1U Higher Voltage DC PDU (240V/380V)
Installation and Maintenance Guide

Advertisement

Table of Contents
loading

Summary of Contents for IBM System X High Voltage DC PDU

  • Page 1 1U Higher Voltage DC PDU (240V/380V) Installation and Maintenance Guide...
  • Page 3 1U Higher Voltage DC PDU (240V/380V) Installation and Maintenance Guide...
  • Page 4 Note: Before using this information and the product it supports, read the general information in “Notices” on page 33, the Warranty Information document, and the IBM Safety Information, the Supplemental Safety Notice L015, and the Environmental Notices and User Guide documents on the IBM Documentation CD.
  • Page 5: Table Of Contents

    . . 37 Installing the PDU in the side of a rack . Avis de conformité à la réglementation Installing the PDU in the side of an IBM Enterprise d'Industrie Canada . . 37 rack only . . 12 Australia and New Zealand Class A statement .
  • Page 6 1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
  • Page 7: Safety

    Ennen kuin asennat tämän tuotteen, lue turvaohjeet kohdasta Safety Information. Avant d'installer ce produit, lisez les consignes de sécurité. Vor der Installation dieses Produkts die Sicherheitshinweise lesen. Prima di installare questo prodotto, leggere le Informazioni sulla Sicurezza. © Copyright IBM Corp. 2014...
  • Page 8: Safety Statements

    Les sikkerhetsinformasjonen (Safety Information) før du installerer dette produktet. Antes de instalar este produto, leia as Informações sobre Segurança. Antes de instalar este producto, lea la información de seguridad. Läs säkerhetsinformationen innan du installerar den här produkten. Bu ürünü kurmadan önce güvenlik bilgilerini okuyun. Safety statements These statements provide the caution and danger information that is used in this documentation.
  • Page 9 Be sure to read all caution and danger statements in this documentation before you perform the procedures. Read any additional safety information that comes with your system or optional device before you install the device. Statement 1 DANGER Electrical current from power, telephone, and communication cables is hazardous.
  • Page 10 DANGER Overloading a branch circuit is potentially a fire hazard and a shock hazard under certain conditions. To avoid these hazards, ensure that your system electrical requirements do not exceed branch circuit protection requirements. Refer to the information that is provided with your device for electrical specifications.
  • Page 11: Chapter 1. Introduction

    If documentation updates are available, you can download them from the IBM web site. The PDU might have features that are not described in the...
  • Page 12: Notices And Statements In This Document

    Notices and statements in this document The caution and danger statements in this document are also in the multilingual Safety Information document, which is on the IBM Documentation CD. Each statement is numbered for reference to the corresponding statement in your language in the Safety Information document.
  • Page 13: Installation Requirements

    The PDU (with an attached power cord) v Two vertical-mounting brackets (for all racks) v Two short mounting brackets (for horizontal mounting in all racks; for vertical mounting only in IBM Enterprise racks) 1. One U is equal to 4.45 cm (1.75 in.) Chapter 1. Introduction...
  • Page 14: Features Of The Pdu

    v Two adjustable mounting rails (for horizontal mounting in all racks) Note: The following illustration shows the two components of one adjustable mounting rail. The adjustable mounting rail might come pre-assembled. v One 1U blank filler panel v Cable straps v Miscellaneous hardware kit (for attaching the mounting brackets to the PDU and installing the PDU in a rack) Note:...
  • Page 15: Front View

    You are responsible for making sure that only a Licensed Electrician installs or removes the PDU power cable from the DC Power source. All National and Local building code requirements must be met. IBM service technicians are not Licensed Electricians.
  • Page 16: Pdu Load Groups

    PDU load groups The PDU dc input power is distributed as a single load group, as described in the following illustration and table. Table 1. PDU load group Circuit breaker number Associated front outlet 1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
  • Page 17: Chapter 2. Installing The 1U Pdu Vertically In A Rack

    This chapter describes how to install the PDU vertically in a rack. To install the PDU in the side of an IBM Enterprise rack, see “Installing the PDU in the side of an IBM Enterprise rack only” on page 12. The PDU is a high-voltage dc device that must be connected to its input power source by a Licensed Electrician.
  • Page 18: Installing The Pdu In The Side Of A Rack

