The tasks performed to set up the D400 for operation are:
Task 1: Connect to the D400
Task 2: Create User Accounts
Task 3: Change the Root Password
Task 4: Set the IP Address
Task 5: Create a Supervisor Password
Task 6: Access the D400 HMI
In the following procedures, the term "enter" indicates that the menu item number is typed in and then the Enter key is pressed.
Task 1: Connect to the D400
1.
Connect the supplied null modem cable (GE part number 977-0529) to your computer serial communications port, and
to the D400 front panel serial communications port.
2.
Start a terminal emulation application. For example, Tera Term.
3.
From the Windows start menu, select All Programs > Tera Term folder > Tera Term.
4.
Click the Serial option, and click OK.
5.
On the Tera Term VT window, select the Setup menu > Serial port... command
6.
Select the communications settings and click OK:
Port: Select the appropriate communication port (for example COM3)
Baud rate: 19200
Data: 8 bit
Parity: none
Stop: 1 bit
Flow control: none
7.
On the Tera Term VT window, select the Setup menu > Terminal... command.
8.
Select the terminal setting: Terminal: VT100, and click OK.
9.
At the D400 login prompt, type the default username root and default password geroot.
Task 2: Create User Accounts
Since you cannot use the root user account to access the D400 remotely, you must create administrator-level user accounts for
this purpose. This must be done first when you connect to the D400 front serial communications port and run a terminal session.
To create a new administrator-level user account:
1.
At the D400#>> prompt, type d400cfg and press Enter.
2.
Enter 1. Configure Authentication.
3.
Enter 6. Administrator Group Users.
4.
Respond to the on-screen prompts as required to create a new administrator-level user. You may now use this user
account to access the D400 remotely through TELNET or SSH.

Quick Start Guide

GE Information

Advertisement

loading

Summary of Contents for GE D400

  • Page 1: Quick Start Guide

    Since you cannot use the root user account to access the D400 remotely, you must create administrator-level user accounts for this purpose. This must be done first when you connect to the D400 front serial communications port and run a terminal session.
  • Page 2 Result: The Log-In screen appears. Enter your user name as supervisor and the newly created password. Click Log In. Result: The D400 HMI (Human Machine Interface) appears. Note: Multiple D400 HMI users can be created. Each user can be assigned with different access levels.
  • Page 3: Product Support

    Contact Customer Service The GE Digital Energy Customer Service Center is open 24 hours a day, seven days a week for you to talk directly to a GE representative. I In the U.S. and Canada, call toll-free: 1 800 547 8629...