Model PAD-5 Intelligent Notification and Auxiliary Power Expander Installation Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Page 3
In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art security concept. Siemens’ portfolio only forms one element of such a concept. You are responsible for preventing unauthorized access to your plants, systems,...
(315-034686) for specifics about configuring the PAD-5-MB and its expansion modules. NOTE: Pathway Survivability: Each circuit must be evaluated and tested to ensure compliance to the application and area of protection to meet the criteria of NFPA 72. Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
- Status LED indicates if output is in trouble, or was previously in trouble, in the case of an intermittent fault Integrated P2 loop circuitry for connection to Fire Panel device loop (P2) with isolation from short circuit capabilities. Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Page 7
NOTE 6: The battery charger is temperature compensated, to help increase the life of the batteries. Because very hot environments can shorten the life of batteries, the panel is set to disable the charger if the Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
The PAD-5 meets the Class A requirements of the Code of Federal Regulations (CFR 47), Part 15, Subpart 15, for electromagnetic field emissions. General Specifications • Operating temperature 32 – 120ºF (0 – 49ºC) • Relative humidity Up to 93%RH @ 86ºF (30ºC) non-considering Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
All field wiring and connections to the PAD-5-MB must be disconnected, and AC must be disconnected before removing fasteners and remov- ing the board assembly from the enclosure. Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Page 10
S54400-Z60-A1 (Document ID A6V10334250) 3. PAD-5-MB, P/N S54339-A5-A1 4. Max. Battery Size inside enclosure, 18AH Batteries, BP-61 P/N 175-387194 FP2012-U1 (300W) POWER SUPPLY FP2011-U1 (170W) ADAPTER PLATE POWER SUPPLY WITH PAD-5-MB Figure 3: Typical Configuration Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Page 11
1. Enclosure, Model PAB2-ENCL-R, P/N S54339-A11-A1 (Red), or Model PAB2- ENCL, P/N S54339-A10-A1 (Black) 2. Power Supply, Model FP2011-U1, P/N 500-450222 or Model FP2012-U1, P/N S54400-Z60-A1 3. PAD-5-MB, P/N S54339-A5-A1 4. Max. Battery Size inside enclosure, up to 35AH Batteries, BTX1, P/N 175-083897 Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
8. Before applying power, the address needs to be set on the PAD-5-MB (and the expansion card if using one). Do not have the expansion module connected to the Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
3. The procedure for programming the cable can be found in the DPU manual (P/N 315-033260). DPU firmware Rev 09.01.0022 or greater is required in order to have compatibility with the PAD-5-MB and the expansion boards. Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Figure 5a: PAD-5 Wire Routing in 1HU NOTE → If batteries larger than 18Ah are needed, an external battery box will be required. Route wires through Non-Power limited, knockout location A. Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Page 15
NOTE → If batteries larger than 35Ah are needed, an external battery box will be required. Route wires through Non-Power limited, knockout location A. Knockout Locations Non-Power Limited - High Voltage (AC power) Power Limited Power Limited Power Limited Power Limited Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
IN PAD-5-ENCL (TO CONNECT GROUND WIRE FROM AC MAINS) CAUTION: INSTALL THE PROTECTIVE COVER ON THE AC MAINS (L, N, G) Figure 6: AC Wiring to FP2011-U1 (Doc P/N 315-050222) or FP2012-U1 (Doc ID A6V10334250) Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
AC IN ORANGE (PIN #1) 120/240V (+26VDC) 50/60Hz Figure 8: FP2012-U1 (Doc. ID A6V10334250) NOTE: Check brownout switch for the power supply and select proper source voltage. Figure 9: FP2011-U1 (Installation Instruction P/N 315-050222) Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
(Green) Power supply status indication. Used by the periphery board to know the health of the power supply. (Black) Return (ground) +24 V (Red) DC +24 V system supply Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
