Siemens SINAMICS G130 Operating Instructions Manual

Siemens SINAMICS G130 Operating Instructions Manual

Cabinet design and emc
Hide thumbs Also See for SINAMICS G130:

Advertisement

SINAMICS G130
Cabinet design and EMC
Operating Instructions · 03/2013
SINAMICS
s

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SINAMICS G130

  • Page 1 SINAMICS G130 Cabinet design and EMC Operating Instructions · 03/2013 SINAMICS...
  • Page 3 ___________________ Cabinet design and EMC Safety information ___________________ General ___________________ Basic information about EMC SINAMICS EMC-compliant design and ___________________ control cabinet configuration SINAMICS G130 ___________________ Cabinet design and EMC Cabinet air conditioning Operating Instructions Control version V4.6 03/2013 A5E00427629A...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5 Table of contents Safety information............................5 Warnings ............................5 Safety and operating instructions....................6 Components that can be destroyed by electrostatic discharge (ESD) ..........7 General..............................9 Safety information ..........................9 Directives .............................10 Standards.............................11 Basic information about EMC ........................15 Introduction to EMC ........................15 EMC-compliant design and control cabinet configuration ................
  • Page 6 Table of contents Cabinet design and EMC Operating Instructions, 03/2013, A5E00427629A...
  • Page 7: Safety Information

    Safety information Warnings WARNING Dangerous electrical voltage Hazardous voltages are present when electrical equipment is in operation. Severe personal injury or substantial material damage may result if these warnings are not observed. Only qualified personnel are permitted to work on or around the equipment. These personnel must be thoroughly familiar with all the warnings and maintenance procedures described in these operating instructions.
  • Page 8: Safety And Operating Instructions

    Note Support by SIEMENS service centers We recommend engaging the support and services of your local Siemens service center for all planning, installation, commissioning and maintenance work. Cabinet design and EMC Operating Instructions, 03/2013, A5E00427629A...
  • Page 9: Components That Can Be Destroyed By Electrostatic Discharge (Esd)

    Safety information 1.3 Components that can be destroyed by electrostatic discharge (ESD) Components that can be destroyed by electrostatic discharge (ESD) CAUTION Components sensitive to electrostatic charge The board contains components that can be destroyed by electrostatic discharge. These components can be easily destroyed if not handled properly. If you do have to use electronic boards, however, please observe the following: ...
  • Page 10 Safety information 1.3 Components that can be destroyed by electrostatic discharge (ESD) Cabinet design and EMC Operating Instructions, 03/2013, A5E00427629A...
  • Page 11: General

    General The modular concept of SINAMICS G130 makes it impossible to describe each individual combination. This section instead aims to provide some basic information and general rules on the basis of which special device combinations can be constructed and to ensure electromagnetic compatibility.
  • Page 12: Directives

    General 2.2 Directives NOTICE Only use original Siemens accessories To ensure that the entire system functions properly, you are advised to use the original Siemens accessories. Only original DRIVE-CLiQ cables may be used for wiring the DRIVE-CLiQ nodes. Before commissioning, check the tightening torque of all the terminal screws.
  • Page 13: Standards

    General 2.3 Standards Standards Note The standards listed in the table below are non-binding and do not in any way claim to be complete. The standards listed do not represent a guaranteed property of the product. Only the statements made in the Declaration of Conformity shall be deemed binding. Table 2- 2 Fundamental, application-relevant standards in succession: EN, IEC/ISO, DIN, VDE Standards*...
  • Page 14 General 2.3 Standards Standards* Title IEC 60287-1 to -3 Cables - Calculation of the current carrying capacity Part 1: Current carrying capacity equations (100 % load factor) and calculating the losses Part 2: Thermal resistance - Part 3: Main sections for operating conditions HD 60364-x-x Erection of power installations with nominal voltages up to 1000 V;...
  • Page 15 General 2.3 Standards Standards* Title EN 61800-5-x Adjustable-speed electrical power drive systems; IEC 61800-5-x Part 5: Safety requirements; DIN EN 61800-5-x Main section 1: Electrical, thermal and energy requirements VDE 0160-105-x Main section 2: Functional safety requirements EN 62061 Safety of machinery; IEC 62061 Functional safety of safety-related electrical, electronic and programmable electronic control DIN EN 62061...
  • Page 16 General 2.3 Standards Cabinet design and EMC Operating Instructions, 03/2013, A5E00427629A...
  • Page 17: Basic Information About Emc

