Preface Open Source Software Table of Contents SIPROTEC 5 Introduction Forms of Devices and On-Site Operation Hardware Description Panels Electronic Modules V7.50 and higher Plug-In Modules Working on the Device Manual Technical Data Ordering Information Appendix Glossary Index C53000-G5040-C002-C...
Page 2
Although including rights created by patent grant or registration of a Siemens AG has made best efforts to keep the document as utility model or a design, are reserved. precise and up-to-date as possible, Siemens AG shall not...
Preface Purpose of the Manual This manual describes the hardware of the SIPROTEC 5 device family and provides general information on the product structure, the modules and technical data. Target Audience Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main- tenance of automation, selective protection and control equipment, and operational crew in electrical installa- tions and power plants.
Page 4
The SIPROTEC 5 catalog describes the system features and the devices of SIPROTEC 5. • Selection guide for SIPROTEC and Reyrolle The selection guide offers an overview of the device series of the Siemens protection devices, and a device selection table. Indication of Conformity...
Preface Additional Support For questions about the system, please contact your Siemens sales partner. Support Our Customer Support Center provides a 24-hour service. Phone: +49 (180) 524-7000 Fax: +49 (180) 524-2471 E-Mail: support.energy@siemens.com Training Courses Inquiries regarding individual training courses should be addressed to our Training Center:...
Page 6
The equipment (device, module) may be used only for such applications as set out in the catalogs and the technical description, and only in combination with third-party equipment recommended and approved by Siemens. Problem-free and safe operation of the product depends on the following: •...
License Conditions provide for it you can order the source code of the Open Source Software from your Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years since purchase of the Product. We are liable for the Product including the Open Source Software contained in it pursuant to the license conditions applicable to the Product.
Table of Contents Preface................................3 Open Source Software..........................7 Introduction..............................15 Advantages of SIPROTEC 5 ....................16 Modular Systems and Hardware Characteristics..............17 Forms of Devices and On-Site Operation Panels..................19 Flush-Mounting Devices....................20 2.1.1 Description ......................... 20 Surface-Mounted Devices with Integrated On-Site Operation Panel........28 2.2.1 Description of the Modular Device................
Page 10
Table of Contents 3.2.5 Input and Output Module IO204.................. 63 3.2.5.1 Description......................63 3.2.5.2 Terminals.......................64 3.2.6 Input and Output Module IO205.................. 66 3.2.6.1 Description ......................66 3.2.6.2 Terminals.......................67 3.2.7 Input and Output Module IO206.................. 69 3.2.7.1 Description ......................69 3.2.7.2 Terminals.......................70 3.2.8 Input and Output Module IO207..................
Page 11
Table of Contents 3.4.2.2 Terminals......................109 3.4.3 Input and Output Module IO102................111 3.4.3.1 Description......................111 3.4.3.2 Terminals......................112 3.4.4 Input and Output Module IO103................114 3.4.4.1 Description......................114 3.4.4.2 Terminals......................115 3.4.5 Input and Output Module IO110................117 3.4.5.1 Description......................117 3.4.5.2 Terminals......................118 3.4.6 Input and Output Module IO111................
Page 12
Table of Contents 5.2.1.3 Expanding Devices with 2nd Device Row.............. 158 5.2.2 Surface-Mounted Devices with Integrated On-Site Operation Panel......160 5.2.2.1 Basic Rules for Expansion..................160 5.2.2.2 Expanding 1st Device Row..................161 5.2.2.3 Expanding Devices with 2nd Device Row.............. 163 5.2.3 Surface-Mounted Devices with Detached On-Site Operation Panel......165 5.2.3.1 Basic Rules for Expansion..................
Page 13
Table of Contents 6.16 Name Plate of Non-Modular Devices (7xx82)..............236 6.17 Name Plate, UL Approval, Base Module and 1/3 Base Module........... 237 6.18 Name Plate, UL Approval, Expansion Module..............238 6.19 Battery ........................... 239 6.20 SDHC Memory Card ......................240 6.21 Display Resolution ......................
1.1 Advantages of SIPROTEC 5 Advantages of SIPROTEC 5 The devices in the SIPROTEC 5 series are based on the many years of experience gathered with SIPROTEC 4. Extensive improvements have also been integrated. Take note of the differences between the modular and non-modular systems.
1.2 Modular Systems and Hardware Characteristics Modular Systems and Hardware Characteristics The SIPROTEC 5 series includes both modular and non-modular devices. Modular devices consist of a base module (1/3 of 19 inches) and can be expanded with expansion modules (1/6 of 19 inches). The device type identifier for modular devices is XXX85, XXX86, or XXX87, for example, 7SA86.
Page 18
Introduction 1.2 Modular Systems and Hardware Characteristics Hardware Characteristics of Non-Modular Devices (7xx82) A non-modular device always consists of just 1 module (1/3 of 19 inches) and cannot be expanded with expansion modules (1/6 of 19 inches). These hardware characteristics are: •...
Forms of Devices and On-Site Operation Panels 2.1 Flush-Mounting Devices Flush-Mounting Devices Description 2.1.1 The flush-mounting devices were conceived for installation in 19-inch racks or special openings in control desks and cabinets. The on-site operation panel is linked permanently to the device. Base Module [le_surface_mounting_front, 2, --_--] Figure 2-1...
Page 21
Forms of Devices and On-Site Operation Panels 2.1 Flush-Mounting Devices [le_rear modular device, 1, --_--] Figure 2-2 Rear View of a Modular Device, Terminals of a Typical Device with IO202 Current terminal 1A Spring clip Voltage terminal 1B Voltage terminal 1C Voltage terminal 1D Protective grounding terminal Plug-in module position F...
Page 22
Forms of Devices and On-Site Operation Panels 2.1 Flush-Mounting Devices [le_rear non modular, 1, --_--] Figure 2-3 Rear View of a Non-Modular Device (7xx82), Terminals of a Typical Device with IO102 Current terminal A Spring clip Voltage terminal B Voltage terminal D Voltage terminal L Time synchronization G Plug-in module position E...
Page 23
Forms of Devices and On-Site Operation Panels 2.1 Flush-Mounting Devices Fastening Openings of the Base and 1/3 Module To remove the screw covers, introduce the screwdriver into the provided slot. [dw_screwdriver, 1, --_--] Figure 2-4 Slot for Introducing the Screwdriver Loosen the cover by turning slightly.
Page 24
Forms of Devices and On-Site Operation Panels 2.1 Flush-Mounting Devices Expansion Module [le_front expansion module, 1, --_--] Figure 2-6 Front View of the Expansion Module Device housing On-site operation panel Bus terminal for an additional expansion module (shown with bus termination plate) Unused bus terminals are sealed with a cover.
Page 25
Forms of Devices and On-Site Operation Panels 2.1 Flush-Mounting Devices [le_rear expansion module, 1, --_--] Figure 2-7 Rear View of the Expansion Module Current terminal xA Spring clip Voltage terminal xB Bus terminal to the base module Voltage terminal xC Voltage terminal xD Protective grounding terminal NOTE...
Page 26
Forms of Devices and On-Site Operation Panels 2.1 Flush-Mounting Devices Counting Method for Assemblies in 19-Inch Rack (View of the Rear of the Device) [dwbgrpos-170713-01.tif, 3, en_US] Figure 2-8 Counting Method for Assemblies in 19-Inch Rack (Example) Current terminal A Voltage terminal A, B, C, D Terminal for time synchronization G Plug-in module E, F...
Page 27
Forms of Devices and On-Site Operation Panels 2.1 Flush-Mounting Devices NOTE The structure of the 2nd device row is described in chapter 5.2.1.3 Expanding Devices with 2nd Device Row. Connection Systems [le_connection, 1, --_--] Figure 2-9 Connection Systems Cut-out for contact tab Contact tab (prefitted on the expansion module) Hinged angle clip Snap-in spring...
Forms of Devices and On-Site Operation Panels 2.2 Surface-Mounted Devices with Integrated On-Site Operation Panel Surface-Mounted Devices with Integrated On-Site Operation Panel Description of the Modular Device 2.2.1 NOTE The basic device structure is described in chapter 2.1.1 Description The surface-mounting devices with integrated on-site operation panel were conceived for fitting on a flat wall surface.
Page 29
Forms of Devices and On-Site Operation Panels 2.2 Surface-Mounted Devices with Integrated On-Site Operation Panel [dwauzeil-040211-01.tif, 2, --_--] Figure 2-11 Basic and Expansion Module of the Surface-Mounting Device Mounting bracket NOTE When a base module is expanded, 2 mounting brackets must be fitted between the on-site operation panels and the distance frame.
