SETTING” according to the ...
Page 756
SWITCHING SELECTION OF FUNCTION SETTING MODE 3) To activate the function setting mode, hold down the three buttons of SET TEMP. q , SET TEMP. p and FAN at the same time for 5 seconds or longer. Function setting mode initial display ...
Page 757
FUNCTION SETTING 4) Pressing the SET TEMP. p button or SET TEMP. q button, select a remote controller address (select the indoor unit you want to operate). Remote controller address Ex.) When remote controller address “01” is selected 5) Press the FAN button so that the “Function number”...
Page 758
COMPLETION OF FUNCTION SETTING MODE 8) Press the three buttons of SET TEMP. p, SET TEMP. q and FAN at the same time for 5 seconds or longer. The function setting mode will be cleared and the regular display will be restored.
2-8. FUNCTION DETAILS Function Function Setting number Default Details number Default Adjust the filter cleaning interval notification. If the notification is too Filter early, change to setting 01. If the notification is too late, change to indicator Longer setting 02. interval Shorter Enable...
Page 760
Function Function Setting number Default Details number Enable *1 Auto Enable or disable automatic system restart after a power outage. restart Disable Super low Cool Air Restrain the cold airflow with making the airflow lower when starting Follow the setting Prevention heating operation.
Page 761
Function Function Setting number Default Details number Single setpoint auto mode Switch the setting method of auto mode to single or dual (cooling/ (traditional) heating). *1 Auto mode type For heat pump systems, it is necessary to set the master indoor unit (by wired remote controller).
Page 762
●Temperature conditions when the external heater is ON Temperature (t) when the external heater is ON= Room temperature - set temperature Set value of function: 61 t ˂ -5.4°F (-3°C) t ≤ -0.9°F (-0.5°C) t ˂ -3.6°F (-2°C) t ≤ -1.8°F (-1°C) t ˂...
2-9. RB UNIT SWITCH POSITION DIP switch SET1 (type A) REF AD REF AD RB AD RB AD DIP switch SET2 (type B) Rotary switch (type C) SWITCH TYPE Rotary switch DIP switch DIP switch (type C) (type A) (type B) - (07 - 116) -...
Page 764
SWITCH TABLE Prohibited type A SET1 Prohibited Prohibited DIP-SW Operation mode selecting switch 1 Operation mode selecting switch 2 type B SET2 Cool/heat selection control time switch 1 Cool/heat selection control time switch 2 RB AD RB unit address switch 1 RB AD RB unit address switch 2 x 10...
Page 765
●Cool/heat selection control time setting Setting to reduce the time to switch between heating and cooling mode at the RB unit. When the switching time is short, refrigerant noise may be heard when switching between modes. Always locate the RB unit is a space that will be not be effected by refrigerant noise. (u...Factory setting) SET2-3 SET2-4 Cool/heat selection control time 6 min.
Page 766
2-10. WIRED REMOTE CONTROLLER (UTY-RNKU) Prohibited Dual remote controller setting Prohibited Switch 1 Fahrenheit (°F) / Celsius (°C) setting Prohibited Memory backup setting * Do not use DIP Switch 2 SWITCH POSITION z Wired remote controller Model : UTY-RNK Ý Front case (back side) DIP Switch 2 DIP Switch 1...
Page 767
z SW2 setting ●Dual remote controller setting Set the remote controller SW2 according to the following table. (u...Factory setting) Indoor unit Master unit Slave unit Number Remote controller cable of remote 1 2 3 controller When ground wire is necessary 1 (Normal) 2 (Dual) 1 2 3...
Page 768
2-11. SIMPLE REMOTE CONTROLLER Prohibited Dual remote controller setting °F / °C setting Switch 1 Prohibited Prohibited Prohibited SWITCH POSITION z Simple remote controller Model : UTY-RSKU Model : UTY-RHKU DIP Switch 1 DIP Switch 1 ...
Page 769
z SW2 setting ●Dual remote controller setting Set the remote controller SW2 according to the following table. Indoor unit (u...Factory setting) Master unit Slave unit Number Remote controller cable of remote 1 2 3 controller When ground wire is necessary 1 (Normal) 2 (Dual) 1 2 3...
Page 770
2-12. TOUCH PANEL CONTROLLER ADDRESS SETTING ● Display the Installer Setting screen and press "Change" button of "1. Touch panel controller address setting". ● Select “Address” from 00 to 15 on the screen and click the button. At the end of setting, click ...
Page 771
2-13. CENTRAL REMOTE CONTROLLER ADDRESS SETTING ● Display the Installer Setting screen and Press the [ ] button and move the cursor to "Central Controller Address Setting". ● Press the [ ] button. Central remote controller address setting ●...
Page 772
2-14. WIRED REMOTE CONTROLLER (Touch panel) 2-14-1. REMOTE CONTROLLER ADDRESS SETTING CONFIRM THE REMOTE CONTROLLER ADDRESS 1) When the [RC Address Setting] on the 2) Enter the Installer Password, and touch the [OK]. “Maintenance” screen is touched, the “R.C.Address Setting”...
Page 773
WHEN MANUAL ADDRESS SETTING NUMBER IS RESET 1) Touch the [Address Reset] on the 2) A verification screen is displayed. When the “R.C.Address Setting” screen. [Yes] is touched, a verification screen is displayed. R.C.Address Setting Current Address [001–05] R.C.Address Setting Manual Addressing The address will be returned to factory...
Page 774
2-14-2. REMOTE CONTROLLER MASTER/SLAVE SETTING 1) Touch the [RC Master/Slave Setting] 2) “RC Master/Slave Setting” screen is displayed. on the “Initial Setting” screen. Select the [Master] or [Slave]. Initial Setting R.C. Master / Slave Setting Page 3/ 3 RC Master/ Master Slave Setting Slave...
Page 775
2-14-3. INDOOR UNIT ADDRESS VERIFICATION 1) Touch the [I.U. Address Verification] on the 2) Enter the Installer Password and touch the [OK]. “Maintenance” screen. “Installer Password “I.U. Address Verification” screen is displayed. Verification” screen is displayed. Enter the Installer Password and touch the [OK]. “I.U.
Page 776
2-15. SIMPLE REMOTE CONTROLLER (UTY-RSRY, UTY-RHRY) 2-15-1. REMOTE CONTROLLER ADDRESS SETTING CONFIRM THE REMOTE CONTROLLER ADDRESS 1) Select the “15” in Menu 2-F1 Settings. 2) You can check current allocation of 2-wire Then press the “ ” button. remote controller address (system number and unit number).
Page 777
WHEN MANUAL ADDRESS SETTING NUMBER IS RESET 1) Select the “14” in Menu 2-F1 Settings. 2) To reset the 2-wire remote controller address, Then press the “ ” button. select “1: Reset” with the SET TEMP. “ ” or SET TEMP.
Page 778
2-15-2. REMOTE CONTROLLER MASTER/SLAVE SETTING 1) Select the “06” in Menu 2-F1 Settings. 2) Select the “0: Master” or the “1: Slave” with the Then press the “ ” button. SET TEMP. “ ” or SET TEMP. “ ” button. 0:Master 1:Slave 3) Press the “...
Page 779
2-15-3. INDOOR UNIT ADDRESS VERIFICATION 1) Select the “10” in Menu 2-F2 Settings. Then press the “ ” button. 2-1) Display the smallest 2-wire remote controller address of indoor unit (system number and unit number) of the remote controller group. This address displayed can be switched by the SET TEMP.
