Operating The Base Station Controller - LG PQCSA001T0 Owners & Installation Manual

Air conditioner base controller
Table of Contents

Advertisement

Product setting

Operating the base station controller

I Setting the running mode, 3.5RT and 5.0RT running mode
• It is the run setting mode due to the added operation mode of LG Telecom.
• There are three setting modes such as normal auto rotary, 3.5RT and 5.0RT operation.
• Press "Mode" button (9 times at the initial setting mode) to display "MODE SELECT" on the LCD.
• Press Up( ) or Down( ) button to set the desired setting.
It is set by the order of Auto Rotary -> 3.5RT -> 5.0Rt -> Auto Rotary.
Made Select Setting
AUTO Rotary Mode
Made Select Setting
Made Select Setting
I Air Conditioner (#1 and #2) OnTime setting
• Set the air conditioner OnTime only at 3.5 RT and 5.0 RT from the MODE SELECT Setting.
Press Up( ) or Down( ) button to set the desired setting.
It is set by 1 minute. (The setting range is 10~300 minutes.)
Aircon OnTime 3.5RT
Setting 180 min
• 3.5 RT is displayed when 3.5 RT is set at the
MODE SELECT Setting or 5.0 RT when 5.0 RT is
set.
20 Air conditioner Base controller
3.5 RT
5.0 RT
[MODE SELECT]
➲ The default value is AUTO ROTARY.
➲ Normal rotary operation mode
[Select MODE 3.5 RT]
[ MODE SELECT ]
Set the air conditioner OnTime only at 3.5 RT
and 5.0 RT from the MODE SELECT Setting.
Press Up( ) or Down( ) button to set the
desired setting.
It is set by 1 minute.
➲ The default value - 3.5 RT: 180 min.
➲ The setting range : 10 ~ 300 min
5.0 RT: 30 min