Forms of Devices and On-Site Operation Panels 2.2 Surface-Mounted Devices with Integrated On-Site Operation Panel Fastening Openings [dwbaaube-040211-01.tif, 2, --_--] Figure 2-12 Fastening Openings of the Base Module Top fastening openings Bottom fastening openings 2.2.2 Description of the Non-Modular Surface-Mounting Device NOTE The basic device structure is described in chapter 2.1.1 Description...
Page 31
Forms of Devices and On-Site Operation Panels 2.2 Surface-Mounted Devices with Integrated On-Site Operation Panel [le_device with console above and below, 1, --_--] Figure 2-13 Bracket with the Opening Upward (Left) and the Opening Downward (Right) Flush-mounting device Bracket for the surface-mounting variant Bracket opening for cable entry or exit when mounting or dismantling the device SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 32
Forms of Devices and On-Site Operation Panels 2.2 Surface-Mounted Devices with Integrated On-Site Operation Panel [sc device mounting, 2, --_--] Figure 2-14 Surface-Mounting Version of the Non-Modular Device, Mounted SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 33
Forms of Devices and On-Site Operation Panels 2.2 Surface-Mounted Devices with Integrated On-Site Operation Panel Fastening Openings [sc fixing console, 2, --_--] Figure 2-15 Fastening Openings of the Bracket SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Forms of Devices and On-Site Operation Panels 2.3 Surface-Mounted Devices with Detached On-Site Operation Panel Surface-Mounted Devices with Detached On-Site Operation Panel Description 2.3.1 NOTE The basic device structure is described in chapter 2.1.1 Description The surface-mounting devices with detached on-site operation panel are a variant of the surface-mounting devices with an integrated on-site operation panel.
Page 35
Forms of Devices and On-Site Operation Panels 2.3 Surface-Mounted Devices with Detached On-Site Operation Panel Rear plate of the on-site operation panel Connecting cable between the base module and the on-site operation panel Fastening Openings [dwbaaube-040211-01.tif, 2, --_--] Figure 2-17 Device Structure of the Base Module Top fastening openings Bottom fastening openings...
Page 36
Forms of Devices and On-Site Operation Panels 2.3 Surface-Mounted Devices with Detached On-Site Operation Panel [dwosobb1-040211-01.tif, 2, --_--] Figure 2-18 Fastening Openings for the On-Site Operation Panel Screw cover (pull towards you to remove) Fastening opening Fastening opening with fastening screw SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Forms of Devices and On-Site Operation Panels 2.4 On-Site Operation Panels On-Site Operation Panels Description 2.4.1 Operating Concept The operating concept is based on 4 groups: • Navigation in the menu tree • Modification of settings • Display of measured values and protocols •...
Forms of Devices and On-Site Operation Panels 2.4 On-Site Operation Panels [dw_osop_with_pushbutton, 2, --_--] Figure 2-20 Variants 1/6 Views Overview of Operating Elements and Display Elements 2.4.2 On-Site Operation Panel of the Base 1/3 Module [le_base_module, 1, --_--] Figure 2-21 Base 1/3 Module in Standard, US, and China Design Operating state display Display in 2 design versions...
Page 39
Forms of Devices and On-Site Operation Panels 2.4 On-Site Operation Panels The on-site operation panels are distinguished by the following characteristics: • Flat and compact design • LCD (Liquid Crystal Display) graphics display Small with 192 x 128 pixels for showing measured values and small control displays Large with 240 x 320 pixels for showing measured values and control displays •...
Page 40
Forms of Devices and On-Site Operation Panels 2.4 On-Site Operation Panels Operating Element/ Function Display Element USB port with protective cover Type B for notebook/PC 16 two-colored parameterizable LEDs On-Site Operation Panel of Expansion Modules [le_expansion modules, 1, --_--] Figure 2-22 Expansion Module 16 monochrome LEDs Cover labels...
Page 41
Forms of Devices and On-Site Operation Panels 2.4 On-Site Operation Panels • Decorative film • 2 key switches for setting the operating mode Besides the base module, you can add an expansion module with key switches. The following table explains the meanings of the switch positions.
Electronic Modules Power-Supply Modules of the Modular Devices Input and Output Modules of the Modular Devices Power-Supply Module of Non-Modular Devices (7xx82) Input and Output Modules of the Non-Modular Devices (7xx82) SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.1 Power-Supply Modules of the Modular Devices Power-Supply Modules of the Modular Devices Application Sheet of the Power-Supply Modules of the Modular Devices 3.1.1 Module Designation Function Description • PS201 Power-supply module • 24 V DC/48 V DC or DC 60 V to DC 250 V and AC 100 V to AC 230 V •...
Electronic Modules 3.1 Power-Supply Modules of the Modular Devices 3.1.2.2 Terminals Overview of Terminals [le_ps201, 1, --_--] Figure 3-1 PS201 – Terminals Voltage terminal 2B Time synchronization G Detached on-site operation panel H Plug-in module position E Integrated Ethernet interface J COM link K, connection to the CB202 PCB assembly (plug-in module assembly), position K Plug-in module position F Protective grounding terminal...
Page 47
Electronic Modules 3.1 Power-Supply Modules of the Modular Devices [tdps201x-270812-01.tif, 1, en_US] Figure 3-3 PS201 – Connection Diagram Time-Synchronization Terminal The terminal for time synchronization is located on the D-sub 9 interface (position G). Time synchronization signals for DC 5 V, DC 12 V, and DC 24 V can be processed as an option. For further information on connecting to the time synchronization, see chapter 6.6 Communication Interfaces in the Technical Data.
Electronic Modules 3.1 Power-Supply Modules of the Modular Devices Ethernet COM Link The Ethernet connection to the CB202 PCB assembly (plug-in module assembly with integrated power supply) is realized using the RJ45 interface. The RJ45 interface can be used exclusively for the connection of the CB202 module. This terminal is left unused when no CB202 module is in use.
Electronic Modules 3.1 Power-Supply Modules of the Modular Devices 3.1.3.2 Terminals Overview of Terminals [le_ps203, 1, --_--] Figure 3-4 PS203 – Terminals 2-pole terminal to connect power supply LED: Power On Protective grounding terminal Connection Diagram [tdps203x-030713-01.tif, 2, en_US] Figure 3-5 PS203 –...
Page 50
Electronic Modules 3.1 Power-Supply Modules of the Modular Devices [dwkl2pol-030211-01.tif, 1, --_--] Figure 3-6 Connection of External Power Supply NOTE When expanding a device with the 2nd device row, you must install the connecting cable for the 2nd device row together with the associated angle rail. All required components are included with a power- supply module PS203.
Electronic Modules 3.1 Power-Supply Modules of the Modular Devices LEDs of the RJ45 Terminals The light-emitting diodes (LEDs) signal the operating state of the communication connection. The operating states are explained in the following table: COM Link (RJ45) Signal Color Operating State LED 1 CL2_LED0_N Yellow Flashes when a communication module is inserted in...
Page 53
Electronic Modules 3.1 Power-Supply Modules of the Modular Devices Connection Diagram [tdcb202x-100713-01.tif, 2, en_US] Figure 3-11 CB202 – Connection Diagram [dwkl2pol-030211-01.tif, 1, --_--] Figure 3-12 Connection of External Power Supply SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Input and Output Modules of the Modular Devices Function Description of the Input and Output Modules of the Modular Devices 3.2.1 Module Designation Function Description • IO201 Input and output module •...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Input and Output Module IO201 3.2.2 3.2.2.1 Description The terminals for the following are located on the input and output module IO201: • 4 current transformers (optionally protection-class current transformers or instrument transformers) •...
Page 56
Electronic Modules 3.2 Input and Output Modules of the Modular Devices NOTE x corresponds to the slot in the 19-inch rack. Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cdio201x-290812-01.tif, 1, en_US] Figure 3-14 IO201 –...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio201x-290812-01.tif, 1, en_US] Figure 3-15 IO201 – Connection Diagram 3.2.3 Input and Output Module IO202 3.2.3.1 Description This input and output module is used as the base measurement module in all protection devices and bay units. One device can contain several IO202 input and output modules.
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.3.2 Terminals Overview of Terminals [dwio202p-030211-01.tif, 2, --_--] Figure 3-16 IO202 – Terminals Current terminal xA Voltage terminal xB Voltage terminal xC Voltage terminal xD Protective grounding terminal NOTE x corresponds to the slot in the 19-inch rack.
