Commercial Fire and Burglary ......................i General Requirements ............................ix Programming Field Settings for UL864 Compliance..................ix SECTION 1............................1-1 SIA Installations .............................1-1 About the VISTA-128FBPN..........................1-1 Features ................................1-1 Guidelines for Wiring a System ........................1-3 SECTION 2............................2-1 Theory of Partitioning.............................2-1 Setting-Up a Partitioned System ........................2-1...
Page 4
Table of Contents Zone Response Type Definitions........................4-6 Zone Input Type Definitions...........................4-8 Programming for Communicator ........................4-9 SECTION 5............................5-1 About Data Field Programming ........................5-1 Programming Data Fields ..........................5-1 SECTION 6............................6-1 Time Window Definitions ..........................6-2 Open/Close Schedules Definitions........................6-3 Scheduling Menu Mode...........................6-4 Time Windows ..............................6-5 Daily Open/Close Schedules ...........................6-6 Holiday Schedules ............................6-6...
Page 5
Table of Contents UL864/NFPA Local Fire ..........................A-1 UL864/NFPA Central Station and Remote Station Fire ................A-1 Commercial Burglary Requirements ......................A-1 UL609 Local Mercantile Premises/Local Mercantile Safe & Vault ............A-2 UL365 Police Station Connected Burglar Alarm ..................A-2 UL1610 Central Station Burglary Alarm .....................
1 = YES 0 = NO 0 ✴ Additional system options are programmed via data fields, which are indicated by a “star” ( ✴ ) followed by the data field number. PRODUCT MODEL NUMBERS: Unless noted otherwise, references to specific model numbers represent Honeywell products.
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Requirements The VISTA-128FBPN control panels provide features that allow the system to meet UL864 Commercial Fire requirements. To meet these requirements, follow the guidelines outlined in this section.
Page 10
Possible settings Program feature or option Permitted in Settings permitted in UL 864 UL864? Y/N Enter 0001-9999 for the test Must be set to “0024” 27 TEST REPORT report interval in hours. (Maximum 24 hours) INTERVAL Enter 0000 for test reporting. 0 = disable 28 POWERUP IN Must be set to “1”...
Page 11
Possible settings Program feature or option Permitted in Settings permitted in UL 864 UL864? Y/N Enter 02–15 times 2 hours (4– 1 30 RF RECEIVER Maximum is 02 (4 hours) for 30 hours) fire installations. SUPERVISION CHECK- Enter 00 to disable receiver IN INTERVAL supervision Enter 02–15 times 2 hours (4–...
Page 12
Possible settings Program feature or option Permitted in Settings permitted in UL 864 UL864? Y/N 0 = disable 2 21 SUPERVISION Must be set to “00000” 1 = enable (disable). PULSES FOR COMMUNICATIONS DEVICE 0 = disable 2 22 DISPLAY FIRE Must be set to “0”...
Page 13
Possible settings Program feature or option Permitted in Settings permitted in UL 864 UL864? Y/N Enter 01-15 multiplied by 2 3 60 BELL 2 & AUX Must be set to “3” (Minimum minutes. of 6 minutes). RELAY TIMEOUT 00 = no timeout. 0 = disable 3 82 ENABLE Must be set to “0”...
Page 14
Item Feature Range Shipping SIA Requirement* Default 1*61 Abort Verify 0 = Disable Enabled Enabled 1 = Enable Zone Auto Stay Arm or 0 = Disable 1 (Enabled) Enabled Programming Occupied Premises 1 = Enable Auto Stay Zone, Zone type 04 has this feature enabled by default...
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About the VISTA-128FBPN The VISTA-128FBPN is an 8-partition, UL Listed commercial fire and burglary control panel with the following features: •...
Page 16
128 zones, as well as openings and closings for all 150 users. This requires central stations to be equipped with the MX8000 receiver to fully support all new VISTA-128FBPN report codes. If you need to update your MX8000 receiver, contact your distributor.
