GE Masoneilan SVI II AP Instruction Manual

GE Masoneilan SVI II AP Instruction Manual

Advanced performance digital positioner

Advertisement

Quick Links

GE Oil & Gas
Masoneilan * SVI * II AP
Advanced Performance Digital Positioner
Bench Quick Start (Rev C)
Instruction Manual
GE Data Classification: Public

Advertisement

loading

Summary of Contents for GE Masoneilan SVI II AP

  • Page 1 GE Oil & Gas Masoneilan * SVI * II AP Advanced Performance Digital Positioner Bench Quick Start (Rev C) Instruction Manual GE Data Classification: Public...
  • Page 2 PROBLEMS ARISE WHICH ARE NOT COVERED SUFFICIENTLY FOR THE CUSTOMER/OPERATOR'S PURPOSES THE MATTER SHOULD BE REFERRED TO GE. THE RIGHTS, OBLIGATIONS AND LIABILITIES OF GE AND THE CUSTOMER/OPERATOR ARE STRICTLY LIMITED TO THOSE EXPRESSLY PROVIDED IN THE CONTRACT RELATING TO THE SUPPLY OF THE EQUIPMENT.
  • Page 3 Autotune on a bench. Additionally, this document also provides guidance on when to run signatures and produce associated reports. This procedure uses GE’s ValVue* 3 software (ver. 3.20 or later) and the SVI II AP DTM (ver. 2.10.1 or later).
  • Page 4: Physical Setup

    Loop Calibrator (with wall power supply and loop test lead wires) and either a USB connector or a serial port connector for your laptop. The setup shown in Figure 1 is a GE product and can be purchased at: https://www.gemeasurement.com/test-calibration/calibrators/ups-iii-loop-calibrator-ma-v ®...
  • Page 5 Minimum tubing diameter 1⁄4" (6 mm x 4 mm) Any other pneumatic accessories are correctly piped without restricting the SVI II AP output(s) to the actuator. Masoneilan SVI II AP Bench Quick Start Manual © 2016 General Electric Company. All rights reserved.
  • Page 6 Communication DTM and install. See “Codewrights HART® Communication DTM” on page 16 for download site. 3. Sign on to ValVue 3 with default values: User name admin. Password ValVue 3. © 2016 General Electric Company. All rights reserved. =GE Oil & Gas...
  • Page 7 ValVue version 3.30 or later and SVI II AP 2.20 or later. For earlier versions continue with manual DTM Library update. Masoneilan SVI II AP Bench Quick Start Manual © 2016 General Electric Company. All rights reserved.
  • Page 8 SVI II AP HART 5, HART 6 or HART 7. Figure 3 DTM Library Management: After Update 6. Click Add Sel and then click OK to close DTM Library Management dialog. © 2016 General Electric Company. All rights reserved. =GE Oil & Gas...
  • Page 9 9. Ensure the Serial Interface pulldown and the Address scan fields are correct. Click Apply and then OK. If device is connected (or powered through DCS), set Master to NOTE Secondary Master. Masoneilan SVI II AP Bench Quick Start Manual © 2016 General Electric Company. All rights reserved.
  • Page 10 12. Click OK to the DTM evaluation period warning, if it appears. The SVI II AP DTM opens. If the SVI II AP DTM doesn’t open automatically: Select the SVI II AP device you added, right-click and select Online Parameter. 10 | © 2016 General Electric Company. All rights reserved. =GE Oil & Gas...
  • Page 11 13. Check that the SVI II AP is connected (see red oval in Figure 7). Figure 7 Connected | 11 Masoneilan SVI II AP Bench Quick Start Manual © 2016 General Electric Company. All rights reserved.
  • Page 12 Upload means to pull data from the SVI II AP and load data into NOTE DTM onto the PC. Download puts data from the DTM into the SVI II 12 | © 2016 General Electric Company. All rights reserved. =GE Oil & Gas...
  • Page 13 For a successful Auto Tune process, the supply pressure must be at least 5 PSI (34.5 kPa) above the spring range. | 13 Masoneilan SVI II AP Bench Quick Start Manual © 2016 General Electric Company. All rights reserved.
  • Page 14 2. Configure the fields on each tab as required and click to move to the next tab. 3. Navigate through to the Device Mode step and click 14 | © 2016 General Electric Company. All rights reserved. =GE Oil & Gas...
  • Page 15 3. Connect the AP wires to next item on order. Click Find New Devices. Go to step 4 of “2. Software Install and Configuration” on page 6 and repeat. | 15 Masoneilan SVI II AP Bench Quick Start Manual © 2016 General Electric Company. All rights reserved.
  • Page 16: Appendix A: Download Instructions

    Appendix A: Download Instructions Masoneilan Software 1. Go to the Download Center (http://www.ge-mcs.com/en/download.html), make selections as shown (Figure 11) and click Search. Figure 11 Download Center: Search for Valve 3 The results appear (Figure 12). Figure 12 Search Results: ValVue 3 16 | ©...
  • Page 17 2. Scroll down to find the specific software program of choice: SVI II AP DTM or ValVue 3. Click the blue link to download. 3. Click I Accept for the terms (Figure 14). Figure 14 Software Terms | 17 Masoneilan SVI II AP Bench Quick Start Manual © 2016 General Electric Company. All rights reserved.
  • Page 18 You must download and install this DTM to use Masoneilan’s HART -based DTM. Go to the link: http://www.codewrights.biz/index.php/en/downloads/software and follow instructions to download and install the CW_CommDTM_HART. 18 | © 2016 General Electric Company. All rights reserved. =GE Oil & Gas...
  • Page 20 Fax: 88+91-11-5-1659635 Fax: 88+65-6861-7172 Fax: 88+1-281-671-1735 Jacksonville, Florida Phone: +1- 844-VALVE-GE www.geoilandgas.com/valves *Denotes a registered trademark of the General Electric Company. Other company names and product names used in this document are the registered trademarks or trademarks of their respective owners.