Page 59
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cdio202x-300812-01.tif, 1, en_US] Figure 3-17 IO202 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio202x-240812-01.tif, 1, en_US] Figure 3-18 IO202 – Connection Diagram Input and Output Module IO203 3.2.4 3.2.4.1 Description The terminals for the following are located on the input and output module IO203: •...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.4.2 Terminals Overview of Terminals [le_io203, 1, --_--] Figure 3-19 IO203 – Terminals Current terminal xA Current terminal xB Voltage terminal xD Protective grounding terminal NOTE x corresponds to the slot in the 19-inch rack. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 62
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cdio203x-280812-01.tif, 1, en_US] Figure 3-20 IO203 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio203x-110313-01.tif, 1, en_US] Figure 3-21 IO203 – Connection Diagram Input and Output Module IO204 3.2.5 3.2.5.1 Description The terminals for the following are located on the input and output module IO204: •...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.5.2 Terminals Overview of Terminals [dwio204p-201112-01.tif, 2, --_--] Figure 3-22 IO204 – Terminals Voltage terminal xA Voltage terminal xC Voltage terminal xD Protective grounding terminal NOTE x corresponds to the slot in the 19-inch rack. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 65
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cdio204x-201112-01.tif, 1, en_US] Figure 3-23 IO204 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio204x-201112-01.tif, 1, en_US] Figure 3-24 IO204 – Connection Diagram Input and Output Module IO205 3.2.6 Description 3.2.6.1 The terminals for the following are located on the input and output module IO205: •...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.6.2 Terminals Overview of Terminals [dwio205p-030211-01.tif, 2, --_--] Figure 3-25 IO205 – Terminals Voltage terminal xA Voltage terminal xB Voltage terminal xC Voltage terminal xD Protective grounding terminal NOTE x corresponds to the slot in the 19-inch rack.
Page 68
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cdio205x-260213-01.tif, 1, en_US] Figure 3-26 IO205 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio205x-240812-01.tif, 1, en_US] Figure 3-27 IO205 – Connection Diagram Input and Output Module IO206 3.2.7 3.2.7.1 Description The terminals for the following are located on the input and output module IO206: •...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.7.2 Terminals Overview of Terminals [dwio206p-030211-01.tif, 2, --_--] Figure 3-28 IO206 – Terminals Voltage terminal xA Voltage terminal xD Protective grounding terminal NOTE x corresponds to the slot in the 19-inch rack. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 71
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cdio206x-280812-01.tif, 1, en_US] Figure 3-29 IO206 – Terminal Diagram [tdio206x-050313-02.tif, 1, en_US] Figure 3-30 IO206 –...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Input and Output Module IO207 3.2.8 3.2.8.1 Description The terminals for the following are located on the input and output module IO207: • 16 binary inputs • 8 binary outputs with 8 standard make contacts (type S) The connections are distributed over four 14-pole voltage terminals.
Page 73
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cdio207x-260213-01.tif, 1, en_US] Figure 3-32 IO207 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio207x-300812-01.tif, 1, en_US] Figure 3-33 IO207 – Connection Diagram Input and Output Module IO208 3.2.9 3.2.9.1 Description The terminals for the following are located on the input and output module IO208: •...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.9.2 Terminals Overview of Terminals [dwio208p-030211-01.tif, 2, --_--] Figure 3-34 IO208 – Terminals Current terminal xA Voltage terminal xB Voltage terminal xC Voltage terminal xD Protective grounding terminal x corresponds to the slot in the 19-inch rack. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 76
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cdio208x-050313-01.tif, 3, en_US] Figure 3-35 IO208 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio208x-300812-01.tif, 1, en_US] Figure 3-36 IO208 – Connection Diagram 3.2.10 Input and Output Module IO209 3.2.10.1 Description The terminals for the following are located on the input and output module IO209: •...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.10.2 Terminals Overview of Terminals [dwio209p-030211-01.tif, 2, --_--] Figure 3-37 IO209 – Terminals Voltage terminal xA Voltage terminal xC Voltage terminal xD Protective grounding terminal NOTE x corresponds to the slot in the 19-inch rack. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 79
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cdio209x-110313-01.tif, 1, en_US] Figure 3-38 IO209 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio209x-270812-01.tif, 1, en_US] Figure 3-39 IO209 – Connection Diagram Input and Output Module IO210 3.2.11 3.2.11.1 Description The terminals for the following are located on the input and output module IO210: •...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.11.2 Terminals Overview of Terminals [dwio202p-030211-01.tif, 2, --_--] Figure 3-40 IO210 – Terminals Current terminal xA Voltage terminal xB Voltage terminal xC Voltage terminal xD Protective grounding terminal NOTE x corresponds to the slot in the 19-inch rack.
Page 82
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cd_io210, 2, en_US] Figure 3-41 IO210 – Terminal Diagram Voltage input MT3 with higher voltage immunity (maximum continuous voltage ±...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [td_io210, 2, en_US] Figure 3-42 IO210 – Connection Diagram 3.2.12 Input and Output Module IO211 3.2.12.1 Description The terminals for the following are located on the input and output module IO211: •...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.12.2 Terminals Overview of Terminals [dwio211p-211112-01.tif, 2, --_--] Figure 3-43 IO211 Terminals Voltage terminal xA Voltage terminal xC Voltage terminal xD Protective grounding terminal NOTE x corresponds to the slot in the 19-inch rack. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 85
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cdio211x-221112-01.tif, 1, en_US] Figure 3-44 IO211 Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio211x-211112-01.tif, 1, en_US] Figure 3-45 IO211 Connection Diagram Input and Output Module IO212 3.2.13 3.2.13.1 Description The terminals for the following are located on the input and output module IO212: •...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.13.2 Terminals Overview of Terminals [dwio204p-201112-01.tif, 2, --_--] Figure 3-46 IO212 – Terminals Voltage terminal xA Voltage terminal xC Voltage terminal xD Protective grounding terminal NOTE x corresponds to the slot in the 19-inch rack. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 88
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cd_io212, 1, en_US] Figure 3-47 IO212 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio212x, 1, en_US] Figure 3-48 IO212 – Connection Diagram Input and Output Module IO214 3.2.14 3.2.14.1 Description This input and output module is used as the base measurement module in all protection devices. One device can contain several IO214 input and output modules.
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.14.2 Terminals Overview of Terminals [dwio214p-030211-01.tif, 2, --_--] Figure 3-49 IO214 – Terminals Current terminal xA Voltage terminal xB Voltage terminal xC Voltage terminal xD Protective grounding terminal NOTE x corresponds to the slot in the 19-inch rack.
Page 91
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram For the binary inputs and outputs, the x corresponds to the slot in the 19-inch rack. [cdio214x-260213-01.tif, 1, en_US] Figure 3-50 IO214 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio214x-270812-01.tif, 1, en_US] Figure 3-51 IO214 – Connection Diagram 3.2.15 Input and Output Module IO215 3.2.15.1 Description This input and output module is used as the base measurement module in all protection devices and bay units. One device can contain several IO215 input and output modules.
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Input Module IO230 3.2.16 3.2.16.1 Description The terminals for the following are located on the IO230 module: • 48 binary inputs The connections are distributed over six 10-pole connection terminals. NOTE Note that the IO230 input module has group switching for switching thresholds.
Page 94
Electronic Modules 3.2 Input and Output Modules of the Modular Devices NOTE x corresponds to the slot in the 19-inch rack. Terminal and Connection Diagram NOTE The polarities of the voltages at the binary inputs must not be reversed! [cdio230x-030713-01.tif, 1, en_US] Figure 3-53 IO230 –...
Page 95
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [tdio230x, 1, en_US] Figure 3-54 IO230 – Connection Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Input and Output Module IO231 3.2.17 3.2.17.1 Description The terminals for the following are located on the input and output module IO231: • 24 binary inputs • 24 binary outputs, standard make contacts (type S) The connections are distributed over six 10-pole connection terminals.
Page 97
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Terminal and Connection Diagram NOTE The polarities of the voltages at the binary inputs must not be reversed! [cd_io231x, 2, en_US] Figure 3-56 IO231 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [td_tdio231x, 1, en_US] Figure 3-57 IO231 – Connection Diagram 3.2.18 Input Module IO233 3.2.18.1 Description The terminals for the following are located on the input module IO233: • 48 binary inputs SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.2 Input and Output Modules of the Modular Devices [td_io233x, 1, en_US] Figure 3-60 IO233 – Connection Diagram 3.2.19 Input and Output Module PB201 3.2.19.1 Description The process-bus assembly is used for the reception of Sampled Measured Values (SMV) according to IEC 61850-9-2 via 6 optical interfaces.