Guidelines for Wiring a System The installer must keep certain guidelines in mind while installing a system. The Vista-128FBPN contains an ECP bus and a polling loop bus for connecting Fire and Burglary devices. When installing a Fire ONLY system or Burglary ONLY system both busses may be used interchangeably.
S E C T I O N Partitioning • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Theory of Partitioning This system provides the ability to arm and disarm up to 8 different areas, as if each had its own control.
Page 20
VISTA-128FBPN Installation and Setup Guide The Common Lobby feature employs logic for automatic arming and disarming of the common lobby. Two programming fields determine the way the common lobby will react relative to the status of other partitions. They are: 1*18 Affects Lobby and 1*19 Arms Lobby.
Section 2 – Partitioning Sequence #2: Office 1 Office 2 Lobby Action User #2: (Armed) Disarms Disarms User #1: Disarms (Disarmed) (No change) User #2: (Disarmed) Arms No Change User #1: Arms (Armed) No Change Notice that in sequence #1, because Office #2 was the last to arm, the lobby also armed (Office #2 is programmed to affect and arm the lobby).
Page 22
VISTA-128FBPN Installation and Setup Guide The following is a typical display: S Y S T E M 1 2 3 4 5 6 7 8 S T A T U S R R N N A T B Possible status indications include:...
S E C T I O N Installing the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring the control panel and all the peripheral devices.
VISTA-128FBPN Installation and Setup Guide RUN BELL WIRES IN CONDUIT PLUG THIS KNOCKOUT TO PLUG AN UNUSED KNOCKOUT OPENING, REMOVE KNOCKOUT AND INSTALL A PAIR OF DISC PLUGS AND A CARRIAGE BOLT AS SHOWN. BOARD CABINET PLATE DISC PLUGS (DIMPLES IN DISC...
Section 3 - Installing the Control NOTES: Installing the Control's Circuit Board • Make sure that the tabs on the side of the plate did To install the circuit board in the cabinet, perform the not pop out during shipping and are inserted into following steps: the appropriate slots.
Figure 3-6. ECP Isolator Wiring Installing External Sounders The VISTA-128FBPN provides two Notification Appliance Circuits for operating fire and burglary alarm notification appliances. Each circuit is rated as Special Application for Fire and 10VDC – 14VDC, 1.7A max. power-limited for Burglary.
Page 27
Section 3 - Installing the Control You may use a Commercial Fire Listed 24VDC Power Supply to convert one or both Vista-128FBPN 12VDC, 1.7A style-Y supervised Special Application Notification Appliance Circuits to 24V, style-Y supervised, Special Application Notification Appliance Circuits.
Page 28
VISTA-128FBPN Installation and Setup Guide ALARM INDICATING DEVICE TYPE MANUFACTURER MODEL # 2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, White SYSTEM SENSOR P2WH 4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red SYSTEM SENSOR 4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red...
Page 29
Section 3 - Installing the Control Table 3-1: BELL 1 AND BELL 2 MAXIMUM DEVICE RATING NOTE: To use this table, the device Candela Setting and Horn Setting MUST match what is listed in the Table. Alarm Indicating Candela Max # of Device Type Model Setting...
VISTA-128FBPN Installation and Setup Guide Auxiliary Relay Connections The VISTA-128FBPN provides a built-in Form C relay with contacts rated at 28VAC/VDC, 2.8A. The relay may be ✳ programmed (field 3 61) for one of the following functions: • Alarm Activation •...
Section 3 - Installing the Control Telephone Line Connections The VISTA-128FBPN provides one main built-in dialer for communication to the central station and one optional 5140DLM Backup Dialer, both supervised for voltage and current on the phone lines. Do not connect the system to telephone lines that require ground start service.
VISTA-128FBPN Installation and Setup Guide Reporting Formats The system is shipped defaulted for Contact ID format. It is the only format capable of uniquely reporting all 128 zones, as well as openings and closings for all 150 users. This requires central stations to be equipped with the MX8000 receiver.
