1U Higher Voltage DC PDU (240V/380V) Installation and Maintenance Guide...
Page 3
1U Higher Voltage DC PDU (240V/380V) Installation and Maintenance Guide...
Page 4
Note: Before using this information and the product it supports, read the general information in “Notices” on page 33, the Warranty Information document, and the IBM Safety Information, the Supplemental Safety Notice L015, and the Environmental Notices and User Guide documents on the IBM Documentation CD.
. . 37 Installing the PDU in the side of a rack . Avis de conformité à la réglementation Installing the PDU in the side of an IBM Enterprise d'Industrie Canada . . 37 rack only . . 12 Australia and New Zealand Class A statement .
Page 6
1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
Les sikkerhetsinformasjonen (Safety Information) før du installerer dette produktet. Antes de instalar este produto, leia as Informações sobre Segurança. Antes de instalar este producto, lea la información de seguridad. Läs säkerhetsinformationen innan du installerar den här produkten. Bu ürünü kurmadan önce güvenlik bilgilerini okuyun. Safety statements These statements provide the caution and danger information that is used in this documentation.
Page 9
Be sure to read all caution and danger statements in this documentation before you perform the procedures. Read any additional safety information that comes with your system or optional device before you install the device. Statement 1 DANGER Electrical current from power, telephone, and communication cables is hazardous.
Page 10
DANGER Overloading a branch circuit is potentially a fire hazard and a shock hazard under certain conditions. To avoid these hazards, ensure that your system electrical requirements do not exceed branch circuit protection requirements. Refer to the information that is provided with your device for electrical specifications.
Notices and statements in this document The caution and danger statements in this document are also in the multilingual Safety Information document, which is on the IBM Documentation CD. Each statement is numbered for reference to the corresponding statement in your language in the Safety Information document.
The PDU (with an attached power cord) v Two vertical-mounting brackets (for all racks) v Two short mounting brackets (for horizontal mounting in all racks; for vertical mounting only in IBM Enterprise racks) 1. One U is equal to 4.45 cm (1.75 in.) Chapter 1. Introduction...
v Two adjustable mounting rails (for horizontal mounting in all racks) Note: The following illustration shows the two components of one adjustable mounting rail. The adjustable mounting rail might come pre-assembled. v One 1U blank filler panel v Cable straps v Miscellaneous hardware kit (for attaching the mounting brackets to the PDU and installing the PDU in a rack) Note:...
You are responsible for making sure that only a Licensed Electrician installs or removes the PDU power cable from the DC Power source. All National and Local building code requirements must be met. IBM service technicians are not Licensed Electricians.
PDU load groups The PDU dc input power is distributed as a single load group, as described in the following illustration and table. Table 1. PDU load group Circuit breaker number Associated front outlet 1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
This chapter describes how to install the PDU vertically in a rack. To install the PDU in the side of an IBM Enterprise rack, see “Installing the PDU in the side of an IBM Enterprise rack only” on page 12. The PDU is a high-voltage dc device that must be connected to its input power source by a Licensed Electrician.
Installing the PDU in the side of a rack About this task The mounting holes on the upper and lower side braces in a rack side compartment must be between 48.6 cm (19.1 in.) and 56.9 cm (22.4 in.) apart. If your rack has movable side braces, see the rack documentation for information about relocating the side braces if they are not already spaced for this installation.
Page 19
Attention: You must install the PDU with the front panel facing either the front or rear of the rack, either horizontally or vertically with the cable end at the bottom; do not install the PDU with the front panel facing up or down, or vertically with the cable end at the top.
Page 20
v The PDU must be installed with the input power cord toward the bottom end of the PDU. Review the documentation that comes with your rack for safety and cabling information. When you install the PDU in a rack, observe the following precautions: v Make sure that the room air temperature is below 40°C (104°F).
Page 21
You are responsible for making sure that only a Licensed Electrician installs or removes the PDU power cable from the DC Power source. All National and Local building code requirements must be met. IBM service technicians are not Licensed Electricians.
Installing the PDU in the side of an IBM Enterprise rack only About this task Attention: You must install the PDU with the front panel facing either the front or rear of the rack, either horizontally or vertically with the cable end at the bottom;...
Page 23
You must use clip nuts to install the mounting brackets. Clip nuts come with the PDU and are installed on the rack mounting flanges, as shown in the following illustration. To install the PDU in the 1U mounting space in the side of an IBM Enterprise rack, complete the following steps: Procedure 1.
Page 24
Short mounting bracket 2. Attach the brackets to the PDU with two M3 x 5 screws per bracket. Use the screws that come with the PDU. 3. Align the PDU with the opening in the side of the rack; then, while you hold the PDU in place, attach the brackets to the rack-mounting flanges with four clip nuts and four M6 screws that come with the PDU.