Page 780
2-16. NETWORK CONVERTOR 2-16-1. MODEL: UTY-VTGX SWITCH POSITION ● Set network convertor rotary switch SET1, and Dip switch SET2, SET3. REFRIGERANT CIRCUIT ADDRESS SETTING (SET 1) z Example SW setting Refrigerant circuit SET1 (x10) SET1 (x1) address (10 digit)
Page 781
2-16-2. MODEL: UTY-VGGXZ1 SWITCH POSITION ● Set network convertor rotary switch SW110 and SW111. SW110 SW111 Network convertor PCB REFRIGERANT CIRCUIT ADDRESS SETTING For Split system z Example SW setting Refrigerant circuit Rotary SW110 Rotary SW111 address (10 digit)
Page 782
2-17. SIGNAL AMPLIFIER SWITCH POSITION AUTOMATIC ADDRESS SETTING ● Refer to 1-5 MANUAL ADDRESS SETTING 1) Turn on the power for the signal amplifier. 2) While holding down SW4 (the set button), press and release SW7 (the reset button) to enter the address setting mode.
Page 783
5) Press SW4 (the set button) to set the selected address. Ex.) Address No.5 is set. 6) Turn the power off and on or press SW7 (the reset button) to exit the address setting mode and return to the normal mode. If an address setting error occurs (“26 ”...
Page 784
® 2-18. MODBUS CONVERTOR FOR VRF MODEL: UTY-VMGX SWITCH POSITION ● Set MODBUS ® convertor rotary switch SET1 and Dip switch SET2, SET4, SET5, SET6, SET7. ® MODBUS CONVERTOR REMOTE CONTROLLER ADDRESS SETTING (SET 1) z Example ...
Page 785
VRF TERMINAL RESISTER SETTING (SET 2-1) When there is no outdoor unit or signal amplifier in the VRF network segment to which the converter is connected, set to “ON.” ON: Terminal resistance enable OFF: Terminal resistance diable (Default) ...
Page 786
2-19. NETWORK CONVERTOR FOR L ORKS ® SWITCH POSITION SW3 SW4 ADDRESS SETTING When setting address, please be sure that the address of Network Convertor for is not overlap the address of other controller like, Touch Panel Controller, ORKS ®...
Page 787
2-20. THERMOSTAT CONVERTOR MODEL: UTY-TTRX SWITCH POSITION Perform the initial settings using 3 DIP switches (SET 1 to 3) on the circuit board. 2WIRE/3WIRE setting (SET1) Remote controller 2WIRE/3WIRE switching SW Factory setting: 2WIRE Set matched with the connection method of the remote controller cable to be connected.
Page 789
2-21. DUCT STATIC PRESSURE SETTING MODEL: ARUL4TLAV1 MODELS: ARUL7TLAV, ARUL9TLAV, ARUL12TLAV, ARUL14TLAV, ARUL18TLAV MODELS: ARUM24TLAV, ARUM30TLAV, ARUM36TLAV MODELS: ARUH72TLAV1, ARUH96TLAV Change the airflow setting when the external static pressure is different than the default static pressure.
Page 790
2-22. ADMINISTRATIVE INDOOR UNIT SETTING ● When multiple indoor units with separate wired remote controller are connected to one branch port of RB unit (group connection), it is possible to give the cool / heat mode selection authority to one particular wired remote controller (called master wired remote controller).
Page 791
2-22-1. SETTING METHOD WIRED R.C.(Touch panel) z Step1: RB unit function setting (Case of VR-II series) Set SET2 of DIP switch to "Priority given to administrative indoor unit" with function setting of RB unit. (SET2-1: OFF, SET2-2:ON) →Refer to 2-9.
Page 792
WIRED R.C. z Step1: RB unit function setting (Case of VR-II series) Set SET2 of DIP switch to "Priority given to administrative indoor unit" with function setting of RB unit. (SET2-1:OFF, SET2-2:ON) →Refer to 2-9. RB UNIT z Step1: Outdoor unit function setting (Case of V-II) ...
Page 793
NOTE The smallest remote controller address No. RB unit Remote controller address No. Set to master WRC NOTE: In remote controller group, the cool/heat mode is changed over according to a detected room temperature of an indoor unit with the smallest remote controller address number. - (07 - 146) -...
Page 794
2-23. ENERGY SAVING SETTING (SYSTEM CONTROLLER) In this section, an energy saving function which uses electricity meters is explained. System Controller (UTY-APGXZ1, UTY-PEGXZ1) or System Controller Lite (UTY-ALGXZ1, UTY- PLGXE2) is required to perform these functions. FEATURES OF ENERGY SAVING FUNCTION ...
Page 795
● Indoor units can be rotated according to the stoppage rate set for each group. Group A Group B Group C Group D *The indoor unit operation stoppage rate can be selected from 10% to 30%. Without control With control Time Time z Outdoor unit capacity save function...
Page 796
z Peak cut operation function Reduces the Input Power by setting a specific target value (maximum average power [kW]) for all the air conditioners and controlling operation so that this value is not exceeded. Limit control is performed in 3 steps of “Step 1: Set temperature shift” → “Step 2: Thermostat OFF”...
Page 797
GENERAL SETTING PROCESS FOR ENERGY SAVING AND ELECTRICITY CHARGE APPORTIONMENT USING ELECTRICITY METER The general setting process for realizing an energy saving function and an electricity charge apportionment function using an electricity meter is shown as an example in the table below. Process Reference item 1 Overview of the energy saving function and electricity...
Page 798
OPERATION EXAMPLE Electric charges usually consist of the following elements. With the energy saving function, operation for each element is as follows. Operation status is checked by Input Power graph display. Electric charge (Input Power) = Basic charge + Usage charge + Demand charge Reduced by indoor unit Reduced by outdoor unit Reduced by peak cut control...
Page 799
NOTES ON ENERGY SAVING FUNCTION Energy saving function precautions and scope of guarantee The effect of the energy saving function depends on the units used, usage environment, installation environment, and so forth. No guarantee is made as to the specific savings from the energy saving functions.
Page 800
INSTALLATION RESTRICTION OF ENERGY SAVING UNITS (1) Only 1 unit may perform energy saving control at a time. When energy saving control is performed by SYSTEM CONTROLLER (UTY-APGXZ1/PEGXZ1), stop energy saving control *1 from the building management system through the following units. ・BACnet ®...
Page 801
2-24. ELECTRICITY CHARGE APPORTIONMENT SETTING (SYSTEM CONTROLLER, TOUCH PANEL CONTROLLER) In this section, an electricity charge apportionment function which uses electricity meters is explained. System Controller (UTY-APGXZ1, UTY-PEGXZ1) or System Controller Lite (UTY- ALGXZ1, UTY-PLGXA2) or Touch panel controller (UTY-DTGYZ1, UTY-PTGXA) is required to perform these functions.
Page 802
ELECTRICAL WIRING z Electricity meter connection composition To perform energy saving peak cut control, electricity meters with pulse transmission function measuring all the power consumed by the air conditioner are necessary. Multiple meter installations are also possible as long as the number of electricity meters is within the specified limit.
Page 803
z Selection of Electricity meter, CT, and VT Select the electricity meter, CT, and VT by considering the following items. (1) Install electricity meters for each refrigerant system, if circumstances allow. (2) Select VT/CT with a small VT/CT ratio. (3) When using an electricity meter which is specified in pulse units (kWh/pulse), usually select a meter with a 1kWh/pulse output.