Section 3 - Installing the Control • These smoke detectors are UL Listed for use with the VISTA-128FBPN and are the only 2-wire smoke detectors that may be used. • A combination of heat detectors and smoke detectors is not permitted on a zone programmed for fire verification.
Zone 6 Tamper Configuration Zone 6 may be used as a tamper loop for the Vista-128FBPN Cabinet Door Tamper Switch. Assign zone 6 to a burglary partition. Program it for day trouble/night alarm (zone type 5) when only one burglary partition is used.
Section 3 - Installing the Control GLASSBREAK DETECTOR ZONE 8 2000 LATCHING TYPE GLASS OHMS BREAK DETECTOR LOOP EOLR Figure 3-12. Wiring Latching Glassbreaks to Zone 8 • The alarm current provided by zone 8 supports only one glassbreak detector in the alarmed state. •...
When a star configuration is used, the total length of all wire runs combined cannot exceed 4000 ft (2000 ft. if you are using unshielded wire in conduit or shielded wire). • The 4190SN right loop must not be used, and the left loop must be EOLR-supervised. • The 4297 must be powered from the VISTA-128FBPN Auxiliary Power Output. 3-14...
Page 37
Section 3 - Installing the Control Compatible Polling Loop Devices Model Number Type 4297 Extender Module 4208SN 8 Zone V-Plex Interface 4208SNF 8 Zone V-Plex Class A Interface 269SN V-Plex Holdup Switch 5192SD Photoelectric Smoke Detector Devices 5192SDT Photoelectric Smoke Detector w/Heat Detector 5193SD Photoelectric Smoke Detector Device 5193SDT...
Refer to Figures 3-16 and 3-17, to follow. DO NOT use the 4197 Polling Loop Extender module with the VISTA-128FBPN. Be sure to include the total current drawn on the polling loop when figuring the total auxiliary load on the panel’s power supply.
Section 3 - Installing the Control TO PANEL AUX POWER • DO NOT CONNECT 4297 MODULES IN EXTENSION POLLING LOOP #1 SERIES (i.e., DO NOT CONNECT ONE MODULE'S EXTENSION LOOP TO ANOTHER MODULE'S INPUT LOOP.) V-PLEX BURG 4297 DEVICE DEVICES CLASS B, STYLE 3 CONTROL PANEL INPUT POLLING LOOP...
Page 40
VISTA-128FBPN Installation and Setup Guide A response type 19 (24-Hour Trouble) must be programmed for zones 990 (1 receiver) and 988 (2 receiver) for UL installations. • The 5881ENHC receiver contains front and back tampers that permit its use in commercial burglary installations.
Section 3 - Installing the Control SCREW 5881ENHC-001-V0 Figure 3-18: Installing the 5881ENHC with Tamper Protection ANTENNAS TO CONTROL'S REMOTE KEYPAD CONNECTION POINTS. EACH RECEIVER MUST BE ON INDIVIDUAL HOME RUN. INSERT IN USE MAX. of 220 ft. [67m of #22 (0.64mm) CIRCUIT RIGHT-HAND WIRE or 550 ft.
Page 42
VISTA-128FBPN Installation and Setup Guide Transmitter Input Types All transmitters have one or more unique factory-assigned input (loop) codes. Transmitters can be programmed as one of the following types: Type Description RM (RF Motion) Sends periodic check-in signals, fault and low-battery signals. The control panel automatically restores the zone to “ready”...
Installing Output Devices The VISTA-128FBPN supports up to 96 outputs. Each device must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP). The 4204, 4204CF, and/or 4101SN may be used as output devices.
Connect the device to the polling loop, terminals 28 (+) and 29 (-). Be sure to observe polarity. Installing a Remote Keyswitch A UL-Listed remote keyswitch, such as the Honeywell 4146, can be used for remote arming/disarming of the burglary part of the system and for silencing alarms. The keyswitch operates in only one particular partition.
