hit counter script
ABB ESP M1R Installation Instructions Manual
ABB ESP M1R Installation Instructions Manual

ABB ESP M1R Installation Instructions Manual

Mains protectors

Advertisement

I N STA L L ATION I N ST RU CT I ON S
ESP M1/M1R
mains protectors
ESP 120 M1, ESP 208 M1, ESP 240 M1,
ESP 415 M1, ESP 277 M1, ESP 480 M1
and M1R variants

Advertisement

Table of Contents
loading

Summary of Contents for ABB ESP M1R

  • Page 1 — I N STA L L ATION I N ST RU CT I ON S ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants...
  • Page 2: Table Of Contents

    Contents Key points of installation Before installation Installation Installation check Neutral-earth warning light Status indication Remote indication Maintenance Application Notes Remote display drilling template...
  • Page 3 — IN TRODUC TIO N This document explains how to install Furse Electronic Systems Protectors for three phase mains power supplies: Single phase ESP 120 M1, Three phase ESP 208 M1 and ESP 208 M1R, Single phase ESP 240 M1, Three phase ESP 415 M1 and ESP 415 M1R, Single phase ESP 277 M1, Three phase ESP 480 M1 and ESP 480 M1R...
  • Page 4 1.4 Connect to phase(s), neutral and earth. NOTE: Units must have a neutral connection (see 3.4). Safety note: 1.5 Units installed at power distribution Safety note: boards can be installed either: on the load side of the incoming Warning! Installation by person with Warning! Installation by person with electrotechnical isolator electrotechnical expertise only.
  • Page 5: Key Points Of Installation

    Key points of installation 1.1 Install protectors very close to the power supply to be protected, either within the distribution panel or directly alongside it. 1.2 Mount units within a panel or WBX enclosure. 1.3 Units are installed in parallel. 1.4 Connect to phases, neutral and earth.
  • Page 6 1.8 Connecting leads should be 10 mm multi stranded cable. 1.9 Keep the connecting leads as short as possible and ideally less than 25 cm (10 inches) in length. This may be better achieved with the equivalent M1R with remote display mounting flexibility.
  • Page 7: Before Installation

    Before installation 2.1 Check that the voltage between neutral and earth does not exceed 10 volts. If this voltage does exceed 10 volts, the installation is unsafe. Find and rectify the cause of this fault before proceeding. 2.2 Make sure that the supply voltage is suitable for the unit. Supply Rated Unit Voltage Voltage (VRMS)
  • Page 8: Installation

    Figure 1: ESP 415 M1 installed inside a power distribution panel. Installation 3.1 Location Protectors need to be installed very close to the power supply to be protected. Usually the protector will be installed at a power distribution panel either inside it (Figure 1) or right next to it (Figure 2).
  • Page 9 Figure 2: ESP 415 M1 installed next to a power distribution panel. Alternatively, for three phase units, a remote display M1R option is available. These units can be installed within the power distribution panel with the remote display mounted on the front of the panel. Installation instructions for mains wire-in protectors | 3/2...
  • Page 10 Volt free contact 240 M1 STATUS INDICATION Figure 3: Parallel GREEN FULL PROTECTION GREEN & RED REDUCED PROTECTION (replace unit) connection for single NO PROTECTION WARNING If lit / flashing disconnect phase supplies. unit & check Neutral to Earth supply voltage ELECTRONIC SYSTEMS PROTECTION Let-through voltage...
  • Page 11 Figure 4: Parallel connection for three phase star (4 wire and earth) supplies. From supply load 3.3 Parallel connection ESP mains wire-in protectors are connected in parallel with the supply to be protected. See Figure 3. The connecting leads do not carry the load current of the supply, only the current associated with suppressing the transient overvoltage.
  • Page 12 Figure 5: ESP unit mounted within a distribution board connected to the incoming supply on the load outgoing outgoing outgoing outgoing outgoing outgoing side (ie downstream) of the ways ways ways ways ways ways isolator. (Note the additional earth bond to the metalwork of the distribution board.
  • Page 13 ESP unit. Consequently, the supply’s phase to earth voltage must be checked before installing the ESP unit. We recommend that you consult ABB Furse ESP before installing ESP units on delta supplies. 3.5 Connection point...
  • Page 14 outgoing outgoing outgoing outgoing outgoing ways ways ways ways ways Distribution Board Alternative first outgoing ESP M1 protector, sited in WBX enclosure, connected to first outgoing way Load side Load side Load side Load side Load side Isolator Isolator Isolator Isolator Isolator Main...
  • Page 15 Figure 7: Outgoing ways internal to the building Connection for supplies continuing external to the building. Incoming supply Outgoing way Outgoing way internal to the to external load building On small, compact, metal cased distribution boards, (such as small MCB boards) the first way is preferable, although any outgoing way is suitable.
  • Page 16 (b) Protecting supplies going out of the building The connection methods 3.5a (i to iii) are not suitable for protecting a power distribution board which provides a supply to outside the building - either to a separate building or some other external load (eg site lighting). To protect the equipment inside the building, from transient overvoltages entering the board on the outgoing feed, protection should be installed close to the...
  • Page 17 Figure 10: Busbar mounted HRC fuse at the end of the Volt free contact Volt free contact live connecting lead. 240 M1 240 M1 STATUS INDICATION STATUS INDICATION GREEN FULL PROTECTION GREEN FULL PROTECTION GREEN & RED REDUCED PROTECTION GREEN & RED REDUCED PROTECTION (replace unit) (replace unit)
  • Page 18 connecting leads in the event of a short circuit. The fuse to the ESP unit (F SPD ) should be lower than the upstream supply fuse F S by a sufficient enough factor to ensure fuse discrimination. As a general guide a factor of at least 2 could be used (F SPD ≤...
  • Page 19 3.8 Size of connecting leads The connecting leads between the terminals of the ESP unit and the power supply, should be 10 mm multi stranded conductor (copper). If required, the terminals on the ESP unit will accept connecting leads of up to 25 3.9 Length of connecting leads The connecting leads should be kept as short as possible and ideally should not exceed 25 cm (10 inches) from the...
  • Page 20 The display is connected to the protector via the supplied 1 m cable (2 m or 4 m cable optional - contact ABB Furse). The remote display drilling template can be found at the back of these instructions. Connecting leads up to 50 cm (20 inches) can be used when:...
  • Page 21 (ii) alternatively, if only one conductor needs to be longer than 25 cm then use a pair of separated (as above) conductors to make that connection. See Figure 6. (iii) for metal distribution boards, if only the earth connection needs to be longer than 25 cm, the following procedure is suggested (See Figure 5): (a) using 6 mm cable make one connection from the ESP...
  • Page 22: Installation Check