Page 804
z Installation example of Electricity meter ● Example of installation for each refrigerant system Electric substation 2nd floor air conditioner Refrigerant system 2 3-phase electric power: equipment (Refrigerant system 2) Single-phase electric power: (Heat Recovery type) MBK: Main Breaker SBK: Sub Breaker Whm: Electricity meter 1st floor air conditioner...
Page 805
● Example of installation for each tenant Electric substation equipment 3-phase electric power: Roof air conditioner Refrigerant system 1 Refrigerant system 2 Single-phase electric power: (All Refrigerant system) MBK: Main Breaker SBK: Sub Breaker Whm: Electricity meter 2nd floor air conditioner (Refrigerant system 2) (Heat Recovery type) Tenant D...
Page 806
INSTALLATION RESTRICTION OF ELECTRICITY METER z Functions that requires installation of electricity meter Use an electricity meter having the following functions: ・Electricity charge apportionment function Install for operation using an electricity meter. (Operation without an electricity meter is also possible.) When using an electricity meter, an electricity meter must be installed for all the units which perform apportionment calculation.
Page 807
z Installation abstract NOTE: The belows are electricity meter connection methods which can be adapted by the System Controller and TPC (Touch panel controller). However, the following mentioned setting restrictions must be observed. (1) Multiple VRF Networks can connect to 1 electricity meter. (with network crossover) NOTE: UTY-ALGXZ1 (+UTY-PLGXE2) does not support multiple VRF Networks.
Page 808
TPC1 management range Whm I/F TPC1 Connect the electricity meter that measures the units managed by the appropriate TPC to the electricity meter I/F belonging to the TPC main unit. Whm I/F TPC2 TPC2 management range TPC1 management range TPC1 Whm I/F Whm I/F TPC2...
Page 809
(3) Installation crossing over refrigerant systems is possible. (4) Outdoor unit/indoor unit/RB unit mixed in 1 meter is possible. (5) There are no restrictions on outdoor units which connect an electricity meter. An arbitrary electricity meter can be connected to an arbitrary outdoor unit. - (07 - 162) -...
Page 810
z Installation restriction Install electricity meters in accordance with the following restrictions: (1) Install an electricity meter only to air conditioners which are the target of the function. When electric lights and other OA equipment are connected to the electricity meter, also their Input Powers are calculated.
Page 811
(5) The externally linked units* shall be connected to the same electricity meter as the air conditioner to which they are connected. * General-purpose unit which performs calculation as an externally linked unit by electricity charge apportionment function. Indoor unit Indoor unit Externally Externally...
Page 812
(9) Installation of electricity meter which crosses the contract is prohibited. When an electricity meter is used by electricity charge apportionment function, install the electricity meter so that it does not cross over the “contract setting” set by electricity charge apportionment.
Page 813
(10) When performing apportionment calculation using electricity meter The electricity meter shall be connected to the necessary air conditioners which are the target of calculation by the electricity charge apportionment function. When an electricity meter is not connected, electricity charge apportionment calculation using an electricity meter may not be possible.
Page 814
<<Outdoor unit + indoor unit + RB unit electricity charge apportionment>> → Connection of an electricity meter to the outdoor unit, indoor unit and RB unit is necessary. Electricity meter is not connected to some indoor units and RB units Electricity meter is not connected to some RB units (11) Electricity apportionment for DX-Kit...
Page 815
● When electricity meter is connected At electricity apportionment, the DX-Kit itself and units [A] and [B] mentioned above can be handled the same as when an electricity meter is not connected. Set the electricity value at ON beforehand for the units [A] and [B] from the “Parameter Setting” screen and install the electricity meter so that the units [A] and [B] are included.
Page 816
ELECTRICITY METER SYSTEM Electricity meter system is the connection configuration of one electricity meter and the air conditioner units which are connected to the power line under it. This is set on the System Controller. Set the System Controller to match the actual electricity meter installation configuration. Since the electricity charge apportionment function/energy saving function perform control using the Input Power data from an electricity meter, it is necessary to set an electricity meter system on the System Controller.
Page 817
SETTING OF OUTDOOR UNIT AND SYSTEM CONTROLLER OR TOUCH PANEL CONTROLLER To obtain the appropriate Input Power by System Controller or Touch Panel Controller, the power value measured by an electricity meter must be properly conveyed. To do this, appropriate setting at the electricity meter, outdoor unit, and System Controller or Touch Panel Controller is necessary.
Page 818
(2) When electricity meter used is specified by pulse constant The connection configuration is shown below. System Controller Electricity meter pulse transmission Pulse constant line reference point to CN135 to CN135 measurement line (PT) Outdoor unit 3ø Touch panel controller Power cable 1ø...
Page 821
1. EXTERNAL INPUT & OUTPUT Note : The length regulations of the cable are as shown in the following figures. L (m) P.C.B [ft. (m)] Type cable Input / Output 492 / 492 Outdoor unit (150 / 150) 492 / 82 connected unit Indoor unit (150 / 25)
Page 822
z V-II series (230V) Output 2 (CN137: Blue) Input 4 Base heater Output 1 (CN134: Red) (CN115: Black) (CN136: Black) Input 3 (CN133: White) Input 2 (CN132: Green) Input 1 (CN131: Yellow) Input 5 (CN135: Orange) Outdoor unit PCB z J-II series ...
Page 823
1-1-1. EXTERNAL INPUT Setting to low noise mode, cooling priority/heating priority selection, outdoor unit operation peak control setting, emergency/batch stop and electricity meter pulse are possible from The electricity meter connections that are can be used by the System Controller are shown below. ...
Page 824
z When function setting is "Batch stop" mode Connector Input signal Command OFF → ON Batch stop CN134 ON → OFF CN134 Command Batch stop Batch stop Operation Indoor unit (outdoor unit) Stop Remote Controller NOTES : ● All indoor units of same refrigerant system stops when Batch stop operates. ●...
Page 825
1-1-2. EXTERNAL OUTPUT Connector Output voltage Status CN136 (Black) Normal DC 12-24 V *1 Error CN137 (Blue) Stop DC 12-24 V *1 Operation ERROR STATUS (Master unit only) This output indicates the outdoor unit and connected indoor unit's "Normal" or "Error" status. ...
Page 826
1-1-3. OPTIONAL PARTS Usage Name and shapes Q'ty Models For external input EXTERNAL UTY-XWZXZ6 For external output CONNECT KIT (Error display, Operation display) For external intput EXTERNAL UTY-XWZXZF (Electricity meter CONNECT KIT pulse) For external output EXTERNAL UTY-XWZXZ9 (Base heater) CONNECT KIT - (08 - 06) -...
Page 827
1-1-4. OUTDOOR UNIT EXTERNAL INPUT / OUTPUT FUNCTION SUMMARY OUTDOOR UNIT EXTERNAL INPUT FUNCTION Function Specifications Power Outdoor usage Dry contact / Low noise Cooling/ unit Item Emergency information Signal Apply voltage mode Heating operation Batch stop Terminal stop from type...
Page 828
1-2. INDOOR UNIT External input External output Input select Connector External connect kit (Optional parts) Apply voltage CNA01 UTY-XWZXZB Control input Dry contact CNA02 UTY-XWZXZD Apply voltage CNA03 UTY-XWZXZ7 Forced thermostat off Dry contact CNA04 UTY-XWZXZE Operation status Error status CNB01 UTY-XWZXZC Indoor unit status...