Section 3 - Installing the Control LED Indications Green Indication Disarmed & Ready Disarmed & Not Ready On Steady Armed Away Slow Flash Armed Stay Rapid Flash Alarm Memory ✳ The keyswitch reports as user 0, if Open/Close reporting is enabled in field Keyswitch Tamper Operation For UL Commercial Burglary installations, the tamper switch must be wired to zone 6, see Figure 3-23).
11 is not, zone 10 will report via the communications device, but zone 11 will not. Messages are transmitted from the VISTA-128FBPN to the communications device on a “first in/first out” basis. If events occur at the same time, they are transmitted in order of priority. The priority from most to least important is : Fire Alarms, Panic Alarms, Burglary Alarms, Fire Troubles, Non-Fire Troubles, Bypasses, Openings/Closings, Test messages, and all other types of reports.
Section 3 - Installing the Control Installing the Communicator To install the communications device, perform the following steps: Step Action Mount the communicator according to the instructions that accompany the Communicator. Connect the data in/out terminals and voltage input terminals of the communicator to the control’s keypad connection points, terminals 11, 12, 13 and 14.
Action Remove the front cover of the enclosure. Mount the enclosure to the wall near the VISTA-128FBPN control panel. The enclosure has four mounting holes on its back surface for this purpose. Run 120VAC wiring to the enclosure in conduit. A dedicated circuit must be used.
Section 3 - Installing the Control Determining the Control’s Power Supply Load In Worksheet 1, enter devices used on the polling In Worksheet 2, enter devices used on Auxiliary loop. Calculate total current draw on the polling Power 1. Calculate standby and alarm currents, loop.
Page 50
(pin 5 on keypad port 2) 400mA max 1.7A max. Worksheet 6: Total VISTA-128FBPN Current Load In Worksheet 4, enter devices connected to the Total Current Bell 1 Output. Calculate alarm currents, then add to get the Bell 1 Output current subtotal.
10 minutes every 4 hours, beginning 4 hours after exiting Programming mode. In addition, entry into the Test mode initiates a battery test. The VISTA-128FBPN also runs a 5-second battery test every 60 seconds to check if the battery is connected.
VISTA-128FBPN Installation and Setup Guide NOTE: WHEN CONNECTING BATTERIES IN PARALLEL: BATTERY TABS USE THE 2nd PAIR OF BATTERY - USE BATTERIES FROM THE SAME MANUFACTURER AND TABS AND THE 2nd PAIR OF WITH THE SAME VOLTAGE AND CAPACITY RATING.
VISTA-128FBPN Installation and Setup Guide NOTE: If the number of digits that you enter in a data The partition-specific programming fields are automatically skipped when programming the field is fewer than the maximum permitted (for global fields. If the system has only 1 partition,...
Page 55
Section 4 – Programming Below are the main menu selections. For details refer to the VISTA-128FBPN Programming Guide. MAIN MENU OPTIONS For programming the following: ZONE PROG? • Zone Number 1 = YES 0 = NO • Zone Response Type •...
Quits Menu Mode and goes back to Data Field Programming Mode, if entered at first prompt of each main menu option. Zone Number Designations The VISTA-128FBPN supports up to 128 zones of Zone Index hardwire, polling loop and/or wireless protection, The zones are designated as follows: distributed among up to 8 partitions.
Page 57
Section 4 – Programming Communication Defaults PRIMARY FORMAT DUAL REPORTING ADEMCO Contact ID LOW SPEED FORMAT (Prim) [0] STANDARD/EXPANDED REPORT PRIMARY ADEMCO Low Speed SECONDARY FORMAT ADEMCO Contact ID standard Alarm Rstr Bypass Trbl Opn/Cls Low Bat LOW SPEED FORMAT (Sec.) [0] ADEMCO Low Speed STANDARD/EXPANDED REPORT SECONDARY CHECKSUM VERIFICATION [0]...
VISTA-128FBPN Installation and Setup Guide Zone Response Type Definitions Each zone must be assigned a zone type, which defines Assign this zone type to a zone that contains a foil- the way in which the system responds to faults in that protected door or window (such as in a store), or to a zone.