    Basic information about EMC Introduction to EMC What is meant by EMC? Electromagnetic compatibility (EMC) describes the capability of an electrical device to function satisfactorily in an electromagnetic environment without itself causing interference unacceptable for other devices in the environment. EMC therefore represents a quality feature for the ●...
  • Page 18 Basic information about EMC 3.1 Introduction to EMC Noise emissions Product standard EN 61800–3 outlines the EMC requirements for variable-speed drive systems. It specifies requirements for converters with operating voltages of less than 1000 V. Different environments and categories are defined depending on where the drive system is installed.
  • Page 19 Basic information about EMC 3.1 Introduction to EMC Table 3- 2 Definition of categories C1 to C4 Definition of categories C1 to C4 Category C1 Rated voltage <1000 V; unrestricted use in the first environment. Category C2 Rated voltage for stationary drive systems <1000 V; for use in the second environment.
  • Page 20 Basic information about EMC 3.1 Introduction to EMC Cabinet design and EMC Operating Instructions, 03/2013, A5E00427629A...
  • Page 21: Emc-Compliant Design And Control Cabinet Configuration

    EMC-compliant design and control cabinet configuration For detailed configuration instructions regarding the EMC-compliant design of drives and control cabinet configuration, refer to the "SINAMICS Low Voltage Configuration Manual". Cabinet design and EMC Operating Instructions, 03/2013, A5E00427629A...
  • Page 22 EMC-compliant design and control cabinet configuration Cabinet design and EMC Operating Instructions, 03/2013, A5E00427629A...
  • Page 23: Cabinet Air Conditioning

    NOTICE Avoid the reduction of service life If the guidelines for installing SINAMICS G130 equipment are not observed, this can significantly reduce the service life of the components and result in premature component failure.
  • Page 24: Ventilation

    5.2 Ventilation Ventilation The SINAMICS G130 devices are forced-ventilated by means of integrated fans. To ensure an adequate air supply, suitable openings for the inlet air (e.g. ventilation slots in the cabinet door) and discharged air (e.g.,by means of a hood) must be provided.
  • Page 25 Cabinet air conditioning 5.2 Ventilation Figure 5-1 Air guidance for Power Module, frame size FX, GX Cabinet design and EMC Operating Instructions, 03/2013, A5E00427629A...
  • Page 26 Cabinet air conditioning 5.2 Ventilation Abluft Figure 5-2 Air guidance for Power Module, frame size HX, JX Devices must not be operated in an "air short circuit", since this can damage equipment or cause it to fail. The pull of the fan causes negative pressure to build up at the ventilation openings in the cabinet doors.
  • Page 27 Cabinet air conditioning 5.2 Ventilation Due to the flow of air within the cabinet, the device fan draws in pre-heated air. This heats up the components considerably and the ventilator does not function effectively. NOTICE To prevent an air short circuit Devices must not be operated in an air short circuit, since this can cause it to fail.
  • Page 28 Cabinet air conditioning 5.2 Ventilation The opening cross-sections specified in the table refer in each case to one device. If more than one device is installed in a cabinet, the opening cross-section increases accordingly. If the required openings cannot be made in the cabinet, the devices must be distributed across several cabinets, which are separated from each other by means of partitions.
  • Page 30 Siemens AG Subject to change without prior notice Industry Sector © Siemens AG, 2004 - 2013 Drive Technologies Large Drives P.O. Box 4743 90025 NUREMBERG GERMANY www.siemens.com/automation...