As soon as the temperature falls below the threshold, the batteries will continue to charge. The OI will post a trouble, and when the temperature is safe, the OI will post the “OUT”. Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
ACTIVE. The dedicated Auxiliary Output (X800) will remain on, even if the battery charger is active. It is only NACs configured for Auxiliary Output that are affect by the battery charger priority. Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
* EOL resistor must be connected for NAC(s) not used. EOL resistance: 2.2K – 24K Ohms Combined Total output between all on-board NACs, Class A Expansion Module NACs, and AUX is 9A for a FP2012-U1 and 6A for a FP2011-U1 Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Page 24
Positive feed for notification appliances for NAC 2 Class A or NAC 4 Class B NAC4_- Return feed for notification appliances for NAC 2 Class A or NAC 4 Class B Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
(1, 2) and leave on (3, 4). If the PAD-5-MB is the end, then the EOL goes on (3, 4). If not, continue the run from (3, 4) to the next PAD-5-MB (1, 2). Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Page 27
Master NAC from PAD-5-MB Polarity shown in Active mode (or other NAC source) PAD-5 Last NAC Follower (configure in ZEUS as NAC follower) BF - X700 X600 Figure 11: Using NAC Follower with multiple XDLCs Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
X800 2 Combined Total output between all on-board NACs, Class A Expansion Module NACs, and AUX is 9A for a FP2012-U1 (300 Watt Power Supply) and 6A for a FP2011-U1 (170 Watt Power Supply). Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Designation Description Positive feed for FDNet (P2) IN / OUT Return feed for FDNet (P2) IN Return feed for FDNet (P2) OUT Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
NOTE: Class X wiring X700 X600 ONE SLOT OF CC -5 24V+ 24V- DO NOT USE TO 24 VDC FROM THE PSC -12 X DLC Card X700 PAD-5 PAD- 5 PAD-5 Figure 12: X700 Wiring Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Page 31
PAD-5 Device Device Device Device XDLC Siemens SLC Devices include polarity insensitive CLASS A Topology Dets, TRIs, Pull Stations, Call Points, Conventional Zone Modules, etc. (Mixed Mode – polarity insensitive and isolator devices) A maximum of 30 SLCs can be connected...
Page 32
PAD-5 Device XDLC Device Device Siemens SLC Devices include polarity insensitive Dets, TRIs, Pull Stations, Call Points, Conventional Zone Modules, etc. CLASS B Topology All NACs provided by all PAD-5s on this circuit must serve a single notification zone. A...
Blinking for event message Blinking Indicates main microprocessor is processing data H600 Yellow P2 - Normal condition H700 Yellow P2 - Trouble Condition P2 – Pattern not Locatable? P2 – Pattern Locate? H701 Green Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
FP2012-U1 (for batteries 35 Ah and larger) Rated: 9A Max @ 24 VDC Not power limited Battery output Plug strip X101 DC 20.4 V…DC 26.4 V Voltage (DC 24 V nominal) Current Max. 11.5 A Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Page 35
Current Max. 3 A ⚫ Design Short-circuit protection ⚫ Voltage surge protection ⚫ Power limited NAC follower input Plug strip X600 Voltage DC 24 V filtered Current Max. 12 mA Design Voltage surge protection Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
"Always ON" Note 3: AUX current must be included in the ALARM column if AUX circuit is configured as "Always ON" Note 4: For CDC ZONES, unused circuits should be selected as a shorting device. Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Page 37
For Releasing Application a battery rating of 18 Ah or greater is required, based on 24 hour Standby time and 5 minutes Alarm time (if greater than 18 Ah is needed, a PAB2- ENCL or external battery box will be needed). Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
3. Load Voltage Test—With full system alarm load, the voltage on a fully charged battery must not fall below 24.6V after one minute. Testing Interval 1. Semiannually—Perform the Load Voltage Test. 2. Annually—Perform the Charger Test and Discharge Test. Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...
Page 39
Model PAD-5 Battery Size Calculations THIS PAGE HAS BEEN LEFT INTENTIONALLY BLANK. Siemens Industry, Inc. A6V101030358_en--_c Smart Infrastructure...