Electronic Modules 3.2 Input and Output Modules of the Modular Devices 3.2.19.2 Terminals Overview of Terminals [dw_pb201, 2, --_--] Figure 3-61 PB201 – Terminals 2 duplex LC interfaces channel A 2 duplex LC interfaces channel B 2 duplex LC interfaces channel C 1 duplex LC interface service port 2 protective grounding terminals Product code...
Page 103
Electronic Modules 3.2 Input and Output Modules of the Modular Devices Optical budget Minimum 7.5 dB for 50 μm/125 μm, NA = 0.2 Minimum 11.0 dB for 62.5 μm/125 μm, NA = 0.275 Laser class 1 as per EN 60825-1/-2 With the use of 62.5 μm/125 μm and 50 μm/125 μm optical fibers Comment: Numerical aperture (NA = sin θ...
Electronic Modules 3.3 Power-Supply Module of Non-Modular Devices (7xx82) Power-Supply Module of Non-Modular Devices (7xx82) Power-Supply Module PS101 3.3.1 3.3.1.1 Description The power-supply module PS101 is always permanently installed in the 1/3 module. The following can be found on the PS101 module: •...
Electronic Modules 3.3 Power-Supply Module of Non-Modular Devices (7xx82) 3.3.1.2 Terminals Overview of Terminals The terminals assigned to the module are identified by the frame in the figure. [le_ps101, 1, --_--] Figure 3-62 PS101 – Terminals Voltage terminal L Time synchronization G Plug-in module position E Plug-in module position F Integrated Ethernet interface J...
Page 106
Electronic Modules 3.3 Power-Supply Module of Non-Modular Devices (7xx82) Terminal and Connection Diagram [cdps101x-210513-01.tif, 1, en_US] Figure 3-63 PS101 – Terminal Diagram [tdps101x-210513-01.tif, 1, en_US] Figure 3-64 PS101 – Connection Diagram Time-Synchronization Terminal The terminal for time synchronization is located on the D-sub 9 interface (position G). Time synchronization signals for DC 5 V, DC 12 V, and DC 24 V can be processed as an option.
Page 107
Electronic Modules 3.3 Power-Supply Module of Non-Modular Devices (7xx82) For further information on connecting to the time synchronization, see chapter 6.6 Communication Interfaces in the Technical Data. Integrated Ethernet Interface (RJ45) This terminal is used to load the device with DIGSI 5 using Ethernet. This terminal also enables straight- forward IEC 61850 Ethernet communication (including GOOSE) or communication with another protocol via Ethernet, for example, for connecting an external RTD unit.
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) Input and Output Modules of the Non-Modular Devices (7xx82) Function Description of the Input and Output Modules of the Non-Modular 3.4.1 Devices Module Designation Function Description • IO101 Input and output module •...
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) 3.4.2.2 Terminals Overview of Terminals The terminals assigned to the module are identified by the frame in the figure. [le_io101, 1, --_--] Figure 3-65 IO101 – Terminals Current terminal A Voltage terminal B Voltage terminal D Protective grounding terminal...
Page 110
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) Terminal and Connection Diagram [cdio101x-220513-01.tif, 1, en_US] Figure 3-66 IO101 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) [tdio101x-220513-01.tif, 1, en_US] Figure 3-67 IO101 – Connection Diagram Input and Output Module IO102 3.4.3 3.4.3.1 Description The terminals for the following are located on the input and output module IO102: •...
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) 3.4.3.2 Terminals Overview of Terminals The terminals assigned to the module are identified by the frame in the figure. [le_io102, 1, --_--] Figure 3-68 IO102 – Terminals Current terminal A Voltage terminal B Voltage terminal D Protective grounding terminal...
Page 113
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) Terminal and Connection Diagram [cdio102x-220513-01.tif, 1, en_US] Figure 3-69 IO102 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) [tdio102x-220513-01.tif, 1, en_US] Figure 3-70 IO102 – Connection Diagram 3.4.4 Input and Output Module IO103 3.4.4.1 Description The terminals for the following are located on the input and output module IO103: •...
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) 3.4.4.2 Terminals Overview of Terminals The terminals assigned to the module are identified by the frame in the figure. [le_io103, 1, --_--] Figure 3-71 IO103 – Terminals Current terminal A Current terminal B Voltage terminal D Protective grounding terminal...
Page 116
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) Terminal and Connection Diagram [cdio103x-131113-01, 3, en_US] Figure 3-72 IO103 – Terminal Diagram SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) [tdio103x-01.vsd, 1, en_US] Figure 3-73 IO103 – Connection Diagram Input and Output Module IO110 3.4.5 3.4.5.1 Description The terminals for the following are located on the input and output module IO110: •...
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) [tdio110x-220513-01.tif, 1, en_US] Figure 3-76 IO110 – Connection Diagram Input and Output Module IO111 3.4.6 3.4.6.1 Description The connections for the following are located on the input and output module IO111: •...
Connections of Temperature Sensors and Cables Connections of Temperature Sensors Directly to the Device It is possible in principle to connect temperature sensors with 2-phase or 3-phase technology. To achieve the specified accuracy, Siemens recommends only using 3-phase technology. [dw_example_temp_sensor_3phase, 1, en_US] Figure 3-80...
Page 124
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) [dw_example_temp_sensor_2phase, 1, en_US] Figure 3-81 Example: Connecting Temperature Sensors RTD 1 (2-Line Terminal) and RTD 2 (2-Line Terminal) to Terminals M1 to M5 [dw_temperature_sensor, 1, en_US] Figure 3-82 Example: Connecting Temperature Sensors RTD 1 (3-Line Terminal) and RTD 2 (2-Line Terminal) to Terminals M1 to M5 Connecting the Lines...
Page 125
Electronic Modules 3.4 Input and Output Modules of the Non-Modular Devices (7xx82) Loosen the 2 screws for fastening the shielding plates on the device next to the 16-pole or 17-pole plug ² so that there is somewhat more than 2 mm (0.08 in) space. Push the prepared shielding plate under the screw heads and tighten them.
Plug-In Modules Function Description of Plug-In Modules of Modular and Non-Modular Devices Communication Modules Measuring-Transducer Modules SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Plug-In Modules 4.1 Function Description of Plug-In Modules of Modular and Non-Modular Devices Function Description of Plug-In Modules of Modular and Non- Modular Devices Plug-In Module Function Description Designation USART-xx-yEL Serial communication module with electric transmission USART-xx-yFO Serial communication module with optical transmission for short distance USART-xx-yLDFO Serial communication module with optical transmission for long distance ETH-xx-2EL...
Plug-In Modules 4.2 Communication Modules Communication Modules Overview 4.2.1 SIPROTEC devices can be ordered with factory-installed communication modules. The communication modules can also be installed and replaced in the SIPROTEC devices afterwards. You do not have to open the device for this.
Page 130
Plug-In Modules 4.2 Communication Modules Time synchronization G Plug-in module position E Detached on-site operation panel H Plug-in module position F Integrated Ethernet interface J Connection to the expansion module with CB202 module Protective grounding terminal [dwlmnppo-030211-01.tif, 2, --_--] Figure 4-2 Plug-In Module Positions and Communication Terminals in the Expansion Module with CB202 2-pole terminal to connect power supply COM link L (connection to interface K of the base unit)
Page 131
Plug-In Modules 4.2 Communication Modules [le_slots and communication terminals, 1, --_--] Figure 4-3 Plug-In Module Positions and Communication Terminals on the 1/3 Module, for Non-Modular Devices (7xx82) Time synchronization G Plug-in module position E Plug-in module position F Integrated Ethernet interface J Protective grounding terminal The following communication modules can be used for SIPROTEC 5: •...
Plug-In Modules 4.2 Communication Modules • Ethernet Modules Application: Ethernet-based communication to the substation automation technology via substation- control protocols (for example, IEC 61850 and DNP3) – Secure communication to DIGSI 5 – Communication between the devices (IEC 61850-GOOSE) – Synchrophasor protocol The modules can be operated with or without an integrated switch.
Page 133
Plug-In Modules 4.2 Communication Modules Plug-In Module 2 x optical serial, 820 nm, ST connector, ● 2 km via 62.5/125 μm multimode optical fiber 2 x electrical Ethernet 100 Mbit/s, RJ45, ● 20 m 2 x optical Ethernet 100 Mbit/s, ●...