Page 829
When connected to Apply voltage terminals of multiple indoor units with a connected unit, be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below example. DC power P.C.B supply 12 - 24 V Load resistance CNA01...
Page 830
z Dry contact terminal ([CNA02], [CNA04]) When a power supply is not required, use the Dry contact terminal ([CNA02], [CNA04]). P.C.B CNA02 Ch 1 Ch 2 CNA04 Ch 3 connected unit *c: Select very low current use contacts (usable at DC 12 V, DC 1 mA or less). *d: The wiring is different from Apply voltage terminals.
Page 831
1-2-2. EXTERNAL OUTPUT ● A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft. (25 m). ● Use an external input and output cable with appropriate external dimension, depending on the number of cables to be installed. ●...
Page 832
1-2-3. COMBINATION OF EXTERNAL INPUT AND OUTPUT External input External output CNA01 or CNA03 or Function CNB01 (EXT.OUT) Mode situation CNA02 CNA04 setting Output 1 Output 2 Output 3 Output 4 EXT. IN1 EXT. IN2 Pins 1-2 Pins 1-3 Pins 1-4 Pins 1-5 Forced Indoor unit...
Page 833
1-2-4. INDOOR UNIT EXTERNAL INPUT / OUTPUT FUNCTION SUMMARY INDOOR UNIT EXTERNAL INPUT FUNCTION Function Specifications External power contact/ Wire Item supply Signal Apply EXT. IN1 EXT. IN2 Terminal size / type Allowable Allowable voltage length voltage current CNA02 Edge (PIN1-3)
Page 834
1-2-6. DETAILS OF FUNCTION CONTROL INPUT FUNCTION -1: Operation/Stop mode ●In the case of "Edge" input Function Dip-SW External input Input signal Command setting OFF → ON Operation SET2-2: OFF CNA01 or CNA02 46-00 (Factory setting) (EXT.IN1) ON → OFF Stop CNA01 or CNA02...
Page 835
-2: Emergency stop mode ●In the case of "Edge" input Function Dip-SW External input Input signal Command setting OFF → ON Emergency stop SET2-2: OFF CNA01 or CNA02 46-01 (Factory setting) (EXT.IN1) ON → OFF Normal CNA01 or CNA02 Emergency stop Command Normal...
Page 836
-3: Forced stop" mode ●In the case of "Edge" input Function Dip-SW External input Input signal Command setting OFF → ON Forced stop SET2-2: OFF CNA01 or CNA02 46-02 (Factory setting) (EXT.IN1) ON → OFF Normal CNA01 or CNA02 Forced stop Command Normal...
Page 837
●Considerations when setting forced stop CAUTION When forced stop function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group. Example 1 : OK Remote controller group DC power supply 12 - 24 V P.C.B Load resistance...
Page 838
FORCED THERMOSTAT OFF FUNCTION Function setting Mode External input Input signal * Command OFF → ON EEV OFF CNA03 or CNA04 60-00, 02, 05, 06, 08 0, 2, 5, 6, 8 (EXT.IN2) ON → OFF Normal operation *Edge input only Example of cooling mode CNA03 or CNA04...
Page 839
●System figure example External controller Relay External input wire Outdoor thermistor Indoor unit Indoor thermistor Indoor Outdoor Temperature Temperature Damper motor 88˚F 82˚F (31˚C) (28˚C) Except Indoor unit and External wire (service parts) all other items are Office Fri 10:00AM Mode Set Temp.
Page 840
●Example of Electrical circuit Indoor unit circuit board Dry contact external input wire Indoor unit External Service parts controller Relay CNA04 CNB01 Max. 492ft. (150m) Specification of external input Requirement for relay switch Item Spec Item Spec Terminal CNA04 Min. permissible 1 mA or less load Output voltage...
Page 841
z Example 2 - Individual connection - Function setting for Fan setting when cooling thermostat OFF Number 49-01 (Stop) Forced thermostat off is one of the function to save energy. For example, case of using ventilator at condition with outdoor temperature is lower than Indoor temperature, Indoor unit of air conditioner stop based upon receiving signal from external controller.
Page 842
●Operation status Outdoor temp. < Indoor temp. : ON Signal detected by external controller Outdoor temp. > Indoor temp. : OFF Forced thermostat off Command from external controller Normal Indoor unit Normal means that Indoor unit continues to operate until [Forced thermostat off] signal received, at condition which are set by central and individual controller or detected by thermo sensors of indoor unit.
Page 843
OPERATION STATUS (External output1) External Function setting Mode Output signal Command output 1 0 V → 12 V Operation CNB01 60-00, 06 0, 6 (PIN 1-2) 12 V → 0 V Stop Operation The output for CNB01 (1-2) is ON when the indoor Indoor unit Stop unit is operating.
Page 844
F RESH AIR CONDITIONER (FOR EXTERNAL CONTROL MODULE*) INPUT FUNCTION (mode 1 or 7) * Module that reduces or stops the cooling operating ratio of the air conditioner by intaking fresh air. Example: Direct Digital Controller Function setting Mode External input External output Input signal *...
Page 845
z Example (Individual connection) Direct digital Output: Cooling thermostat ON Output : OFF (Cooling thermostat OFF) controller Thermistor Ventilator Input : VRF cooling control Thermistor Input : ON Indoor Outdoor (VRF cooling OFF) Temperature Temperature 83˚F 89˚F (27.5˚C) (31˚C) Office Fri 10:00AM...
Page 846
●Example of Electrical circuit Indoor unit circuit board Dry contact external input wire External Indoor unit Service parts controller Relay CNA04 CNB01 Max. 492 ft. (150 m) Specification of external input Requirement for relay switch Item Spec Item Spec Terminal CNA04 Min.
Page 847
ECONOMIZER INPUT FUNCTION Cooling economizer: Consists of ducts, dampers, and automatic controlling system. In cold or warm climate, the economizer reduces or stops the VRF compressor, providing cooling using outside air. ●Example of economizer Economizer logic module Fresh air damper Return air damper Room space Exhaust damper...
Page 848
-1: Economizer 1 (Cooling 1 output + occupied) In / Out Mode 2 or 8 (60-02 or 08) Function setting Mode External output Remote controller CNB01 CNB01 (PIN 1-2) (PIN 1-4) UTY-RNRU 60-02, 08 2, 8 [Cooling [Remote Occupied/Unoccupied thermostat controller status...
Page 849
●Wiring diagram example Economizer Logic Indoor unit Modules * Relay CNB01 (Coil side:DC 12 V) AC power supply 24 V *Only the terminals connected to the indoor unit are mentioned here for description. ● As for the connected sensors or other connections to Economizer logic module, refer to the manual for the module.
Page 850
-2: Economizer 2, 3 (Cooling 2 stage output + occupied) In / Out Mode 3 or 4 (60-03 or 04) Function Mode External input External output Remote controller setting CNB01 CNB01 CNB01 (PIN 1-2) (PIN 1-3) (PIN 1-4) 60-03 CNA03 or [Cooling [Cooling high /...
Page 851
●Operation status Economizer input by external controller [VRF cooling ON] (EXT.IN2) Cooling thermostat ON (EXT.OUT) Indoor Cooling high / low unit (EXT.OUT) Indoor Set temp. + 0.9°F (+ 0.5°C) temp. Set temp. - 0.9°F (- 0.5°C) Operation start Room temperature is stable - (08 - 31) -...
