The HP97OA, B and HP972B Pneumatic Humidistats
(Humidistats) are nylon element, proportional, two-pipe,
devices used to control humidity in HVAC systems.
The HP970A and B Pneumatic Humidistats control pneumatic
valve and damper actuators in air conditioning systems
requiring humidification and/or dehumidification.
The HP972B is used in systems requiring a reset of relative
humidity as a function of outdoor air temperature, wide
throttling range, or replacement of existing one-pipe
humidistats" A special
model,
necessary adapter fittings to convert older models or
competitors' humidistats" Figure 1 shows a typical HP970A,
Copyright 0 1989 Honeywell Inc. 0 All Rights Reserved
HP970A, B and HP972B
Pneumatic Humidistats
Fig. 1. Typical HP970A, 6 or HP972B Humidistat
Two-Pipe Hookup.
RESTRICTION
(BLUE)
Fig. 2. Typical HP972B Humidistat One-Pipe Hookup.
SPECIFICATIONS
Action:
Means of Adjustment:
External knob with internally adjustable setpoint locking stops
for minimum and maximum settings
Maximum Safe Pressure:
25 psi
Supply Air Pressure:
13 to 21 psi (90 to 145 kPa)
18 psi (124 kPa) nominal
Branchline Pressure Indication:
Self-sealing gage tap under the cover
Honeywell
SERVICE DATA
MB
VALVE
N.C.
SUPPLY
HUMIDIFIER
VALVE
N.C.
SUPPLY
C3226
75-7195