Page 134
Plug-In Modules 4.2 Communication Modules Plug-In Module 2 x optical serial, bidirectional via ● 1 common optical fiber, 1550 nm/ 1300 nm (Tx/Rx), 2 x simplex LC plugs, 40 km via 9/125 μm singlemode optical fiber Applications DIGSI 5 Protocol ●...
The RS485 interface in devices of the SIPROTEC 4 series is a D-Sub 9 connection with a connected terminal resistor. If you connect devices from the SIPROTEC 5 series with devices from the SIPROTEC 4 series, then use a Y adaptor with the order designation 7XV5103-2BA00. Complete the connection on the last device with a terminal resistor.
Plug-In Modules 4.2 Communication Modules The preceding figure shows the cabling using the new RJ45 sockets in a simplified format. The serial RS485 bus can be extended by simply connecting Ethernet patch cables from device to device. [dwserma2-030211-05.tif, 1, en_US] Figure 4-6 Redundant Communication with 2 Masters Using RS485 Bus (for Example, Redundant IEC 60870-5-103 Protocol)
Plug-In Modules 4.2 Communication Modules 4.2.3.3 USART-AC-2EL Description Serial asynchronous communication module with 2 independent elec- trical interfaces Product code P1Zxxxxxxxxxx Figure Connector type 4 x RJ45 Baud rate 1.2 kbits/s to 115.2 kbits/s For 1 or 2 protocols or applications IEC 60870-5-103 (1 application per connection) DNP3...
Plug-In Modules 4.2 Communication Modules Laser class 1 as per EN 60825-1/-2 With the use of 62.5 μm/125 μm and 50 μm/125 μm optical fibers Comment: Numerical aperture (NA = sin θ (launch angle)) 4.2.3.5 USART-AE-2FO Description Serial asynchronous or synchronous communication module with 2 independent optical interfaces Product code P1Zxxxxxxxxxx...
Plug-In Modules 4.2 Communication Modules The attainable distance in multimode optical fibers is limited by 2 factors. • Bandwidth length product Typical for 62.5 μm/125 μm optical fibers: 400 MHz x km to 800 MHz x km Typical for 50 μm/125 μm optical fibers: 400 MHz x km to 1200 MHz x km •...
Page 140
Plug-In Modules 4.2 Communication Modules Figure Connector type 1 x duplex LC Wavelength λ = 1300 nm Baud rate 2 Mbit/s for the protection-interface communication Protocol Protection-interface communication Max. line length 60 km for singlemode optical fibers or 8 km with multimode optical fiber Distance 8 km Laser class 1 as per EN 60825-1/-2 With the use of 62.5 μm/125 μm and 50 μm/125 μm optical fibers...
Plug-In Modules 4.2 Communication Modules NOTE If you use the module USART-AG-1LDFO for distances under 25 km, connect 2 attenuators 7XV5107-0AA00. To continue using the Duplex LC plugs, attach both attenuators at one end of the remote connection (see Figure 4-7).
Plug-In Modules 4.2 Communication Modules Figure Connector type 1 x LC Simplex Wavelength λ = 1550 nm Baud rate 2 Mbit/s for the protection-interface communication Protocol Protection-interface communication Max. line length 40 km for singlemode optical fibers Distance 40 km Laser class 1 as per EN 60825-1/-2 With the use of 9 μm/125 μm optical fibers Minimum...
Plug-In Modules 4.2 Communication Modules NOTE If you use the protection-interface module USART-AK-1LDFO for distances under 50 km, then connect 2 attenuators 7XV5107-0AA00. To continue using the Duplex LC plugs, attach both attenuators at one end of the remote connection (see Figure 4-7).
Plug-In Modules 4.2 Communication Modules Figure Connector type 2 x duplex LC Wavelength λ = 1300 nm Baud rate 2 Mbit/s for the protection-interface communication Protocol Protection-interface communication Max. line length 60 km for singlemode optical fibers or 8 km with multimode optical fiber Distance 8 km Laser class 1 as per EN 60825-1/-2 With the use of 62.5 μm/125 μm and 50 μm/125 μm optical fibers...
Plug-In Modules 4.2 Communication Modules Description Protection-interface module for synchronous or asynchronous operation with 2 optical interfaces In particular, a bidirectional data exchange through a single optical fiber is possible with the USART-AY-2LDFO module. Product code P1Zxxxxxxxxxx Figure Connector type 2 x LC Simplex Wavelength λ...
Operation of Ethernet Modules The Ethernet modules of the SIPROTEC 5 series can be operated optionally with or without integrated switch function. This applies for the electrical as well as the optical module. This function can be selected via the SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 147
EN100 modules of the SIPROTEC 4 series. If the RSTP protocol or the HSR protocol is active, the optical modules of the SIPROTEC 4 series and the SIPROTEC 5 series can be operated in a ring. When using SIPROTEC 4 devices with module firmware ≤ V4.05 and SIPROTEC 5 devices, the maximum allow- able number of participants is 30 devices.
Plug-In Modules 4.2 Communication Modules [dwethsw3-090713-01.tif, 2, en_US] Figure 4-9 Operation of Ethernet Modules Without Integrated Switch Function with Single or Redundant Connection to the Switch 4.2.5.2 ETH-BA-2EL Description Communication module for the transmission of Ethernet protocols via 2 electrical interfaces Product code P1Zxxxxxxxxxx Figure...
Plug-In Modules 4.2 Communication Modules 4.2.5.3 ETH-BB-2FO Description Communication module for the transmission of Ethernet protocols via 2 optical interfaces Product code P1Zxxxxxxxxxx Figure Connector type 2 x duplex LC Wavelength λ = 1300 nm Baud rate 100 Mbit/s Protocol DIGSI 5 protocol (secure Web service protocol) IEC 61850 (MMS and GOOSE) DNP3...
Plug-In Modules 4.3 Measuring-Transducer Modules Measuring-Transducer Modules Overview 4.3.1 You can install the measuring-transducer modules in base modules or 1/3 modules (plug-in module positions E and F) and in expansion modules with a CB202 module (plug-in module position M, N, or P). ANAI-CA-4EL 4.3.2 The ports CH1 to CH4 of the measuring-transducer modules are Safety Extra Low Voltage circuits (SELV...
Pulse duration connection test 11 μs Comment: All values in combination with sensors approved by Siemens. Numerical aperture (NA = sin θ (launch angle)) NOTE Laser class 1 is maintained in compliance with EN 60825-1 and EN 60825-2 when using 1 mm polymer optical fibers.
Working on the Device First Steps Expanding Modular Devices Plug-In Modules Arc Sensors for Module: ARC-CD-3FO Battery SDHC Memory Card Installing Current and Voltage Terminals SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Join several on-site operation panels to one another with firm contact. ² Siemens recommends the use of contact washers on painted metal mounting walls. If the mounting wall is not metallic, place a metal layer, for example a metal sheet, between the mounting wall and the on- site operation panels.
Page 155
Working on the Device 5.1 First Steps Safety Notes DANGER Danger during electrical inspection Noncompliance with the safety notes will result in death, severe injury or considerable material damage. Comply with all given safety notes when carrying out the electrical inspection. ²...
Working on the Device 5.2 Expanding Modular Devices Expanding Modular Devices Flush-Mounting Devices 5.2.1 5.2.1.1 Basic Rules for Expansion NOTE Prepare the following tools for the device expansion: • Phillips screwdriver size PZ1 and PZ2 • Screwdriver DIN 4 x 0.8 •...
Working on the Device 5.2 Expanding Modular Devices 5.2.1.2 Expanding 1st Device Row Preparation NOTE Reordered modules are not contained in the original device configuration. Use DIGSI to perform the corre- sponding extension in the Hardware and Protocols Editor. Carry out the steps described in this chapter if you wish to expand an installed device later on with expan- sion modules.
Working on the Device 5.2 Expanding Modular Devices 5.2.1.3 Expanding Devices with 2nd Device Row Preparation NOTE Reordered modules are not contained in the original device configuration. Use DIGSI to perform the corre- sponding extension in the Hardware and Protocols Editor. Carry out the steps described in this chapter if you want to expand an installed device later on with a 2nd device row.
Page 159
Working on the Device 5.2 Expanding Modular Devices [dw_2zauba-020414-01, 2, --_--] Figure 5-2 Expansion with 2nd Device Row Extreme right expansion module of the 1st device row Connecting cable 2nd device row [dw_schiene-020414-01, 1, --_--] Figure 5-3 Angle Rail Angle rail 2 Rubber seals [dw_winkel-020414-01, 1, --_--] Figure 5-4...