Page 852
Economizer 2: Mode 3, Function 60-03) ●Wiring diagram example ( Economizer Logic Indoor unit Modules * Relay CNB01 (Coil side : DC 12 V) AC power supply 24 V Relay CNA04 (Coil side : AC 24 V) *Only the terminals connected to the indoor unit are mentioned here for description. ●...
Page 853
EXTERNAL HEATER OUTPUT (External output4) Function Setting Indoor unit Wired R. C. Outdoor unit Sensor activation Presence of Primary Auxiliary Installation Recommended Control IU fan setting Control heater selection (UTY-RNRU, heater heater configration connection switching for external control using UTY-RNRUZ*, external heaters heater...
Page 854
● Inappropriate designing and installation of external heater Supply air Return air may cause a fire by emitted heat from the external heater. ● Fujitsu-general is not responsible for inappropriate designing or installation of external heating device. - (08 - 34) -...
Page 855
AUXILIARY HEATER CONTROL 1 Operation Condition Heater ON ▪ Heater ON as shown in diagram of heating temperature ▪ Heater OFF as shown in diagram of heating temperature ▪ Other than Heating mode Heater OFF ▪ Error occurred ▪...
Page 856
HEAT PUMP PROHIBITION CONTROL Perform heating by external heater only. VRF indoor unit is Continuous thermostat OFF. Operation Condition Heater ON ▪ Heater ON as shown in diagram of heating temperature ▪ Heater OFF as shown in diagram of heating temperature DIP-SW2-3 ON ▪...
Page 857
●Operation status Heating operation 0.9°F (0.5°C) Room temperature Set temp. -0.9°F (-0.5°C) EEV ON/OFF 12 V Heater 3min or more 1min 1min DIP-SW2-3 ON DIP-SW2-3 OFF NOTE : ● In following operations, EEV will be ON. - Other than Heating - Test Run.
Page 858
HEATER SELECTION CONTROL BY OUTDOOR TEMPERATURE 1 Selects Heat pump or External heater according to the outdoor temperature. When outdoor temperature is high, the heating is performed by using heat pump only. Operation Condition Heater ON ▪ Heater ON as shown in diagram of heating temperature ▪...
Page 859
Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump Heat pump prohibition Combination zone only zone Outdoor temperature zone * zone EEV ON/OFF 12 V Heater DIP-SW2-3 ON DIP-SW2-3 OFF * The Outdoor temperature zone transition from one to another will stay in that zone for minimum 30 min.
Page 860
HEATER SELECTION CONTROL BY OUTDOOR TEMPERATURE 2 Selects Heat pump or External heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Condition Heater ON ▪...
Page 861
●Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump prohibition Combination zone Outdoor temperature zone * zone EEV ON/OFF 12 V Heater DIP-SW2-3 ON DIP-SW2-3 OFF * The Outdoor temperature zone transition from one to another will stay in that zone for minimum 30 min.
Page 862
HEATING THERMOSTAT ON FOR HUMIDIFIER Indoor unit Function Setting External output Situation Installation Heating Cool Air Indoor unit (Example) configration Heating thermostat ON Prevention fan operation thermostat ON No.60 No.43 status CNB01 60-05 Output 1 (PIN 1-2) CNB01 60-06 Output 4 (PIN 1-5) 43-00...
Page 863
2 (In-line connection) ●Example Indoor unit fan operation status use External output: Heating thermostat ON External output 3: Indoor unit fan operation status Humidifier 3 (In-line connection) ●Example Disable cool air prevention function. The indoor unit fan is operated at the set speed continuously. External output: Heating thermostat ON Humidifier The Heating thermostat output for CNB01 (1-2 or 1-3 or 1-4 or 1-5) will be ON when EEV ON or external heater...
Page 864
1-3. RB UNIT External input External output Input select Connector External connect kit (Optional parts) Dry contact CNA01 UTY-XWZXZ6 Cooling priority/ Heating priority Apply voltage CNA02 UTY-XWZXZB 1-3-1. EXTERNAL INPUT ● RB unit can be cooling priority/heating priority selection by using RB unit PCB CNA01 or CNA02. ●...
Page 865
When connected to Dry contact terminals of multiple RB units with a connected unit, insulate each RB unit with relay, etc. as shown on below example. P.C.B P.C.B P.C.B Input device K1 - K3 : Relay (Device for DC Current) NOTE : ●...
Page 866
z Apply voltage terminal ([CNA02]) When a power supply must be provided at the input device you want to connect, use the Apply voltage terminal ([CNA02]) DC power supply 12 - 24 V P.C.B Load resistance CNA02 connected unit *1: Make the power supply DC 12 to 24 V.
Page 867
COOLING/HEATING PRIORITY FUNCTION ●"Edge" input only Connector Input signal Command OFF → ON Heating priority CNA01 or CNA02 ON → OFF Cooling priority CNA01 or CNA02 Heating Priority mode Cooling 1-3-2. OPTIONAL PARTS Usage Name and shapes Q'ty Models EXTERNAL For control input port...
Page 868
1-4. TOUCH PANEL CONTROLLER External input External output Connector External connect kit (Optional parts) Control input TM201 (CN411 or CN412) Electricity meter Operation status CN410 UTY-XWZXZA Error status 1-4-1. EXTERNAL INPUT ● This function performs “Emergency stop” or “All On / All Off” by using the signal to be input externally at external input terminals.
Page 869
Connection example 2: When the electricity meter is connected TM201 Connect the electricity meter to CH1. In this case, the use of CH2 is prohibited. z Apply voltage terminal TM201 (CN412) When a power supply must be provided at the input device you want to connect, use the Apply voltage terminal TM201 (CN412).
Page 870
SELECTING THE FUNCTION The function of the external input terminals is disabled at the factory. Select the function to be used (following table) by installer setting of application. * Turn on the power and select by installer setting after starting the application. Emergency stop Edge / Pulse All on / All off...
Page 871
CONTROL INPUT FUNCTION ●In the case of "Edge" input Terminal Input signal Command OFF → ON All on / Emergency stop TM201 ON → OFF All off / Normal 300ms or more All on / Emergency stop Indoor unit All off / Normal ●In the case of "Pulse"...
Page 872
1-4-2. EXTERNAL OUTPUT Connector Output voltage Status All of indoor units "Stop" Pins1-2 DC 12 V *17 At least one more indoor units "Operation" CN410 (Black) Normal Pins3-4 DC 12 V *17 Error *17: Provide a DC 12 V power supply. Select P.C.B a power supply capacity with an ample DC power supply...
Page 873
1-5. CENTRAL REMOTE CONTROLLER External input External output Input select Connector External connect kit (Optional parts) Dry contact CN6 (and CN7) UTY-XWZXZ7 Control input Apply voltage CN11 (and CN12) UTY-XWZXZ8 Operation status UTY-XWZXZA Error status 1-5-1. EXTERNAL INPUT ● This function performs “Emergency stop” or “All On / All Off” by using the signal to be input externally at external input terminals.
Page 874
z Apply voltage contact When a power supply must be provided at the input device, connect to CN11 and CN12. DC power supply 24 V Connected unit CN11 CN12 (White) (Green) *2 : Make the power supply 24 V. Select a power supply capacity with an ample surplus for the connected load.