Page 59
Section 4 – Programming Type 20: Arm-STAY (5800 Series devices only) Type 14: CO Detector Alarm Causes the system to arm in the STAY mode when the Sends a report to the central station and displays a CO zone is activated. text message at the keyboard.
VISTA-128FBPN Installation and Setup Guide Zone Input Type Definitions Type 05 Unsupervised Button RF (BR) Each zone must be assigned an input type, which defines the where the system will “look” for status of Select for 5800 Series transmitters specifically designed the zone (RF receiver, polling loop, etc.).
Section 4 – Programming Using a Relay to Unlock a Door This control can be programmed so that a user can Step Action trigger a relay for 2 seconds (e.g., to unlock a door) by Enter Output Programming in the #93 Menu entering the User Code + [ 0 ].
Page 62
VISTA-128FBPN Installation and Setup Guide 4-10...
S E C T I O N Data Field Descriptions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order.
Page 64
VISTA-128FBPN Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Entry delay defines the delay time that allows users to re-enter the premises Entry Delay #1 (partition-specific) through a door that has been programmed as an entry delay door and disarm Enter 02-15 multiplied by 15 seconds.
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION If enabled, randomizes AC loss reporting within the selected time after an Randomize AC Loss Report actual AC loss. 0 = within 2 minutes 1 = 10-40 minutes If disabled (0), AC loss reporting about 2 minutes after actual AC loss.
Page 66
VISTA-128FBPN Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Select the dialing method for the main dialer. Main Dialer TouchTone or Rotary Dial 0 = rotary 1 = touchtone If you select TouchTone, make sure the subscriber has requested and is paying for TouchTone service. Note that whether or not TouchTone dialing for call placement is permitted, communication by the use of DTMF signaling (ADEMCO High Speed) will still take place.
Page 67
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION If EOLR supervision is selected, end-of-line resistors must be used on zones Normally Closed or EOLR (Zones 3-8. 3-8) If N.C. loops is selected, end-of-line resistors cannot be used and only 0 = EOLR supervision normally closed devices must be used.
Page 68
VISTA-128FBPN Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION This field has six entries as follows: Alarm, Restore, Bypass, Trouble, Standard/Expanded Reporting Open/Close, Low Battery. If enabled, expanded reports are sent to the Primary primary phone number if low speed format is selected in field *45.
Page 69
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION This field has eight entries, one for each zone type. Select the zone types that Zone Type Restores for Zone will send Restore reports. Types 1-8 0 = disable 1 = enable This field has three entries, one for each zone type.
Page 70
VISTA-128FBPN Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Zone Bypass After Disarm 1*11 Enter 1 for each partition in which zones will remain bypassed after disarm. 0 = disable NOTES: 1 = enable For each partition in which field 1✳11 is enabled, the USER CODE + OFF will no longer unbypass zones.
Page 71
Section 5 – Data Field Descriptions Cross Zoning is designed so that a combination of two zones must be faulted within a 5-minute period of each other to cause an alarm on either zone. This prevents momentary faults from one of the zones from causing an alarm condition. You can select four "sets"...
Page 72
VISTA-128FBPN Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Select the check-in monitoring interval for the RF transmitters. RF Transmitter Check-in Interval 1*31 Failure of an individual transmitter to send a supervision signal within the time Enter 02-15 times 2 hours (4-30 hours).
Page 73
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION Select whether a callback from the control panel is required for downloading. Disable Download Callback 1*53 0 = callback required Must be set to “0” for Commercial Fire and Burglary installations. 1 = no callback required European Date Format Select the date format for display in the event log.
Page 74
VISTA-128FBPN Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION If enabled, the assigned relay closes for 2 seconds when the user enters his Control Relay (partition-specific) 1*76 code and presses 0. 01-96 = relay number 00 = relay not used.