Working on the Device 5.2 Expanding Modular Devices Adaptor angle 2 mounting screws Installation and Commissioning Reinstall the plastic screw covers. ² Refasten the terminal blocks and the necessary communication lines. ² Connect the current and voltage blocks of the expansion module. ²...
Working on the Device 5.2 Expanding Modular Devices [dwauize1-040211-01.tif, 2, --_--] Figure 5-5 Device Row Distance frame Mounting bracket Distance frame on base module rotated by 180 5.2.2.2 Expanding 1st Device Row Preparation NOTE Reordered modules are not contained in the original device configuration. Use DIGSI to perform the corre- sponding extension in the Hardware and Protocols Editor.
Page 162
Working on the Device 5.2 Expanding Modular Devices Remove the device completely. ² Assembling the On-Site Operation Panel into One Block [dwaublo1-040211-01.tif, 2, --_--] Figure 5-6 On-Site Operation Panel Fitted on Mounting Bracket Place the 2 mounting brackets intended for expansion in parallel to one another on a flat surface. ²...
Working on the Device 5.2 Expanding Modular Devices Fit the device back onto the wall without fastened on-site operation panels. ² Use the supplied grounding cable to connect the expansion module with the device and reconnect the ² device to service ground. Fasten the connecting cable for the on-site operation panel on the extreme left-hand operation panel of ²...
Page 164
Working on the Device 5.2 Expanding Modular Devices NOTE The distance between the 1st and the 2nd device row must be not more than 80 mm (3.15 in). Install the 2nd device row. ² Unscrew the captive screws from the handle mold. ²...
Working on the Device 5.2 Expanding Modular Devices Sealing plate Device bus of the outermost left expansion module of the 1st device row Installation and Commissioning Reinstall the plastic screw covers. ² Refasten the terminal blocks and the necessary communication lines. ²...
Working on the Device 5.2 Expanding Modular Devices [dwauizei-040211-01.tif, 1, --_--] Figure 5-9 Device Row [dwabosop-040211-01.vsd, 2, en_US] Figure 5-10 Detached On-Site Operation Panel 5.2.3.2 Expanding 1st Device Row Preparation NOTE Reordered modules are not contained in the original device configuration. Use DIGSI to perform the corre- sponding extension in the Hardware and Protocols Editor.
Page 167
Working on the Device 5.2 Expanding Modular Devices If you want to expand the device, then detach it completely. ² If you want to expand the on-site operation panel, then remove the on-site operation panel from the ² installation space. NOTE The device and the on-site operation panel can be expand independently of one another.
Working on the Device 5.3 Plug-In Modules Plug-In Modules Fasteners 5.3.1 The fasteners of the plug-in modules are shown in the following figure regarding the example of an installed module and an empty, covered slot. [le_fxing_elements, 1, --_--] Figure 5-11 Fasteners EMC spring contact Fastening screw...
Working on the Device 5.3 Plug-In Modules CAUTION Exercise caution with laser beams of the optical plug-in modules. Noncompliance with the safety notes can result in medium-severe or slight injuries. Do not look directly into the optical fiber terminals of the active optical plug-in modules, not even with ²...
Page 170
Working on the Device 5.3 Plug-In Modules Preparing Removal DANGER Risk of live voltage when removing the plug-in modules. Noncompliance with the safety notes will result death or severe injuries. Remove plug-in modules on the electrically deactivated device only. ² CAUTION Exercise caution with laser beams of the optical plug-in modules.
Working on the Device 5.3 Plug-In Modules Replacement 5.3.4 Preparing for Replacement DANGER Danger due to live voltage when replacing the plug-in modules. Noncompliance with the safety notes will result in death or severe injuries. Install plug-in modules on the electrically deactivated device only. ²...
Page 172
Working on the Device 5.3 Plug-In Modules NOTE If you have not cabled the optical fiber plug-in modules, then seal the terminals with protective covers. This prevents soiling of the terminals. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Working on the Device 5.4 Arc Sensors for Module: ARC-CD-3FO Arc Sensors for Module: ARC-CD-3FO Point Sensor 5.4.1 5.4.1.1 Description The point sensor detects arcs in the control cabinets of the air-insulated system part. [dwsensap-210314-01, 2, en_US] Figure 5-12 Point Sensor for the Arc-Protection Module: ARC-CD-3FO Optically active zone Sensor head Supply line...
Working on the Device 5.4 Arc Sensors for Module: ARC-CD-3FO [dw_point_sensor_dimensions, 1, en_US] Figure 5-13 Dimensional Drawing of the Point Sensor The sensitivity of the point sensors with line lengths up to 4 m typically begins at 10 kLux. 5.4.1.2 Installation The point sensors are mounted in the different compartments of a control cabinet, see the following figure.
Page 175
As an alternative, you can also fasten the point sensor using a screw (M4). Tighten the screw with a ² torque of 0.2 Nm. Siemens recommends fastening the line to the wall below the point sensor. The line must not be bent or ² stressed in any other way.
In order to warrant safe functioning, the affected sensor must be substituted after detection of an arc. NOTE Hereby, Siemens declares that until now, UL has neither investigated whether the device can detect an arc- protection fault, neither if in case of an arc-protection fault, the safety of personnel and system is guaran- teed.
Page 177
Laser class 1 is maintained in compliance with EN 60825-1 and EN 60825-2 when using 1 mm polymer optical fibers. You need 2 holes (10.0 mm in diameter) in the control cabinet for fastening. Siemens recommends a ² distance of approx. 10 cm.
Page 178
In order to warrant safe functioning, the affected sensor must be substituted after detection of an arc. NOTE Hereby, Siemens declares that until now, UL has neither investigated whether the device can detect an arc- protection fault, neither if in case of an arc-protection fault, the safety of personnel and system is guaran- teed.
Working on the Device 5.5 Battery Battery Description 5.5.1 The battery lies in an externally accessible battery compartment. The battery compartment is located on the rear of the base module. You need not open the device when replacing the battery. If the auxiliary voltage fails, the battery ensures continued operation of the internal clock and storage of certain data (statistic values, values of thermal models) for at least 6 months.
Working on the Device 5.5 Battery Replacing the Battery 5.5.2 Safety Notes NOTICE Exercise caution when replacing the battery. Noncompliance with the specified measures can result in material damage. Replace the battery only with the type specified in the Technical Data. ²...
Reading the data of the SDHC memory card with a PC is not intended. Avoid too frequent insertion cycles! NOTE Use only the original SDHC memory card (ACCESAR) approved by Siemens for the 7KE85 fault recorder. Replacing the SDHC Memory Card De-energize the device.
Page 182
Working on the Device 5.6 SDHC Memory Card Push the holder, push the sealing cap to the back and remove it Unlock the eject lever Remove the SDHC memory card Unpack the new SDHC memory card. ² Do not touch the contacts of the SDHC memory card with your fingers. Insert the new SDHC memory card.
Working on the Device 5.7 Installing Current and Voltage Terminals Installing Current and Voltage Terminals Description 5.7.1 [dwklepos-030211-01.tif, 1, --_--] Figure 5-22 Current and Voltage Terminals with Spring Clips Current-terminal block Voltage-terminal block Spring clips The spring clips fix the terminal block in place. [sc_klepos-020414-01, 1, --_--] Figure 5-23 Voltage Terminal with Screw Connection...
Page 184
Working on the Device 5.7 Installing Current and Voltage Terminals Current-Terminal Block for Non-Modular Devices (7xx82) The following transformers can be installed optionally in a current-terminal block for non-modular devices: • 4 protection-class current transformers • 3 protection-class current transformers and 1 instrument transformer Protection-class current transformers on non-modular devices are transformers with a rated current of 1 A or 5 A and a measuring range of 50 x rated current.
Stranded-wire conductor with bootlace ferrule • Solid conductor Siemens recommends the use of ring-type lugs with the dimensions shown in the following figure. Use copper cables only. The equivalent 50/60/16.7-Hz terminal is used as a re-orderable single part. SIPROTEC 5, Hardware Description, Manual...
Page 186
In order to maintain the insulation route, you must use insulated cable lugs or you must insulate the crimping zone (for example, by using heat-shrink tube insulation) Siemens recommends ring-type lugs of the PIDG series made by Tyco Electronics. Use copper conductors only, at least certified for a temperature of +105 °C. Use prepared solid conductors intended for single or multi-wiring connection, maximum 2 wires per pole, and for usage of ferrules, crimped- on pressure wire connectors (ring-type and pin-type).