Page 875
CONTROL INPUT FUNCTION ●In the case of "Edge" input Connector Input signal Command OFF → ON All on / Emergency stop CN6 or CN11 ON → OFF All off / Normal CN6 or CN11 All on / Emergency stop Indoor unit All off / Normal ●In the case of "Pulse"...
Page 876
1-5-2. EXTERNAL OUTPUT Connector Output voltage Status All of indoor units "Stop" Pins3-4 DC 12 V *5 At least one more indoor units "Operation" (Black) Normal Pins1-2 DC 12 V *5 Error *5: Provide a DC12 V power supply. Select a power supply capacity with an ample DC power surplus for the connected load.
Page 877
1-5-4. CONTROLLER EXTERNAL INPUT / OUTPUT FUNCTION SUMMARY CONTROLLER EXTERNAL INPUT FUNCTION Function Specifications Central External power supply contact / Wire controller Emergency Batch on / Signal Apply Terminal size / (Input function) Allowable Allowable stop Batch off type voltage length...
1. REFRIGERANT CONCENTRATION PRECAUTIONS The system designer and installer are to ensure that the system adheres to all local regulations regarding refrigerant leakage. 1-1. INTRODUCTION Designing VRF systems requires special attention to codes and standards relating to Refrigeration Concentration Limit (RCL). The RCL is intended to “reduce the risks of acute toxicity, asphyxiation and flammability hazards in normally occupied, enclosed spaces”.
1-2. CHECKING CONCENTRATION LIMIT Check concentration limit following steps , and take appropriate measures depending on the situation. Calculate amount of refrigerant [lbs. (kg)] per refrigerant system. Amount of refrigerant per Total amount of refrigerant in Amount of additional refrigerant system system (lbs, kg) refrigerant...
1-3. REFRIGERATION CONCENTRATION COUNTERMEASURES When the concentration limit is exceeded, the designer will need to change the original design or use one of the countermeasures below to reduce potential exposure to refrigerant. Always consult local codes to ensure proper design. ●...
Page 883
2. INSTALLATION PRECAUTIONS 2-1. INDOOR UNIT INSTALLATION PRECAUTIONS Note: The information listed below are general precautions. Some models also include items that do not apply. PLACES WHERE USE PROHIBITED ● Places where there is the danger of combustible gas leakage. ●...
Page 884
[Installation precautions] Contents Countermeasures (Reference) When inside When the indoor unit is installed where the 1) Add heat insulating material the ceiling inside of the ceiling is 86°F (30°C) RH80% to the outside of the indoor is high or greater, the dew point temperature of the unit cabinet.
Page 885
[Installation precautions] Contents Countermeasures (Reference) When In are is returned through the attic, the 1) Replace the indoor unit installing duct thermistor in the indoor unit may not correctly thermistor with a Remote type in an attic detect the room temperature. sensor unit (optional parts) and install the Heating operation: Room is not heated...
2-2. OUTDOOR UNIT INSTALLATION PRECAUTIONS Note: The information listed below are general precautions. Some models also include items that do not apply. PLACES WHERE USE PROHIBITED ● Places where there is the danger of combustible gas leakage ● Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is generated ●...
3. COMPATIBILITY OF VRF SYSTEM COMPATIBILITY OF OUTDOOR UNIT AND INDOOR UNIT z OUTDOOR UNIT AND INDOOR UNIT Compatibility of outdoor unit and indoor unit in refrigerant system as follows. Indoor unit Previous New model *1 model *2 VR- Ⅱ series Heat ...
Page 888
COMPATIBILITY OF CONTROLLER SYSTEM V- Ⅱ series Model VR- Ⅱ series J- Ⅱ series UTY-APGXZ1 System Controller UTY-APGX System Controller UTY-ALGXZ1 Lite UTY-ALGX Touch Panel UTY-DTGYZ1 Controller UTY-DTGY Central Remote UTY-DCGY Controller Wired Remote UTY-RNRUZ Office Fri 10:00AM z Mode Set Temp.
Page 889
V- Ⅱ series Model VR- Ⅱ series J- Ⅱ series External Switch UTY-TERK Controller UTY-TEKX IR Receiver unit (for UTB-YWC all Duct type) IR Receiver unit (for UTY-LRHYB1 Cassette type) IR Receiver unit UTY-LBHXD [for Cassette (circular flow type)] Human Sensor Kit UTY-SHZXC [for Cassette (circular flow type)]...
4. ABOUT CONNECTION BETWEEN SERIES 4-1. PIPING CONNECTION Note: · Piping connection of VR-II V-II and J-II in the same refrigerant system is prohibited. · Mixed connection of 230V model and 460V model is prohibited. EXAMPLE1 (OK) Refrigerant system 1 VR-II Outdoor unit Separation...
4-2. WIRING CONNECTION Note: · Wiring connection of VR-II V-II and J-II in the same refrigerant system is prohibited. · Mixed connection of 230V model and 460V model is possible. EXAMPLE1 (OK) When wiring to each refrigerant system VRF network system Refrigerant system 1 VR-II Outdoor unit...
Page 892
EXAMPLE2 (OK) When stepping over, and wiring to the refrigerant system VRF network system Refrigerant system 1 VR-II Outdoor unit Transmission line RB unit Master Slave Slave Refrigerant system 2 J-II Outdoor unit Transmission line Transmission line Refrigerant system 3 V-II Outdoor unit Transmission line...
Page 893
EXAMPLE3 (Prohibited) Note: Slave unit of VR-II V-II and J-II cannot be connected VRF network system Refrigerant system 1 VR-II Outdoor unit Transmission line RB unit Master Slave Slave Refrigerant system 2 Transmission line V-II Outdoor unit Transmission line Master Slave Refrigerant system 3...
Page 894
10. OPTIONAL PARTS DTV_VR2U025E_12--CHAPTER10 2018.03.16...
Page 896
1. SEPARATION TUBE CONNECTION CAPACITY Separation tube Total cooling capacity of indoor units (x) (kBtu/h) For 2 pipes For 3 pipes UTR-BP090X or x < 96.5 UTP-BX090A UTP-AX090A UTR-BP180X or 96.5 ≤ x < 193 UTP-BX180A UTP-AX180A UTR-BP567X or 193 ≤...
Page 897
z For 2 pipes Unit: KBtu/h UTP-AX090A UTP-AX180A Liquid pipe Liquid pipe 89 ≤ x < 185.5 7.5 ≤ x < 89 96.5 ≤ x < 193 15 ≤ x < 96.5 7.5 ≤ x < 96.5 7.5 ≤ x < 48 Gas pipe Gas pipe 89 ≤...
Page 898
z For 3 pipes Unit: KBtu/h UTP-BX090A UTP-BX180A Liquid pipe Liquid pipe 89 ≤ x < 185.5 7.5 ≤ x < 89 96.5 ≤ x < 193 15 ≤ x < 96.5 7.5 ≤ x < 96.5 7.5 ≤ x < 48 Discharge gas pipe Discharge gas pipe 89 ≤...
Page 899
1-1. SEPARATION TUBE FOR 2 PIPES UTR-BP090X z Port diameters Unit: in. (mm) Liquid pipe Gas pipe Q'ty Q'ty ø3/8 (9.52) ø1/2 (12.70) ø5/8 (15.88) ø1/2 (12.70) ø1/4 (6.35) ø1/4 (6.35) ø5/8 (15.88) ø3/4 (19.05) ø3/8 (9.52) ø3/8 (9.52) ø3/4 (19.05) ø7/8 (22.22)
Page 928
4. RB UNIT 4-1. SPECIFICATIONS Model name UTP-RU01AH UTP-RU01BH UTP-RU01CH UTP-RU04BH Power source 1 Phase 208 / 230V ~ 60Hz Available voltage range 187 to 253V Number of branches Maximum number of connectable indoor units per branch Maximum capacity of connectable indoor Q ≤...
