Sensitivity Mode - Honeywell Morley-IAS ZX Series Commissioning Manual

Fire alarm control panels
Table of Contents

Advertisement

MORLEY-IAS
---------------------------------------------
Stage 1 time
Press 'Yes' to accept and step on. Press 'No' to change and then enter the required end time using
the number buttons.
---------------------------------------------
Stage 2 time
( Key in number, then press "Enter"
In the above example, the internal warning buzzer will sound and the sensor location will be shown on
the display immediately a fire is detected. If this Stage 1 alarm is not acknowledged at the panel by
pressing the 'ACCEPT' button within the 30 seconds a full alarm will be generated.
Pressing the 'ACCEPT' button within this period will cause stage 2 to be entered.
The stage '2' timer will start counting down as soon the panel detects an alarm signal (i.e. starts at the
same time as stage 1). Setting the stage 2 time for a longer period than stage 1 provides the user with
the opportunity to investigate the cause of the alarm and take appropriate action. If the panel is not
reset by the time stage 2 has expired, or if a new fire alarm signal is detected during stage 2, a full fire
alarm will be raised.
Finally, the display prompts the zones that are to be used in delayed mode.
---------------------------------------------
Zone[001] to [012] may use day mode
The above example shows that zones 1 to 12 inclusive will not use the day mode times and hence, a
fire alarm will be generated immediately any sensor in these zones detects a high sensor reading.
To change the zones, use the '<' or '>' to select the appropriate field. Use the number keys to change
the zone numbers. Use the Change key to toggle between [TRUE] and [FALSE].
The user can choose to enable and disable the delayed day mode at level 2. This is as
described in the User Manual.
EN54-2 7.11c
EN54
Delays to
!
Outputs.

11.3 Sensitivity Mode

The commissioning engineer can adjust the sensitivity of both temperature and smoke detectors by
adjusting the threshold at which pre-alarm and fire alarm signals are generated.
Page 44
[ Panel in Commissioning mode ]
= 30 seconds
[ Panel in Commissioning mode ]
= 120 seconds
[ Panel in Commissioning mode ]
Note that for compliance with EN54 the maximum total delay is 10
minutes. Therefore, the stage 2 delay plus any sounder delay must
not exceed this time.
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
OK ?
OK ?
)
[FALSE]
Commissioning Manual