Page 75
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION If enabled, Open/Close reports are sent only if the openings/closings occur Open/Close Reports by 2*09 outside the arm and disarm windows. Exception (partition-specific) NOTES: 0 = disable Open reports are also suppressed during the closing window in order to 1 = enable prevent false alarms if the user arms the system, then re-enters the premises, for example to retrieve a forgotten item.
VISTA-128FBPN Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Check or TRBL Display Select whether the system should display CHECK or TRBL when a trouble 3*00 condition occurs. 0 = CHECK 1 = TRBL ✳ If enabled, the system locks the display on the first fire alarm. Press...
Page 77
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION Auxiliary Input Alternate If enabled, pins 5 and 9 on the J2 connector function as RS232 output and 3*19 input, respectively. If disabled, they function as fire alarm trigger and Function Enable communications device Xmit Okay.
Page 78
VISTA-128FBPN Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION This field has two entries, one for bell 2 and one for the auxiliary relay. If Enable Bell 2 & Auxiliary Relay 3*59 enabled, the system produces chime annunciation on the output.
VISTA-128FBPN Installation and Setup Guide Exception Reports Time-Driven Events This option allows the reporting of openings and The system can automatically activate and de-activate closings to the central station only if the arming and relays at predetermined times to turn lights or other disarming occurs outside of the predetermined opening devices on and off.
Section 6 – Scheduling Options Open/Close Schedules Definitions General Additional Schedules The open/close scheduling is controlled by one of three Additional opening and closing schedules can be schedules. Each schedule consists of one time window programmed using the Time-Driven Event for openings and one time window for closings.
VISTA-128FBPN Installation and Setup Guide Scheduling Menu Mode The #80 Scheduling Menu Mode is used to program Steps to Program Scheduling Options most of the scheduling and timed-event options. Enter Installer Code + [#] + [8] + [0] from the normal This section contains examples of the operating mode.
Section 6 – Scheduling Options PROMPT EXPLANATION Enter 1 to program access schedules. Refer to Limitation of Access Schedules Programming later in this Access Sched. ? section for detailed procedures. 1 = YES 0 = NO Enter 0 to move to the “Quit?” prompt. Enter 1 to quit #80 Scheduling Menu Mode and return to normal operating mode.
VISTA-128FBPN Installation and Setup Guide Open/Close Schedule Worksheet Daily Open/Close Schedules The following worksheet is an example of the worksheet Each partition can be assigned one daily open/close found in the Programming Guide. Write the previously schedule, plus a holiday schedule. Temporary...
Section 6 – Scheduling Options Holiday Schedule Worksheet The following worksheet is an example of the worksheet found in the Programming Guide. Partition Month/Day 3…16 Holiday Schedule Programming After entering Scheduling Menu Mode, press [0] until the “Holidays ?” prompt appears. PROMPT EXPLANATION Enter 1 to program holiday schedules.
Page 86
VISTA-128FBPN Installation and Setup Guide Open/Close Windows Enter the schedule number (01-20) and time window number (01-20), and note the day of the Action Code Action Action Specifier week the action is desired. Enable Opening Window by Partition(s) partition Enter the code for the desired action and action specifier.
Page 87
Section 6 – Scheduling Options Time-Driven Event Programming Field *04 must be enabled for randomization. A user The following menu items must first be programmed in must initiate a random schedule by entering one of the Output Programming in the #93 Menu Mode: following sequences: •...
Page 88
VISTA-128FBPN Installation and Setup Guide ACTION CODES EXPLANATION ACTION SPECIFIER 30=Auto bypass – Zone list Actions 30-31 01 ZONE LIST ? 31=Auto unbypass – Zone list If you selected actions 30-31, the prompt at the right appears. Enter the zone ENTER 01-15 list number that contains the zones to be bypassed or unbypassed.
Section 6 – Scheduling Options Limitation of Access Schedules Limitation of Access is a means by which a user’s access The user’s access code is assigned to a group when that code is limited to working during a certain period of user is added to the system.