Page 929
4-2. DIMENSIONS MODELS: UTP-RU01AH, UTP-RU01BH, UTP-RU01CH Unit: in. (mm) 7-13/16 (198) 13-1/8 (333) 1-3/16 (30) 6-1/8 (155) 11/16 (18) 8-1/8 (206) 6-3/8 (162) 11-3/4 (298) 5-13/16 (147) Indoor unit side Outdoor unit side Ceiling hanging 13-1/8 (333) 11/16 (18) 7-13/16 (198) 1/4 (7) Wall hanging...
Page 931
4-3. INSTALLATION ● Control box which is a part of RB units can be also changed the position depending on installation condition at each side of RB units ● Be sure to prepare Service access in control box side. ● Since the sound of refrigerant flow may be felt as an unusual sound, do not install in the underpart of the roof, such as a bedroom which sound worries.
Page 932
MODEL: UTP-RU04BH z Ceiling installation Unit: in. (mm) 1 (20) or more 20 (500) or more 20 (500) or more 1 (20) or more (11 (280) or more *1) (11 (280) or more *1) *1: When piping is not connected Service access 28 (700) or more - (10 - 37) -...
Page 933
4-4. REFRIGERANT CIRCUIT MODEL: UTP-RU01AH GAS LINE (Discharge gas) (D1) (B2) to Indoor unit GAS LINE (B1) (S1) (Suction gas) MODEL: UTP-RU01BH GAS LINE (Discharge gas) (D1) (B2) to Indoor unit GAS LINE (B1) (S1) (Suction gas) (S2) ...
Page 934
MODEL: UTP-RU04BH GAS LINE (Suction gas) LIQUID LINE GAS LINE (Discharge gas) to Indoor unit (D1) (B2) to Indoor unit (B1) (S1) (S2) to Indoor unit (D1) (B2) to Indoor unit (B1) (S1) (S2) to Indoor unit (D1) (B2) to Indoor unit (B1)
Page 942
® BACnet GATEWAY ® BACnet GATEWAY (Hardware) (Software) ● UTY-VBGX ● UTY-ABGXZ1 - Software protection key with software ● UTY-ABGX - DVD-ROM ® VRF network system to the BMS system using BACnet protocol. - Software protection key ...
Page 943
7. CASSETTE GRILLE ● UTG-CCGV ● UTG-CCGVG ● For Compact Cassette type ● For Compact Cassette type IR receiver attached IR receiver attached For grid ceiling ● UTG-LCGV ● UTG-LCGVCW, UTG-LCGVCB ● For Cassette type ● For Circular Flow Cassette type - (10 - 48) -...
Page 944
8. OTHERS 8-1. PARTS LIST 8-1-1. INDOOR UNIT Air outlet shutter plate Panel spacer Wide panel Insulation kit for high humidity UTR-YDZK UTG-BKXA-W UTG-AKXA-W UTZ-KXRA UTZ-KXRA Type Model name UTR-YDZB UTZ-KXGC UTR-YDZC UTG-BGYA-W UTG-AGYA-W UTZ-KXGA UTZ-KXGB Compact cassette AUUA4TLAV1 AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV...
Page 945
Fresh air intake kit IR receiver unit Human sensor kit UTZ-VXRA Type Model name UTZ-VXAA UTY-LRHYB1 UTB-YWC UTY-LBHXD UTY-SHZXC UTZ-VXGA Compact cassette AUUA4TLAV1 AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV AUUA18TLAV AUUA24TLAV Cassette AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV Circular flow cassette AUUB18TLAV1 AUUB24TLAV1 AUUB30TLAV1 AUUB36TLAV1 AUUB48TLAV1 Mini duct...
Page 946
Auto louver grille kit Air filter Type Model name UTD-GXSA-W UTD-GXSB-W UTD-GXTA-W UTD-GXTB-W UTD-LF25NA UTD-LF60KA Compact cassette AUUA4TLAV1 AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV AUUA18TLAV AUUA24TLAV Cassette AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV Circular flow cassette AUUB18TLAV1 AUUB24TLAV1 AUUB30TLAV1 AUUB36TLAV1 AUUB48TLAV1 Mini duct ARUL4TLAV1 Slim duct / ARUL7TLAV Slim concealed floor...
Page 947
Remote Flange Drain pump unit sensor unit Type Model name UTD-SF045T UTD-RF204 UTZ-PU1NBA UTZ-PU1EBA UTR-DPB24T UTY-XSZX Compact cassette AUUA4TLAV1 AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV AUUA18TLAV AUUA24TLAV Cassette AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV Circular flow cassette AUUB18TLAV1 AUUB24TLAV1 AUUB30TLAV1 AUUB36TLAV1 AUUB48TLAV1 Mini duct ARUL4TLAV1 Slim duct / ARUL7TLAV...
Page 951
AIR OUTLET SHUTTER AIR OUTLET SHUTTER PLATE PLATE ● UTR-YDZB ● UTR-YDZC, UTR-YDZK ● For Compact Cassette type ● For Cassette type ● For Cicular flow Cassette type PANEL SPACER WIDE PANEL ●...
Page 952
FRESH AIR INTAKE KIT IR RECEIVER UNIT ● UTY-LRHYB1 ● UTZ-VXGA, UTZ-VXRA ● For Cassette type ● For Cassette type For use with wireless remote controller Model UTY- LNHU (must be purchased separately). IR RECEIVER UNIT ...
Page 953
Unit: in. (mm) AIR FILTER AIR FILTER ● UTD-LF25NA (2pcs.) ● UTD-LF60KA (2pcs.) ● For Medium Static Pressure Duct type ● For High Static Pressure Duct type 19-15/16 (507) „‚o‚oƒ?@‚X‚R‚V‚Q‚O‚R‚Q‚w‚w‚w PULL 16-15/16 (430) FLANGE (Square) ...
Page 954
REMOTE SENSOR UNIT HALF CONCEALED KIT ● UTR-STA ● UTY-XSZX ● For All Duct type ● For Compact Floor type PRESSURE SENSOR KIT ● UTY-SPWX ● For V-II series Controller Sensor Controller: Connect to Master outdoor unit Sensor: On the closest pipe of the indoor unit - (10 - 59) -...
Page 955
EXTERNAL CONNECT KIT EXTERNAL CONNECT KIT ● UTY-XWZXZ6 ● UTY-XWZXZ7 ● For Outdoor unit / RB unit ● For Indoor unit / Central remote controller EXTERNAL CONNECT KIT EXTERNAL CONNECT KIT ● UTY-XWZXZ8 ●...
Page 956
EXTERNAL CONNECT KIT EXTERNAL CONNECT KIT ● UTY-XWZXZD ● UTY-XWZXZC ● For Indoor unit ● For Indoor unit EXTERNAL CONNECT KIT EXTERNAL CONNECT KIT ● UTY-XWZXZE ● UTY-XWZXZF ● For Indoor unit ●...