Page 25
You are responsible for making sure that only a Licensed Electrician installs or removes the PDU power cable from the DC Power source. All National and Local building code requirements must be met. IBM service technicians are not Licensed Electricians.
Page 26
1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
Page 28
DANGER Electrical current from power, telephone, and communication cables is hazardous. To avoid a shock hazard: v Do not connect or disconnect any cables or perform installation, maintenance, or reconfiguration of this product during an electrical storm. v Connect all power cords to a properly wired and grounded electrical outlet. v Connect to properly wired outlets any equipment that will be attached to this product.
Page 29
Short mounting bracket 2. If the adjustable mounting rail is not assembled, complete the following steps to assemble it: a. Align the two parts of the adjustable mounting rail as shown in the following illustration. Adjustable mounting rail b. Secure the two adjustable mounting rail parts with three screws that come with the rack-mounting kit.
Page 30
Adjustable mounting rails 4. Orient the PDU so that the vent holes are facing up. Hold the PDU at a slight angle and carefully insert it into the 1U mounting space in the rack. Pushing in slightly on both of the adjustable mounting rails helps clear the rails from the rack flanges.
Page 31
You are responsible for making sure that only a Licensed Electrician installs or removes the PDU power cable from the DC Power source. All National and Local building code requirements must be met. IBM service technicians are not Licensed Electricians.
Page 32
1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
Attention: You are responsible for making sure that only a Licensed Electrician installs or removes the PDU power cable from the DC Power source. All National and Local building code requirements must be met. IBM service technicians are not Licensed Electricians.
Page 34
1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
Replaceable components are of three types: v Tier 1 customer replaceable unit (CRU): Replacement of Tier 1 CRUs is your responsibility. If IBM installs a Tier 1 CRU at your request, you will be charged for the installation. v Tier 2 customer replaceable unit: You may install a Tier 2 CRU yourself or request IBM to install it, at no additional charge, under the type of warranty service that is designated for your server.
Page 36
1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
Appendix. Getting help and technical assistance If you need help, service, or technical assistance or just want more information about IBM products, you will find a wide variety of sources available from IBM to assist you. Use this information to obtain additional information about IBM and IBM products, determine what to do if you experience a problem with your IBM system or optional device, and determine whom to call for service, if it is necessary.
The troubleshooting information or the diagnostic programs might tell you that you need additional or updated device drivers or other software. IBM maintains pages on the World Wide Web where you can get the latest technical information and download device drivers and updates.
Software service and support Through IBM Support Line, you can get telephone assistance, for a fee, with usage, configuration, and software problems with your IBM products. For more information about Support Line and other IBM services, see http://www.ibm.com/services or see http://www.ibm.com/planetwide for support telephone numbers.
Page 42
1U Higher Voltage DC PDU (240V/380V): Installation and Maintenance Guide...
Consult your local IBM representative for information on the products and services currently available in your area. Any reference to an IBM product, program, or service is not intended to state or imply that only that IBM product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any IBM intellectual property right may be used instead.
(TBW). A device that has exceeded this limit might fail to respond to system-generated commands or might be incapable of being written to. IBM is not responsible for replacement of a device that has exceeded its maximum guaranteed number of program/erase cycles, as documented in the Official Published Specifications for the device.
IBM makes no representations or warranties with respect to non-IBM products. Support (if any) for the non-IBM products is provided by the third party, not IBM. Some software might differ from its retail version (if available) and might not include user manuals or all program functionality.
In the request, be sure to include the publication part number and title. When you send information to IBM, you grant IBM a nonexclusive right to use or distribute the information in any way it believes appropriate without incurring any obligation to you.
Klasse A ein. Um dieses sicherzustellen, sind die Geräte wie in den Handbüchern beschrieben zu installieren und zu betreiben. Des Weiteren dürfen auch nur von der IBM empfohlene Kabel angeschlossen werden. IBM übernimmt keine Verantwortung für die Einhaltung der Schutzanforderungen, wenn das Produkt ohne Zustimmung der IBM verändert bzw.
914-499-1900 Der verantwortliche Ansprechpartner des Herstellers in der EU ist: IBM Deutschland GmbH Technical Regulations, Abteilung M372 IBM-Allee 1, 71139 Ehningen, Germany Telephone: +49 7032 15 2941 Email: lugi@de.ibm.com Generelle Informationen: Das Gerät erfüllt die Schutzanforderungen nach EN 55024 und EN 55022 Klasse...
Japan Electronics and Information Technology Industries Association (JEITA) statement Japan Electronics and Information Technology Industries Association (JEITA) Confirmed Harmonics Guidelines with Modifications (products greater than 20 A per phase) Korea Communications Commission (KCC) statement This is electromagnetic wave compatibility equipment for business (Type A). Sellers and users need to pay attention to it.