The single cable connection type is available for the connection. You can connect solid conductors as well as stranded-wire conductors with and without ferrules as single cables. Siemens recommends the use of twin ferrules of series PN 966 144 made by Tyco Electronics for the connection of 2 single cables.
Working on the Device 5.7 Installing Current and Voltage Terminals Permissible tensile force for each connected 50 N following IEC 60947-1 (VDE 660, part 100) conductor 5.7.3.2 Connections of Voltage Terminals with Screw Connection For the connection of the following modules, Phoenix terminals are used (see Figure 5-23): •...
Technical Data 6.1 Analog Inputs Analog Inputs Current Inputs All current, voltage, and power data are specified as RMS values. Rated frequency f 50 Hz, 60 Hz rated 16.7 Hz (for rail protection devices only) Protection-class current trans- Rated current I Measuring range of Measuring range of the rated...
Page 191
1 pulse per second Pulse duration connection test 11 μs Comment: All values in combination with sensors approved by Siemens. Numerical aperture (NA = sin θ (launch angle)) High-Speed Measuring-Transducer Inputs, Voltage/Current (via IO210, IO212) NOTE Current and voltage must not be connected to a measuring-transducer input at the same time; only either current or voltage may be connected.
Page 192
Technical Data 6.1 Analog Inputs Max. permissible voltage with 300 V respect to ground on the meas- uring inputs Permissible overload DC 20 V continuously DC 60 V continuously (IO210 MT3 terminal point C9) Measurement repetition 62.5 μs Insulation class IO210 ELV (Extra Low Voltage) (acc.
Technical Data 6.2 Supply Voltage Supply Voltage Integrated Power Supply For modular devices, the following printed circuit-board assemblies have a power supply: PS201 – Power supply of the base module and of the 1st device row PS203 – Power supply of the 2nd device row CB202 –...
Page 194
Technical Data 6.2 Supply Voltage Integrated Power Supply Plug-in module for base < 5 W < 6 VA < 6 VA module or plug-in module assembly (for example, communication module) Stored-energy time for auxiliary voltage outage or For V ≥ DC 24 V ≥ 50 ms short circuit, modular devices For V ≥...
Technical Data 6.3 Binary Inputs Binary Inputs Rated voltage range DC 24 V to 250 V The binary inputs of SIPROTEC 5 are bipolar with the exception of the binary inputs on the IO230, the IO231, and the IO233. Current consumption, excited Approx.
Technical Data 6.4 Relay Outputs Relay Outputs Standard Relay (Type S) Switching capacity On: 1000 W/VA Off: 30 VA; 40 W ohmic; 30 W/VA at L/R ≤ 40 ms AC and DC contact voltage 250 V Permissible current per contact (continuous) Permissible current per contact (switching on and 30 A for 1 s (make contact) holding)
Page 197
Technical Data 6.4 Relay Outputs High-Speed Relay with Semiconductor Acceleration (Type HS) Switching capacity On/Off: 1000 W/VA Contact voltage AC 200 V, DC 250 V Permissible current per contact (continuous) Permissible current per contact (switching on and 30 A for 1 s (make contact) holding) Short-time current across closed contact 250 A for 30 ms...
Technical Data 6.5 Light-Emitting Diodes in the On-Site Operation Panel Light-Emitting Diodes in the On-Site Operation Panel Base Module Status Color Quantity Green ERROR Routable (adjustable with DIGSI 5) 2-colored: red or green Only the defined color can be used in operation.
Technical Data 6.6 Communication Interfaces Communication Interfaces User Interface, Front Side You can find a USB connection of type B for the connection to a laptop computer or to a PC on the front side of the device. A protection cover protects this USB connection against pollution and humidity. User interface Connection USB type B...
Page 200
Technical Data 6.6 Communication Interfaces Signal Levels/ Signal Rated Input Voltage, DC Burdens 12 V 24 V 6.0 V 15.8 V 31.0 V IHigh 1.0 V at 1.4 V at 1.9 V at ILow = 0.25 mA = 0.25 mA = 0.25 mA ILow ILow...
Page 201
Flashes when a communication module is inserted in plug-in module position N Table 6-5 Connection Signal Signal Description Siemens-specific assignment Connection using a special cable. Is part of the device delivery. Insulation class SELV (according to IEC 60255-27) Plug-In Modules...
Technical Data 6.7 Electrical Tests Electrical Tests Standards IEC 60255 (product standard) IEEE Std C37.90 UL 508 Additional standards are listed for the individual tests. Installation Requirements Overvoltage category Degree of pollution Protection class Voltage-Immunity and Safety Tests Standards IEC 60255-27 Voltage test (routine test), current measurement inputs, voltage meas- AC 2.5 kV urement inputs, relay outputs...
Page 203
Technical Data 6.7 Electrical Tests Radiated electromagnetic field 20 V/m, 80 MHz/160 MHz/380 MHz/450 MHz/900 MHz immunity 10 V/1.85 GHz/2.15 GHz Spot frequencies 80 % AM IEC 61000-4-3 1 kHz Dwell time ≥ 10 s Electrical fast transient/ 4 kV burst immunity 5 ns/50 ns IEC 61000-4-4...
Page 204
Technical Data 6.7 Electrical Tests Standard for Withstand Capability 20 V/m or Relay Systems to Radiated Elec- 80 MHz to 1 GHz tromagnetic Interference from Pulse modulation Transceivers (Keying test) IEEE Std C37.90.2 Ring wave immunity test 100 kHz (2.5 kV peak value) IEC 61000-4-12 Common-mode and differential-mode test Test duration ≥...
Technical Data 6.8 Mechanical Tests Mechanical Tests Vibration and Shock Stress in Stationary Use Standards IEC 60255-21 and IEC 60068 Vibration Test (sinusoidal) Sinusoidal 10 Hz to 60 Hz: ± 0.075 mm amplitude IEC 60255-21-1, class 2 60 Hz to 150 Hz; 10 m/s acceleration IEC 60068-2-6 Frequency sweep 1 octave/min...
Technical Data 6.9 Environmental Conditions Environmental Conditions Temperatures Type test, in operation -25 °C to +85 °C (in compliance with IEC 60068-2-1 and IEC 60068-2-2, test Ad for 16 h and test Bd for 16 h) Temporarily permissible during operation (tested for -20 °C to +70 °C 96 h) Load conditions for the non-modular devices: With...
Page 207
Technical Data 6.9 Environmental Conditions Humidity Permissible humidity stress ≤ 75 % relative humidity on the annual average (according to IEC 60068-2-30) Up to 93 % relative humidity on 56 days a year Devices subjected to condensation are not to be oper- ated! Arrange the devices so that they are not exposed to direct sunlight or extreme temperature changes.
The protection device is designed for flush mounting in conventional relay rooms and systems such that elec- tromagnetic compatibility (EMC) is ensured with proper flush mounting. Siemens additionally recommends: • Use contactors and relays that work within the same cabinet or the same relay panel with digital protec- tion equipment, only with suitable quenching equipment.
Technical Data 6.11 Reference Conditions and Influencing Variables 6.11 Reference Conditions and Influencing Variables Reference Conditions Measurand current I ± 1 % rated Measurand voltage V ± 1 % rated Frequency f ± 1 % rated Sine waveform, total harmonic distortion ≤...
Technical Data 6.13 Design Data 6.13 Design Data Masses Device Size Weight of the Modular Devices Type of construction Flush-mounting device 4.4 kg 7.2 kg 9.9 kg 12.7 kg 15.5 kg Surface-mounted device with inte- 7.4 kg 11.7 kg 15.9 kg 20.2 kg 24.5 kg grated on-site operation panel...
Page 212
Technical Data 6.13 Design Data Type of Width over all x Height over all x Depth (in Inches) Construction (Maximum Dimensions) Surface- 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x mounted device 314 mm x 314 mm x 314 mm x 314 mm x...
Page 213
Technical Data 6.13 Design Data Tightening Torques for Terminal Screws Type of Line Current Terminal Voltage Terminal with Voltage Terminal with Spring-Loaded Terminals Screw Connection (also see Figure 5-22) (also see Figure 5-22) (also see Figure 5-23) Stranded wires with ring- 2.7 Nm No ring-type lug No ring-type lug...
Page 218
Technical Data 6.14 Assembly Dimensions All drillings in the area of the specific device cut-out widths (see Table 6-6) must comply with the dimensions in the corresponding figures. [dw_z2_2-6, 2, en_US] Figure 6-6 Cut-Out Widths and Drilling Pattern – 1/3 Device, 2nd Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 221
Drilling Pattern – 1/1 Devices, 1st and 2nd Device Row Siemens recommends a drilling space of at least 55 mm (2.17 in) between the 1st and 2nd device row. Due to the connecting-cable length, the maximum space may be approx. 80 mm (3.15 in). The length of the cable is 890 mm (35.04 in) from the center of the plug to the center of the plug.
