Site Power Guidelines
Hardware component(s)
A900-IMA16D (16-port T1/E1 interface module)
A900-IMA32D (32-port T1/E1 interface module)
A900-IMA1Z8S-CX (OC-192 Interface Module +
8-port low rate Interface Module)
A900-IMA48D-C (48 port T1/E1 Interface Module)
A900-IMA48T-C (48 port T3/E3 Interface Module)
A900-IMA4OS (4-port OC-3 interface Module)
A900-IMA8S1Z (8-port 1GE SFP + 1-port 10 GE
interface module)
A900-IMA8T1Z (8-port 1GE RJ-45 Copper + 1 10
GE interface module
A900-IMA2Z (2-port 10 GE interface module)
A900-IMA8Z (8-port 10 Gigabit Ethernet Interface
Module)
A900-IMA1C (1-port 100 Gigabit Ethernet Interface
Module)
A900-IMA2F (2-port 40 Gigabit Ethernet QSFP
Interface Module)
A900-IMASER14A/S (14-port Serial Interface
Module)
A900-IMA6EM (6-port E & M Interface Module)
A900-IMA4C3794 (4-port C37.94 Interface Module)
Electrical Circuit Requirements
Each Cisco ASR 903 Router requires a dedicated electrical circuit. If you equip it with dual power feeds,
provide a separate circuit for each power supply to avoid compromising the power redundancy feature.
The Cisco ASR 903 Routers can be powered by a DC source or an AC source. Ensure that equipment grounding
is present and observe the power strip ratings. Make sure that the total ampere rating of all products plugged
into the power strip does not exceed 80% of the rating.
For more information about the Cisco ASR 903 Router power supply, see
Cisco ASR 903 Aggregation Services Router Hardware Installation Guide
68
Maximum power draw value
14.5 W
18 W
92 W
35 W
52 W
26 W
29 W
27 W
24 W
60 W
60 W
60 W
20 W
20 W
14 W
Power Supply
Preparing for Installation