The TZIDC, TZIDC-110, TZIDC-120 is an electronically Additional documentation on TZIDC, TZIDC-110, TZIDC-120 configurable positioner with communication TZIDC-120 is available for download free of charge at capabilities designed for mounting on pneumatic www.abb.com/positioners. linear or rotary actuators. Alternatively simply scan this code:...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E Table of contents Change from one to two columns Connection on the device ............. 38 Safety ................3 Conductor cross-section ..........39 General information and instructions ........3 ...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E 1 Safety General information and instructions Warnings These instructions are an important part of the product and The warnings in these instructions are structured as follows: must be retained for future reference.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 1 Safety Manufacturer’s address Intended use ABB Automation Products GmbH Positioning of pneumatically controlled actuators; designed for Measurement & Analytics mounting on linear and rotary actuators. Schillerstr. 72 The device is designed for use exclusively within the stated 32425 Minden values on the name plate and in the data sheet.
Commissioning, Installation Notes for operation The ABB positioner has to be mounted in a major system. • The positioner must be integrated in the local potential Depending on the degrees of IP-protection, an interval for equalization system.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 2 Use in potentially explosive atmospheres Maintenance, repair Definition of terms according to IEC 60079-17: • Maintenance and exchange work may be conducted by Maintenance qualified specialists only, i.e., qualified personnel in Defines a combination of actions performed to maintain or accordance with TRBS 1203 or similar.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E Preconditions for safe operation of the positioner Cable gland DANGER Limited temperature range of the M20 × 1.5 plastic cable gland Risk of explosion due to hot parts for explosion protection variants.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 2 Use in potentially explosive atmospheres TZIDC – Ex relevant specification Note Electrical Data The values indicated here are taken from the respective In intrinsically safe types of protection Ex ib IIC / Ex ia IIC or certificates.
• When used with gases from group IIA and a temperature Type ’n’ type of protection class of T1 for power supply, the TZIDC positioner may only Device class II 3 G be used outdoors or inside sufficiently ventilated buildings.
T6, the maximum permissible ambient temperature range is −40 to 35 °C. Electrical Data Electric data for TZIDC with Ex ia IIC or Ex ib IIC marking. In ‘intrinsic safety Ex ib IIC / Ex ia IIC’ type of protection, only for connection to a certified intrinsically safe circuit.
Page 11
Note: It is considered very Electric data for TZIDC with Ex nA IIC T6 or T4 Gc marking unlikely that a potentially hazardous atmosphere would be present in zone 2 at the same time that installation or...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 2 Use in potentially explosive atmospheres … TZIDC – Ex relevant specification FM / CSA Note • The “x” in P/N denotes minor mechanical variations or CSA International optional features.
Page 13
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E Note CSA certification record • The ‘x’ in P/N denotes minor mechanical variations or optional features. Certificate • Local communication interface LCI shall not be used in Certificate 1649904 (LR 20312) hazardous location.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 2 Use in potentially explosive atmospheres TZIDC-110 – Ex relevant specification Note ATEX – ‘Ex n’ type of protection The values indicated here are taken from the respective Ex marking certificates.
−40 to 50 °C Electrical Data TZIDC-110 for ia / ib / ic with Ex i IIC T6 or T4 Gb marking With the intrinsically safe Ex i IIC type of protection, only for connection to a certified FISCO power supply unit, a barrier or a...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 2 Use in potentially explosive atmospheres … TZIDC-110 – Ex relevant specification TZIDC-110 with Ex nA IIC T6 or T4 Gc marking FM / CSA CSA International Current circuit (terminal)
Page 17
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E CSA certification record FM approvals TZIDC-110 Positioner, Model V18346-a032b2cd0e Certificate IS/I,II,III/1/ABCDEFG/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C-901265 Entity, FISCO Certificate 1649904 (LR 20312) Class 2258 04 PROCESS CONTROL EQUIPMENT –...
Page 18
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 2 Use in potentially explosive atmospheres … TZIDC-110 – Ex relevant specification Equipment Ratings: TZIDC-110 Intrinsically safe, Entity and FISCO, for Class I, II and III, Division 1, Applicable Groups A, B, C, D, E, F, G; non-Incendive for Class I,...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E TZIDC-120 – Ex relevant specification Note ATEX – ‘Ex n’ type of protection The values indicated here are taken from the respective Ex marking certificates. Always observe the specifications and supplements in the explosion protection certificates.
−40 to 50 °C Electrical Data TZIDC-120 for ia / ib / ic with Ex i IIC T6 or T4 Gb marking With the intrinsically safe Ex i IIC type of protection, only for connection to a certified FISCO power supply unit, a barrier or a...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E TZIDC-120 with Ex nA IIC T6 or T4 Gc marking FM / CSA CSA International Current circuit (terminal) System bus, computer interfaces Signal circuit U = 9 to 32 V DC Certificate (+11 / −12)
Page 22
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 2 Use in potentially explosive atmospheres … TZIDC-120 – Ex relevant specification CSA certification record FM approvals TZIDC-120 Positioner, Model V18347-a042b2cd0e Certificate IS/I,II,III/1/ABCDEFG/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C-901265 Entity, FISCO...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E Change from two to one column 3 Product identification Name plate 1 Full type designation 6 Supply air pressure 2 Software revision 7 Input 3 Serial number 8 Output 4 NL number...
Transporting the device purposes: All devices delivered to ABB must be free from any hazardous Observe the following instructions: materials (acids, alkalis, solvents, etc.). •...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E 5 Installation Safety instructions CAUTION Risk of injury due to incorrect parameter values! Incorrect parameter values can cause the valve to move unexpectedly. This can lead to process failures and result in injuries.