VISTA-128FBPN Installation and Setup Guide Limitation of Access Schedules Programming To program access schedules enter Scheduling Menu Mode Installer Code + # 80. After entering Scheduling Menu Mode, press [0] until the “Access Sched. ?” prompt appears. PROMPT EXPLANATION Enter 1 to program access schedules.
Page 91
Section 6 – Scheduling Options Temporary Schedule Worksheet Partition/Windows Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window Start Time HH:MM Stop Time HH:MM 2…8 Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window Start Time HH:MM Stop Time HH:MM Temporary Schedules Programming Enter User Code + [#] + 81 to enter this mode.
VISTA-128FBPN Installation and Setup Guide User Scheduling Menu Mode The system provides up to 20 “timers” available to the end user to control output devices. The output devices themselves are programmed into the system by the installer during Output Programming in the #93 Menu Mode. The end user needs only to know the output device number and its alpha descriptor.
S E C T I O N Downloading Primer (Remote Downloading is not a UL Listed feature) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information Downloading allows the operator to remotely access, Access Security...
Page 94
VISTA-128FBPN Installation and Setup Guide • The account number (field ✳32) If Compass does not have an account already created, and the panel is defaulted; the installer enters Code • Primary central station telephone number (field #89, enters the unattended phone number, account ✳33)
Alarms and Trouble responses and reports Only) are disabled during actual uploading or downloading sessions. If you are on-line, The VISTA-128FBPN can be programmed to but not actively uploading or downloading, periodically and automatically call the downloader. all alarms report immediately. All other...
Month of the year (if monthly, quarterly, or yearly is selected) Direct-Wire Downloading The VISTA-128FBPN can be downloaded without using Connector J2 on the main PC board (see the Summary a modem or telephone line by using a 4100SM Serial of Connections diagram on the inside back cover of this Module and Compass Downloading Software.
S E C T I O N Setting the Real-Time Clock • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information This system provides a real-time clock, which must be Use a 6160/6160CR-2 alpha keypad to set the...
Page 98
VISTA-128FBPN Installation and Setup Guide...
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information The VISTA-128FBPN system allows a total of 150 A user code other than the installer code must be security access codes to be allocated.
VISTA-128FBPN Installation and Setup Guide Duress Reporting NOTE: A non-zero report Level 6: Duress Codes code for zone 992 (duress) must be • Sends a silent alarm to a central monitoring station programmed, and partition-specific field *85 if the user is being forced to disarm (or arm) the...
Press 0 (NO) or 1 (YES), depending on whether this user will be allowed to arm more than one Global Arm ? partition via Global Arm prompts (described in the VISTA-128FBPN User Guide). 0 = NO , 1 = YES The keypad now prompts for the user’s access to the next partition.
VISTA-128FBPN Installation and Setup Guide PROMPT EXPLANATION If the user number is from 001-050 this appears. Answer YES (1) to have the system send the XMT USER DATA user’s attributes to all the other control panels that are “linked” to this control. If you answer NO 1 = YES 0 = NO (0), the system displays the following prompt on the next page.
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Battery Test When AC power is present, the VISTA-128FBPN runs a If the VISTA-128FBPN finds that the battery voltage is brief battery test every 60 seconds to determine if there low (less than approximately 11.5V), it initiates a...
VISTA-128FBPN Installation and Setup Guide PROMPT EXPLANATION Enter 1 (YES) to have the system automatically test all polling loop points with a fire response type 9 or 16. AUTO-TEST DET? Other fire zones will have to be tested manually. 0=NO 1=YES Enter 0 (NO) to test every point manually.
Section 10 – Testing the System The system automatically exits the Test mode if there is no activity (no doors or windows are opened and closed, no motion detectors are activated, etc.) for 60 minutes. The system beeps the keypad(s) twice every 15 seconds during the last 5 minutes as a warning that it is about to exit the Test mode and return to normal operation.
VISTA-128FBPN Installation and Setup Guide Trouble Conditions Supervisory Messages Other System Messages Display Description Display Description SUPV + This indicates that a fire supervisory COMM Indicates a failure occurred in the Zone condition exists on the zone number FAILURE telephone communication portion of your Number displayed.
