5.2.1 Auto Learn
•
This facility saves considerable time and effort when installing a system, or when changing sensor
configuration. It allows the system to learn for itself what devices have been installed on a particular loop.
•
Press '3' from the CONFIGURE menu to select 'Auto Learn'. The display will respond with the message:
----------------------------------------------
Auto Learn finds ALL device addresses
and types on loop 1. Shall I do this ?
5.2.1.1
Full Auto Learn
•
To proceed with 'Auto Learn', press the 'Yes' key. The system will confirm your command with the
message 'Program running' on the display. It may take several minutes to learn a complete loop. Each
possible sensor address is checked to see if any detector is installed at that address. If a detector has been
installed, the panel determines the type of the detector. If more than one detector is located at a single
address, or the detector type code is invalid, a warning message will appear on the display.
•
Do not press any key until the display changes from the 'program running' message.
•
Once the system has finished learning, it will respond with a display giving a summary of the detectors
found on the loop. For example.
---------------------------------------------
Ion
•
This display should be checked, against the installation sheets, to ensure that the system has found
the correct number of devices.
•
Pressing any key then restores the display to the normal commissioning menu.
•
The Auto Learn sequence should be repeated for each loop on the system. It can be used as many times
as required and does not affect the text description used to describe the location of each sensor.
Always verify that the system has found all devices correctly. Use the 'Devices' option to
obtain detailed information on the device type and to see the address of each device
found on the loop.
5.2.1.2
Quick Status Check
•
To perform a 'Quick Status Check', press the 'No' key instead when prompted to perform the Auto
Learn. The system will respond immediately with a display giving a summary of the detectors already
programmed for this loop. For example.
---------------------------------------------
Ion
37
Page 16
[ Panel in Commissioning mode ]
[ Panel in Commissioning mode ]
Opto
Temp Sounder MCP Zone-Mon Other
37
24
2
[ Panel in Commissioning mode ]
Opto
Temp Sounder MCP Zone-Mon Other
24
2
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
8
14
2
8
14
2
3
3
Commissioning Manual