    Installation check The ESP unit should now be correctly installed. Switch the power supply on. Check that a green LED per phase and neutral is lit. See Figure 12. The unit is now fully operational. Watch the WARNING light for 30 seconds. If it is flashing or lit there is a problem with your installation (see opposite).
  • Page 23: Neutral-Earth Warning Light

    Neutral-earth warning light If the WARNING light is illuminated there is an excessive voltage present between neutral and earth. The WARNING light should never be illuminated. (a) Illumination at time of installation If the WARNING light flashes as soon as the mains supply to the ESP unit is turned on, one of the phase/live cables may have been connected to neutral and the neutral to phase/live.
  • Page 24: Status Indication

    The ESP protector should not be reconnected until the cause of the fault has been identified and rectified. Note: The ESP unit may have suffered damage - check the status indication (see section 6). Status indication ESP units give a continuous visual display of their status. They have a two colour indicator light, for each phase and neutral: Green only...
  • Page 25: Remote Indication

    Remote indication A remote indication of the reduced protection state is provided for linking the protector to a building management system, remote telemetry, PLC or directly to an indication light or buzzer. The unit has both a normally open and a normally closed volt free contact.
  • Page 26 The ESP units remote indication is rated at 1 Amp, 250 V Note: For reliable contact operation, the minimum permissible load is 10 mA, 5 V DC. Unit Reduced or Healthy No protection OPEN CLOSED Power Present CLOSED OPEN CLOSED CLOSED Power Absent OPEN...
  • Page 27: Maintenance

    Consider the protection of the environment! Used electrical and electronic equipment must NOT be disposed of with domestic waste. The device contains valuable raw materials which can be recycled. Therefore, contact ABB for disposal of this equipment. Installation instructions for mains wire-in protectors | 8/1...
  • Page 28: Application Notes

    Application notes 9.1 ESP coordination ESP M1/M1R units are designed to fully coordinate with ESP units of equivalent system voltage on the same installation. For example the ESP 415 M2 located at the main distribution panel would coordinate effectively with the ESP 415 M1 unit typically located at sub-distribution panels.
  • Page 29 Where ESP units are installed after (or downstream) of RCDs, special transient hardened RCDs (type ’S’) should be used (e.g. ABB F 200 A selective type series). 9.3 Insulation tests (flash testing) The ESP unit should be fully disconnected from the circuit before testing.
  • Page 30 If possible the two units should be connected to the power supply a short distance apart either: (a) onto the first two outgoing ways (b) up to a metre apart on the incoming power supply 9.5 Installing three phase units on single phase supplies If a three phase unit is installed on a single phase mains supply (or a supply in which one or two phases are not in use), the ESP units spare (or unused) live terminal(s)
  • Page 31: Remote Display Drilling Template

    55.0mm Remote display drilling template 35.5mm...
  • Page 32 +44 (0) 115 964 3700 Fax: +44 (0) 115 986 0071 National Sales Tel: +44 (0) 333 999 9900 National Sales Fax: +44 (0) 333 999 9901 E-Mail: enquiry@furse.com www.furse.com © Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice.

Table of Contents