User • Guide supplied. Note your Honeywell customer number and/or company name. In particular, explain the operation of each zone (entry/exit, perimeter, interior, fire, etc.). Be sure the...
Page 108
VISTA-128FBPN Installation and Setup Guide 10-6...
4. The control cabinet must be protected from unauthorized access. This can be done by installing a tamper switch on the cabinet door (supplied with VISTA-128FBPN). Wire the selected device to any EOLR-supervised zone (Zone 1-8). Program this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response.
VISTA-128FBPN Installation and Setup Guide UL609 Local Mercantile Premises/Local Mercantile Safe & Vault 1. All zones must be configured for EOLR supervision (*41=0). If 4190SN V-Plex devices are used, set field *24 to "0" to enable tamper detection. 2. Attach a Listed door tamper switch to protect the cabinet door. Wire the selected device to Zone 6.
Page 111
Appendix A – Regulatory Agency Statements FEDERAL COMMUNICATIONS COMMISSION (FCC) STATEMENTS The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. CLASS B DIGITAL DEVICE STATEMENT NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
Page 112
VISTA-128FBPN Installation and Setup Guide CANADIAN EMISSIONS STATEMENTS This Class B digital apparatus complies with Canadian ICES-003 NOTICE AVIS The Industry Canada Label identifies certified L’étiquette d’Industrie Canada identifie equipment. This certification means that the matériel homologué. Cette étiquette certifie que le equipment meets telecommunications network matériel est conforme aux normes de protection,...
A P P E N D I X Summary of System Commands • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • User Code Add A User Code = User Code + 8 + New User Number + New User’s Code Commands...
Page 114
VISTA-128FBPN Installation and Setup Guide Relay Control Activate Relay for Current Partition = User Code + 0. Commands...
VISTA-128FBPN Installation and Setup Guide Code Definition Code Definition ACS Zone Shunt Fire Walk-Test – Point Not Tested ACS Point Bypass Event Log Reset Vent Zone Bypass Time/Date Reset Communicator Test Program Entry Fire Test Program Exit Listen-In to Follow...
Page 119
Appendix D – Contact ID Codes Alpha Event Description Access Control Events PROG CHANGE Program Change ACZN CHG Access Control Zone Change BAT TST FAIL Battery Test Failure ACS PROG Access Control Program Entry V-PLEX RST V-Plex Restore ACS PRGX Access Control Program Exit RFLB RST RF Low Battery Restore...
Page 120
VISTA-128FBPN Installation and Setup Guide...
Page 122
VISTA-128FBPN Installation and Setup Guide Burglary Trigger for Response Type 8....5-3 Deleting a User Code ..........9-4 Burglary Walk Test..........10-2 DEVICE PROG............Button RF ............Dial Tone Detection ..........5-4 3-21 Bypass Commands ..........6-8 Dial Tone Pause...........5-4 Dialer Operation..........3-11 Dialer Test ............10-1 DIGITAL COMMUNICATOR.........
Page 123
Holiday Schedule Programming ......6-7 Multiple Alarms............5-3 Holiday schedules ..........Multiple Partition Access........9-2 Holiday Schedules ..........6-6 Honeywell 4146..........3-23 No Alarm Response Type 23 ......Normally Closed or EOLR (Zones 2-8) ....5-4 Ignore Expansion Zone Tamper ......5-3 Number of Partitions .........5-12 Installer (User 1) Code Level 0 ......9-1...
Page 125
Temporary Schedules........6-12 Temporary Schedules Programming ....6-13 Test Report Interval..........5-3 Testing The System ..........10-1 View Capabilities ..........Time Driven Events ..........6-2 Vista-128FBPN Current Load ......3-29 Time Driven Events Worksheet ......Time Window Definitions........6-2 Time Windows ..........Time Windows Programming......6-5 Wire Run Length/Gauge........
Page 126
THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced wireless security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a vari- ety of reasons.