Remote Sensor on page 40. M10904 Note 1 TZIDC Control Unit 5 Compressed air supply To connect the TZIDC Remote Sensor, a cable with the following 2 Connection cable 6 Set point signal specifications needs to be used: 3 TZIDC Remote Sensor 7 Remote position sensor ²...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E Mechanical mounting General Operating range of rotary actuators: The usable span is 90°, which must be entirely within the measuring range, but does not necessarily need to run symmetrically to the longitudinal axis.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 5 Installation … Mechanical mounting Mounting on linear actuators For mounting on a linear actuator in accordance with DIN / IEC 534 (lateral mounting as per NAMUR), the following attachment...
Page 29
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E 5. Secure the mount bracket with screws and washers Note using the relevant tap holes on the positioner housing. Adjust the height of the positioner on the cast iron yoke or ...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 5 Installation … Mechanical mounting Position of actuator bolt Mounting on rotary actuator The actuator bolt for moving the potentiometer lever can be For mounting on part-turn actuators in accordance with mounted permanently on the lever itself or on the valve stem.
Page 31
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E M10421-01 1 Attachment bracket M10424-01 Figure 15: Screwing the attachment bracket onto the positioner Figure 14: Mounting the adapter on the positioner 1. Determine the mounting position (parallel to actuator or at 90° angle) 2....
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E 6 Electrical connections Safety instructions DANGER Risk of explosion for devices with local communication interface (LCI) A local communication interface (LCI) may not be operated in hazardous areas. • Never use the local communication interface (LCI) on the...
It is not position sensor) possible to combine both variants. For the version TZIDC Control Unit with TZIDC Remote Sensor, the limit switches are located in the TZIDC Remote Sensor. Change from two to one column...
Figure 18: TZIDC Remote Sensor Electrical Connection Change from one to two columns Connections for inputs and outputs Note The TZIDC Remote Sensor can be fitted either with proximity Terminal Function / comments switches or microswitches as limit switches. It is not possible to...
Digital feedback Limit 1 with microswitch (optional) 51 / 52 / 53 Digital feedback Limit 2 with microswitch (optional) Note The TZIDC-1x0, TZIDC-210 or TZIDC-220 can be fitted either with proximity switches or microswitches as limit switches. It is not possible to combine both variants.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 6 Electrical connections Electrical data for inputs and outputs Note Digital input When using the device in potentially explosive atmospheres, Only for devices with HART® Communication. note the additional connection data in Use in potentially...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E Option modules Assembly kits for digital feedback Module for analog feedback AO* Two proximity switches or microswitches for independent Only for devices with HART® Communication. signaling of the actuator position, switching points are Without any signal from the positioner (e.g.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E hange from two to one column … 6 Electrical connections Connection on the device M 20 mm / NPT 1/2" M10901 1 Cable gland 4 Terminal attachment kit for digital feedback...
If necessary, the following options can be installed if required: • Optical position indicator • If the TZIDC Control Unit is fastened so that it is it non- • Mechanical feedback contacts designed as proximity conductive, the housing must be grounded (TZIDC Control switches or microswitches.
TZIDC / TZIDC Control Unit terminal assignment on page 33. • If the TZIDC Control Unit is fastened such that it is it non- conductive, the housing must be grounded (TZIDC Control Unit and remote position sensor housing with the same electric potential);...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E 7 Pneumatic Connections Connection on the device Note The positioner must only be supplied with instrument air that is free of oil, water, and dust. The purity and oil content must meet the requirements of Class 3 in accordance with DIN/ISO 8573-1.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E 8 Commissioning Air supply Note The electrical power supply and supply air pressure data Instrument air* indicated on the name plate must be complied with during commissioning. Purity Maximum particle size: 5 μm...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 8 Commissioning TZIDC-110 / TZIDC-120 … TZIDC Commissioning the positioner: Operating modes 1. Open the pneumatic power supply. Selection from the operating level 2. Connect fieldbus or power supply to the bus connections.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E Setting the bus address Request information When the device is in bus operation, the information listed below 1. Switching to the configuration level: can be called up. • Press and hold down and simultaneously, Press the following control buttons to access this information: •...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 8 Commissioning Standard automatic adjustment … TZIDC-110 / TZIDC-120 Operating modes Note Standard Auto Adjust does not always result in optimum control Selection from the operating level: conditions. 1. Press and hold down MODE.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E Sample parameters 4. Changing parameter settings: ‘Change the zero position of the LCD display from clockwise • Quickly press and release to select CTCLOCKW. (CLOCKW) to counter-clockwise limit stop (CTCLOCKW)’...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 8 Commissioning … Sample parameters Setting the mechanical limit switch with proximity Setting the mechanical limit switch with 24 V switches microswitches 1. Loosen the screws for the housing cover and remove it.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E 9 Operation Safety instructions Value display with unit CAUTION This 7-segment display with four digits indicates parameter Risk of injury due to incorrect parameter values! values or parameter reference numbers. For values, the physical Incorrect parameter values can cause the valve to move unit (°C, %, mA) is also displayed.
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 9 Operation 10 Maintenance … Parameterization of the device The positioner does not require any maintenance if it is used as intended under normal operating conditions. Operating button functions Note...
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E 13 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
Page 58
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E … 13 Appendix … FM installation drawing No. 901265...
Page 59
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E Change from one to two columns Trademarks HART is a registered trademark of FieldComm Group, Austin, Texas, USA FOUNDATION Fieldbus is a registered trademark of FieldComm Group, Austin, Texas, USA. PROFIBUS and PROFIBUS PA are registered trademarks of PROFIBUS &...
Page 60
We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.