SERIAL PRINTER
POWER
PARALLEL PRINTER
TB1
4
3
2
*
1
*
MMB-1/-2:
120 OHMS, 1/4W, 5%
P/N 140-820150
MMB-3:
RES EOL ASSEMBLY
120 OHMS, 1/4W, 5%
P/N 140-049099
Notes:
1. Use a minimum wire gauge of 22 AWG.
2. Use a maximum of 80 ohms per pair of wires for
the network connections.
3. Use shielded twisted pair for network connections.
4. Terminate the shield ONLY at the MMB
enclosure.
5. For MMB-1/-2 Style 4, use a 120 Ohm, 1/4W,
5% EOLR, P/N 140-820150, in positions 1 and
2 on plug J8.
For MMB-3 Style 4, use Res EOL Assembly, 120
Ohm, 1/4W, 5%, P/N 140-049099.
SUPERVISION
OPTIONAL
NOTE:
INSTALL EITHER A SERIAL OR
PARALLEL PRINTER. ONLY ONE
PRINTER CAN BE CONNECTED
TO THE SYSTEM.
SUPERVISED BY DEFAULT
For RCC-3/3 F Installation Only
MMB
Figure 4
RCC-3/3F Style 4 Wiring
4
1
BACKLIGHT
J3
13
1
14
2
12
LCD
J2
J12
+
1
+24VDC
-24VDC
CHASSIS
GND
For 24 VDC connections, refer to the following terminations:
MMB
PSR-1
PLM-35 (Used with PS-35)
ALARMSAF (Model BN4-002-UL)
PAD-3
6. This configuration is power limited to NFPA
70 according to NEC 760.
7. The RCC-3/-3C/-3F/-3FC MUST have an
earth ground connected to the chassis. Wire
shield or conduit is not an acceptable ground.
Use any available unused, unpainted stud on
the MMB for chassis grounding.
8. Refer to Wiring Specification for MXL, MXL-IQ
and MXLV Systems, P/N 315-092772 revision
6 or higher, for additional wiring information.
9. Maximum voltage: 8V peak to peak
Maximum current: 150mA
8
1
1
KEYBOARD
LEDS
J1
J5
J4
J8
NETWORK
TO OPTIONAL
-
2
MODULES
1
2
3
4
5
1
8
P/N 140-820150
120 OHMS, 1/4W, 5%
TB5, 9-12
TB3, 3-6
TB1, 1-2
DC1
TB2, 18-19