    Installing the PDU in the side of a rack About this task The mounting holes on the upper and lower side braces in a rack side compartment must be between 48.6 cm (19.1 in.) and 56.9 cm (22.4 in.) apart. If your rack has movable side braces, see the rack documentation for information about relocating the side braces if they are not already spaced for this installation.
  • Page 19 Attention: You must install the PDU with the front panel facing either the front or rear of the rack, either horizontally or vertically with the cable end at the bottom; do not install the PDU with the front panel facing up or down, or vertically with the cable end at the top.
  • Page 20 v The PDU must be installed with the input power cord toward the bottom end of the PDU. Review the documentation that comes with your rack for safety and cabling information. When you install the PDU in a rack, observe the following precautions: v Make sure that the room air temperature is below 40°C (104°F).
  • Page 21 You are responsible for making sure that only a Licensed Electrician installs or removes the PDU power cable from the DC Power source. All National and Local building code requirements must be met. IBM service technicians are not Licensed Electricians.
  • Page 22: Installing The Pdu In The Side Of An Ibm Enterprise Rack Only

    Installing the PDU in the side of an IBM Enterprise rack only About this task Attention: You must install the PDU with the front panel facing either the front or rear of the rack, either horizontally or vertically with the cable end at the bottom;...
  • Page 23 You must use clip nuts to install the mounting brackets. Clip nuts come with the PDU and are installed on the rack mounting flanges, as shown in the following illustration. To install the PDU in the 1U mounting space in the side of an IBM Enterprise rack, complete the following steps: Procedure 1.
  • Page 24 Short mounting bracket 2. Attach the brackets to the PDU with two M3 x 5 screws per bracket. Use the screws that come with the PDU. 3. Align the PDU with the opening in the side of the rack; then, while you hold the PDU in place, attach the brackets to the rack-mounting flanges with four clip nuts and four M6 screws that come with the PDU.
  • Page 25 You are responsible for making sure that only a Licensed Electrician installs or removes the PDU power cable from the DC Power source. All National and Local building code requirements must be met. IBM service technicians are not Licensed Electricians.
  • Page 26 1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
  • Page 27: Chapter 3. Installing The 1U Pdu Horizontally In A Rack

    Use cage nuts for racks with square holes, and use clip nuts for racks with round holes. If your rack requires cage nuts, use a cage-nut-insertion tool or a flat-blade screwdriver to install them. Cage nuts Clip nuts Cage nuts Statement 1 © Copyright IBM Corp. 2014...
  • Page 28 DANGER Electrical current from power, telephone, and communication cables is hazardous. To avoid a shock hazard: v Do not connect or disconnect any cables or perform installation, maintenance, or reconfiguration of this product during an electrical storm. v Connect all power cords to a properly wired and grounded electrical outlet. v Connect to properly wired outlets any equipment that will be attached to this product.
  • Page 29 Short mounting bracket 2. If the adjustable mounting rail is not assembled, complete the following steps to assemble it: a. Align the two parts of the adjustable mounting rail as shown in the following illustration. Adjustable mounting rail b. Secure the two adjustable mounting rail parts with three screws that come with the rack-mounting kit.
  • Page 30 Adjustable mounting rails 4. Orient the PDU so that the vent holes are facing up. Hold the PDU at a slight angle and carefully insert it into the 1U mounting space in the rack. Pushing in slightly on both of the adjustable mounting rails helps clear the rails from the rack flanges.
  • Page 31 You are responsible for making sure that only a Licensed Electrician installs or removes the PDU power cable from the DC Power source. All National and Local building code requirements must be met. IBM service technicians are not Licensed Electricians.
  • Page 32 1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
  • Page 33: Chapter 4. Cabling The Pdu

    Attention: You are responsible for making sure that only a Licensed Electrician installs or removes the PDU power cable from the DC Power source. All National and Local building code requirements must be met. IBM service technicians are not Licensed Electricians.
  • Page 34 1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
  • Page 35: Chapter 5. Customer Replaceable Unit Parts