Page 222
Technical Data 6.14 Assembly Dimensions Width of the Assembly Opening in mm (in Inches) 5/6 device (base module with 3 expansion modules) mm (14.61 +0.08 1/1 device (base module with 4 expansion modules) mm (17.56 +0.08 Table 6-7 Variable Housing Widths Dimension a Housing Widths in mm (in Inches) (Total Width: Housing Width + 4.6 mm (0.18 in))
Page 223
Technical Data 6.14 Assembly Dimensions Surface-Mounted Devices with Integrated On-Site Operation Panel (Modular Device) [dwosopin-070211-01.tif, 2, en_US] Figure 6-14 1/3-Surface-Mounted Device with Integrated On-Site Operation Panel, Dimensions from the Side and Front Views NOTE For surface-mounted devices, make sure that the drillings fit for a screw of the size M6. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 224
Technical Data 6.14 Assembly Dimensions [dwbohrge-1_3.vsd, 2, en_US] Figure 6-15 Drilling Pattern of a 1/3 Surface-Mounted Device – 1st Device Row [dwbohrge-1_2.vsd, 2, en_US] Figure 6-16 Drilling Pattern of a 1/2 Surface-Mounted Device – 1st Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 225
Technical Data 6.14 Assembly Dimensions [dwbohrge-2_3.vsd, 2, en_US] Figure 6-17 Drilling Pattern of a 2/3 Surface-Mounted Device – 1st Device Row [dwbohrge-5_6.vsd, 2, en_US] Figure 6-18 Drilling Pattern of a 5/6 Surface-Mounted Device – 1st Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 226
Technical Data 6.14 Assembly Dimensions [dwbohrge-070211-01.tif, 3, en_US] Figure 6-19 Drilling Pattern of a 1/1 Surface-Mounted Device – 1st Device Row [dw_z2_bohr_1-3.vsd, 2, en_US] Figure 6-20 Drilling Pattern of a 1/3 Surface-Mounted Device – 2nd Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 227
Technical Data 6.14 Assembly Dimensions [dw_z2_bohr_1-2.vsd, 2, en_US] Figure 6-21 Drilling Pattern of a 1/2 Surface-Mounted Device – 2nd Device Row [dw_z2_bohr_2-3.vsd, 2, en_US] Figure 6-22 Drilling Pattern of a 2/3 Surface-Mounted Device – 2nd Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 230
Technical Data 6.14 Assembly Dimensions Surface-Mounted Devices with Integrated On-Site Operation Panel (Non-Modular Device) [dw_console side view.vsd, 3, en_US] Figure 6-25 Non-Modular Surface-Mounted Device with Integrated On-Site Operation Panel, Dimensions from the Side and Front Views Surface-Mounted Devices with Integrated On-Site Operation Panel (Non-Modular Device) NOTE For surface-mounted devices, make sure that the drillings fit for a screw of the size M6.
Page 231
Technical Data 6.14 Assembly Dimensions [dw_drilling non modular surface mounting with several consoles, 1, en_US] Figure 6-26 Drilling Pattern of a Non-Modular Surface-Mounted Device - Several Consoles The 149 mm are valid if several mounted consoles are to be mounted next to each other. Surface-Mounted Devices with Detached On-Site Operation Panel You can find more information on the drilling patterns for the devices in section Surface-Mounted Devices...
Page 232
Technical Data 6.14 Assembly Dimensions [dw_z1_osop_1-2, 1, en_US] Figure 6-28 Drilling Pattern of the On-Site Operation Panel of the 1/2 Device [dw_z1_osop_2-3, 1, en_US] Figure 6-29 Drilling Pattern of the On-Site Operation Panel of the 2/3 Device SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 233
Technical Data 6.14 Assembly Dimensions [dw_z1_osop_5-6, 1, en_US] Figure 6-30 Drilling Pattern of the On-Site Operation Panel of the 5/6 Device [dw_z1_osop_1-1, 1, en_US] Figure 6-31 Drilling Pattern of the On-Site Operation Panel of the 1/1 Device SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Page 234
Technical Data 6.14 Assembly Dimensions [dwosopab-070211-01.tif, 2, en_US] Figure 6-32 Surface-Mounted Device with Detached On-Site Operation Panel, Dimensions in the Side and Front Views Refer to Table 6-7. for the variable dimension a. The drilling patterns correspond to the figures Figure 6-15 Figure 6-24.
Technical Data 6.15 Modular Device Name Plate 6.15 Modular Device Name Plate In the following table, the name plate of a modular device is explained as an example. The name plate is located on the device. 7SJ85 Device type or, in the case of expansion modules, designa- tion of the printed circuit board assembly Overcurrent Protection Product group...
Technical Data 6.16 Name Plate of Non-Modular Devices (7xx82) 6.16 Name Plate of Non-Modular Devices (7xx82) In the following table, the name plate of a non-modular device is explained as an example. The name plate is located on the device. 7SJ82 Device type Overcurrent Protection...
Technical Data 6.17 Name Plate, UL Approval, Base Module and 1/3 Base Module 6.17 Name Plate, UL Approval, Base Module and 1/3 Base Module UL approved for Canada and the USA IND. CONT. EQ. Industrial controller 69CA Approval number : max. 70 °C normal op. The ambient temperature must not exceed 70 °C or 158 °F Surr during normal operation.
The ambient temperature must not exceed 70 °C or 158 °F Surr during normal operation. Listed accessory for use with manufacturer´s Approved accessory for use with a protection device from protection relay. Siemens SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-C, Edition 10.2017...
Technical Data 6.19 Battery 6.19 Battery Type CR2032 Button cell Lithium Voltage Capacity 230 mAh Average service life of the battery, unpowered after removal of protec- At least 6 months tive film Service life of the battery in the activated state with protective film 10 years removed NOTE...
Technical Data 6.20 SDHC Memory Card 6.20 SDHC Memory Card NOTE You can use only Siemens SDHC memory cards. Capacity 16 GB Performance class ≥ Class 10 Temperature range -40 °C to +85 °C Flash type Dimensions Width x Height x Depth (in Inches) SDHC memory card 24 mm x 32 mm x 2.1 mm (0.94 x 1.26 x 0.08)
Ordering Information 7.1 Ordering Spare Parts and Accessories Ordering Spare Parts and Accessories Order Configurator and Order Options 7.1.1 Order Configurator The order configurator assists you in the selection of SIPROTEC 5 products. The order configurator is a Web application that can be used with any browser. The order configurator can be used to configure complete devices or individual components, such as communication modules, expansion modules, or other accessories.
Page 245
Ordering Information 7.1 Ordering Spare Parts and Accessories Group Accessories Terminal Type A current terminal, 3 x protection and 1 x measurement (for modular devices) Terminal Type A current terminal, 4 x measurement (for modular devices) Terminal Type B current terminal, 4 x protection (for non-modular devices) Terminal Type B current terminal, 3 x protection and 1 x measurement...
Page 246
Ordering Information 7.1 Ordering Spare Parts and Accessories Group Accessories Sensors for arc protection Point sensor with line length of 15 m Sensors for arc protection Point sensor with line length of 20 m Sensors for arc protection Point sensor with line length of 35 m Sensors for arc protection Line sensor, length 3 m Sensors for arc protection...
Glossary Control display The control display becomes visible for devices with a large display after pressing the Control key. The diagram contains the switching devices to be controlled in the feeder. The control display serves for implementing switching operations. Specification of this diagram forms part of configuring. DCF77 The precise official time is determined in Germany by the Physikalisch-Technische Bundesanstalt PTB in Bruns- wick.
Index Activating the battery 154 Device structure Arc protection Base module 20 Installing the line sensor 176 Expansion module 24 Installing the point sensor 174 Dimensions 211, 240 Line sensor 176 Display elements 38 Plug-in module 151 Expansion module 40 Point sensor 173 On-site operation panel with push-button func- Assembly dimensions...
Page 254
Index LEDs 201 SDHC memory card Data 240 Replacement 181 Secure Digital High Capacity 181 Measuring-Transducer Module 150 Spring clip 183 Modular systems 17 Standards 202 Surface-mounted device with 2nd device row Expanding 163 Surface-mounted device with detached on-site operation panel 34 Expanding 165 On-site operation panel...