Page 957
9. OPTIONAL PARTS INSTALLATION 9-1. DRAIN PUMP UNIT MODEL: UTZ-PU1NBA z Specifications Unit Specifications Pump Lift-up in. (mm) Maximum 39-3/8 (1,000) Power source 220-240V, 50/60Hz Input Power (230V, 50/60Hz) 12 / 10.8 Current (230V, 50/60Hz) 114 / 92 Dimensions (H ×...
Page 958
z Installing drain pump unit NOTE: Loosen the nut on the indoor unit and hook the tip of the bracket. Tighten the nut securely. Make sure that the drain pump unit is level. Hose band (Big) Hose band (Small) Joint hose Thread the hose band through the joint hose and secure to the drain pump unit and indoor unit.
Page 959
z Installing pipe Gap of 59-1/16 to 78-3/4in. (1.5 to 2.0m) Air vent Rise Supports Locally purchased Pipe [O.D.1-1/16in.] or more Trap Prohibited [O.D.1-5/16in.] or more Observe the following procedures to construct centralized drain pipe fittings. z Electrical wiring ...
Page 960
MODEL: UTZ-PU1EBA z Application indoor units Type Model name Ceiling ABUA30TLAV, ABUA36TLAV z Installing drain pump unit & Electrical wiring To indoor unit Drain hose B circuit board Float switch wire Drain pump assy (Connector: Red) Drain pump wire (Connector: Blue) Drain hose A...
Page 961
9-2. FRESH AIR INTAKE KIT (MODEL: UTZ-VXAA) FEATURE • Up to 10% of the units “high” air volume of outside air can be introduced into the “Fresh Air Intake Kit”. Connecting duct Indoor unit (Locally purchased) Panel Fresh air intake kit ...
Page 962
SPECIFICATIONS Model name UTZ-VXAA Fresh air Max. fresh air %(for High) intake intake volume Connection duct type in. (mm) ø 3-15/16 (100) Dimension 4-3/4 × 22-7/16 × 22-7/16 (120 × 570 × 570) in. (mm) (H × W × D) Gross 6-1/2 ×...
Page 963
PRECAUTION z About fresh air intake kit • The Fresh Air Intake Kit can be installed onto cassette type air conditioners. • The volume of ventilated air provided by the Fresh Air Intake Kit may be unable to fulfill ventilation regulations in all countries.
Page 964
DIMENSIONS Unit: in. (mm) Min.17-11/16 (450) Inspection hatch 4-1/4 (108) 10-1/8 (257) 3-15/16 (100) 7-15/16 (201) 1-3/4 (45) (SIDE VIEW) 22-7/16 (570) (TOP VIEW) (SIDE VIEW) • When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) - (10 - 69) -...
Page 965
AIRFLOW (200) 0.80 Unit: in. (mm) (150) 0.60 (100) 0.40 (50) 0.20 17-11/16 (450) Measurement location of data (50) (100) (150) (200) shown in graph Airflow [CFM (m /h)] - (10 - 70) -...
Page 966
FRESH AIR CONTROL OUTPUT • You can control duct fan by synchronization with fan operation of indoor unit. • Wire for fresh air control output is supplied with Fresh Air Intake Kit. • Extended length of the wire : Max. 82ft. (25m) z Connection diagram ...
Page 967
ACCESSORY PARTS Name and shape Q'ty Application Name and shape Q'ty Application Installation Extension wire for Extension wire for receiver kit receiving kit manual Chamber Adaptor for connecting Wire (External output ) For connect indoor unit duct to relay of duct fan (For single or multi) Wire cover...
Page 968
9-3. FRESH AIR INTAKE KIT (MODELS: UTZ-VXRA, UTZ-VXGA) FEATURE • Up to 10% of the units “high” air volume of outside air can be introduced into the “Fresh Air Intake Kit”. Cassette type attached Fresh Air Intake Kit Indoor unit Connecting duct (Locally purchased)
Page 969
SPECIFICATIONS Model name UTZ-VXRA, UTZ-VXGA Fresh air Max. fresh air 2- way intake % (for High) intake intake volume 1- way intake Connection duct type ø 3-15/16 (100) in. (mm) Dimension 4-3/4 × 33-1/16 × 33-1/16 (120 × 840 × 840) in.
Page 970
PRECAUTION z About fresh air intake kit • The Fresh Air Intake Kit can be installed onto cassette type air conditioners. • The volume of ventilated air provided by the Fresh Air Intake Kit may be unable to fulfill ventilation regulations in all countries.
Page 971
DIMENSIONS Unit: in. (mm) □ Min. 17-11/16 (450) Inspection hatch □ Min. 17-11/16 (450) (TOP VIEW) 15-3/4 to 17-11/16 Inspection hatch (400 to 450) 2-3/16 (55) 33-1/16 (840) 2-3/16 (55) 3-15/16 (100) (SIDE VIEW) (SIDE VIEW) Standard type * Slim type * *: The size is different according to indoor unit used.
Page 972
AIRFLOW Unit: in. (mm) for 2-Way Intake (200) 0.80 39-3/8 (1000) (150) 0.60 (100) 0.40 1-Way Intake (50) 0.20 2-Way Intake Measurement location of data (50) (100) (150) (200) (250) (300) (350) (400) shown in graph Airflow [CFM (m /h)] for 1-Way Intake 39-3/8 (1000)
Page 973
FRESH AIR CONTROL OUTPUT • You can control duct fan by synchronization with fan operation of indoor unit. • Wire for fresh air control output is supplied with Fresh Air Intake Kit. • Extended length of the wire: Max. 82ft. (25m) z Connection diagram ...
Page 974
ACCESSORY PARTS Name and shape Q'ty Application Name and shape Q'ty Application Installation Insulation Affixing the insulation manual outside of the kit Duct Flange Adaptor for connecting Insulation Affixing the insulation duct outside of the cover Cover Protective cover to Cable Tie...
Page 975
9-4. AUTO LOUVER GRILLE KIT MODELS: UTD-GXSA-W, UTD-GXTA-W UTD-GXSB-W, UTD-GXTB-W SPECIFICATIONS UTD-GXSA-W UTD-GXSB-W Model name UTD-GXTA-W UTD-GXTB-W Power Supply Connecting with Control box of indoor unit Attachment of Auto Louver Louver attached by screws to the flange or rectangular duct Extension Square Duct Limit 39-3/8 (1.0) (Max.
Page 976
DIMENSIONS z MODELS : UTD-GXSA-W, UTD-GXTA-W Unit : in. (mm) 25-3/8 (645) P7-7/8 (200) x 3 = 23-5/16 (600) 4 x ø1/8 (3.2) Burring hole 2 x ø3/16 (5) Hole 10-3/8 (263) 3-5/16 (84) 26-7/8 (683) 2-15/16 (74) 2 x ø1/8 (3.2) Burring hole 1-1/8 (29) 21-7/8 (555)
Page 977
ACCESSORY PARTS Name and shape Q'ty Name and shape Q'ty Installation manual Screw-A 3/8 in. (10 mm) Operating manual Screw-B 3/8 in. (10 mm) Grille Cable clip Bracket frame Cable tie Bushing - (10 - 82) -...
Page 978
URL : http://www.fujitsu-general.com " " is a worldwide trademark of FUJITSU GENERAL LIMITED. * Microsoft, Internet Explorer, and Windows are trademarks of Microsoft Corporation in the United States and other countries. * Adobe and Acrobat Reader are either registered trademarks or trademarks of Adobe Systems Incorporated in the United States and/or other countries.