    Replaceable components are of three types: v Tier 1 customer replaceable unit (CRU): Replacement of Tier 1 CRUs is your responsibility. If IBM installs a Tier 1 CRU at your request, you will be charged for the installation. v Tier 2 customer replaceable unit: You may install a Tier 2 CRU yourself or request IBM to install it, at no additional charge, under the type of warranty service that is designated for your server.
  • Page 36 1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
  • Page 37: Chapter 6. Pdu Specifications

    The high-voltage dc power cord that comes with the PDU must be connected to a properly wired and grounded high-voltage dc power source by a licensed electrician. See “Connecting input power” on page 23 for additional information. © Copyright IBM Corp. 2014...
  • Page 38 1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
  • Page 39: Appendix. Getting Help And Technical Assistance

    Appendix. Getting help and technical assistance If you need help, service, or technical assistance or just want more information about IBM products, you will find a wide variety of sources available from IBM to assist you. Use this information to obtain additional information about IBM and IBM products, determine what to do if you experience a problem with your IBM system or optional device, and determine whom to call for service, if it is necessary.
  • Page 40: Using The Documentation

    The troubleshooting information or the diagnostic programs might tell you that you need additional or updated device drivers or other software. IBM maintains pages on the World Wide Web where you can get the latest technical information and download device drivers and updates.
  • Page 41: Software Service And Support

    Software service and support Through IBM Support Line, you can get telephone assistance, for a fee, with usage, configuration, and software problems with your IBM products. For more information about Support Line and other IBM services, see http://www.ibm.com/services or see http://www.ibm.com/planetwide for support telephone numbers.
  • Page 42 1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
  • Page 43: Notices

    Consult your local IBM representative for information on the products and services currently available in your area. Any reference to an IBM product, program, or service is not intended to state or imply that only that IBM product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any IBM intellectual property right may be used instead.
  • Page 44: Important Notes

    (TBW). A device that has exceeded this limit might fail to respond to system-generated commands or might be incapable of being written to. IBM is not responsible for replacement of a device that has exceeded its maximum guaranteed number of program/erase cycles, as documented in the Official Published Specifications for the device.
  • Page 45: Particulate Contamination

    IBM makes no representations or warranties with respect to non-IBM products. Support (if any) for the non-IBM products is provided by the third party, not IBM. Some software might differ from its retail version (if available) and might not include user manuals or all program functionality.
  • Page 46: Documentation Format

    In the request, be sure to include the publication part number and title. When you send information to IBM, you grant IBM a nonexclusive right to use or distribute the information in any way it believes appropriate without incurring any obligation to you.
  • Page 47: Industry Canada Class A Emission Compliance Statement

    Klasse A ein. Um dieses sicherzustellen, sind die Geräte wie in den Handbüchern beschrieben zu installieren und zu betreiben. Des Weiteren dürfen auch nur von der IBM empfohlene Kabel angeschlossen werden. IBM übernimmt keine Verantwortung für die Einhaltung der Schutzanforderungen, wenn das Produkt ohne Zustimmung der IBM verändert bzw.
  • Page 48: Japan Vcci Class A Statement

    914-499-1900 Der verantwortliche Ansprechpartner des Herstellers in der EU ist: IBM Deutschland GmbH Technical Regulations, Abteilung M372 IBM-Allee 1, 71139 Ehningen, Germany Telephone: +49 7032 15 2941 Email: lugi@de.ibm.com Generelle Informationen: Das Gerät erfüllt die Schutzanforderungen nach EN 55024 und EN 55022 Klasse...
  • Page 49: Japan Electronics And Information Technology Industries Association (Jeita) Statement

    Japan Electronics and Information Technology Industries Association (JEITA) statement Japan Electronics and Information Technology Industries Association (JEITA) Confirmed Harmonics Guidelines with Modifications (products greater than 20 A per phase) Korea Communications Commission (KCC) statement This is electromagnetic wave compatibility equipment for business (Type A). Sellers and users need to pay attention to it.
  • Page 50 1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
  • Page 51: Index

    36 safety statements v, vi using 30 LED, green 5 sending diagnostic data to IBM 30 documentation CD 1 load groups, PDU 6 service and support DSA, sending data to IBM 30 before you call 29...
  • Page 52 1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
  • Page 54 Part Number: 16Y6043 Printed in USA (1P) P/N: 16Y6043...